5 Configuration
Installation manual
14
EHBH/X04+08DA
Daikin Altherma – Low temperature split
4P495266-1 – 2017.06
2
Enter the applicable code for the user permission.
—
▪ Move the cursor from left to right.
▪ Browse through the list of digits and change the
selected digit.
▪ Confirm the pincode and proceed.
Installer pin code
The Installer pin code is
5678
. Additional menu items and installer
settings are now available.
5678
Installer
Advanced user pin code
The Advanced user pin code is
1234
. Additional menu items for the
user are now visible.
User pin code
The User pin code is
0000
.
To access the installer settings
1
Set the user permission level to Installer.
2
Go to [9]: Installer settings.
To modify an overview setting
Example:
Modify [1‑01] from 15 to 20.
All settings can be done using the menu structure. If for any reason it
is required to change a setting using the overview settings, then the
overview settings can be accessed as follows:
1
Set the user permission level to Installer. See
"To
change the user permission level" on page 13
.
—
2
Go to [9.I]: Installer settings > Overview field
settings.
3
Turn the left dial to select the first part of the setting
and confirm by pressing the dial.
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0
1
2
3
4
Turn the left dial to select the second part of the
setting
00
01
15
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
1
5
Turn the right dial to modify the value from 15 to 20.
00
01
20
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
1
6
Press the left dial to confirm the new setting.
7
Press the center button to go back to the home
screen.
INFORMATION
When you change the overview settings and you go back
to the home screen, the user interface will show a popup
screen and request to restart the system.
When confirmed, the system will restart and recent
changes will be applied.
5.2
Configuration wizard
After first power ON of the system, the user interface will guide you
using the configuration wizard. This way you can set the most
important initial settings. This way the unit will be able to run
properly. Afterwards, more detailed settings can be done via the
menu structure if required.
5.2.1
Configuration wizard: Language
#
Code
Description
[7.1]
N/A
Language
5.2.2
Configuration wizard: Time and date
#
Code
Description
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. If you want to change these
settings, you can do this in the menu structure (User
settings > Time/date) once the unit is initialised.
5.2.3
Configuration wizard: System
Indoor unit type
The indoor unit type is displayed, but cannot be adjusted.
Backup heater type
The backup heater is adapted to be connected to most common
European electricity grids. The type of backup heater must be set on
the user interface. For units with a built-in backup heater, the type of
heater can be viewed but not changed.
#
Code
Description
[9.3.1]
[E‑03]
▪ 2: 3V
▪ 3: 6V
▪ 4: 9W
Domestic hot water
This part only applies to systems with a domestic hot water tank
installed.
▪ EHBH/X : an optional domestic hot water tank is available.
Set the following settings according to the actual installation. The
setting determines if the system can prepare domestic hot water or
not, and which tank is used.
In case of EKHWP/HYC, we recommend to set the temperature of
the booster heater NOT higher than 70°C.