Condensate Kit
Table 1
6.3 Downflow/Horizontal Right Installation
IMPORTANT NOTE:
In the downflow application, to prevent
coil pan “sweating”, a downflow kit (DFK) is available through
your local Daikin distributor. The DFK is not supplied with the air
handler and is required by Daikin on all downflow installations.
See Downflow Kit table for the correct DFK and follow the
instructions provided for installation.
DV25PTCB14**
DV31PTCC14**
DV37PTCD14**
DV29PTCB14**
DV37PTCC14**
DV49PTCD14**
DV35PTCB14**
DV59PTCC14**
DV59PTCD14**
DV37PTCB14**
DV33PTCC14**
DV61PTCD14**
DV39PTCC14**
DV49PTCC14**
DFK-C
DFK-D
Downflow Kit
Downflow Kit
Downflow Kit
MODEL LIST FOR DOWNFLOW KITS
DFK-B
Downflow Kit
Table 2
Refer to Figure 6 and 7 for the location of the components
referenced in the following steps.
1. Before inverting the air handler, remove blower access panel
and coil access panel. The coil access panel and tubing
panel may remain screwed together during this procedure.
Remove and retain the seven (7) screws securing the coil
access panel to the cabinet and the six (6) screws securing
the blower access panel to the cabinet.
2. Slide the coil assembly out using the drain pan to pull the
assembly from the cabinet.
NOTE: DO NOT USE MANIFOLDS OR FLOWRATOR TO
PULL THE COIL ASSEMBLY OUT. FAILURE TO DO SO
MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS.
3. Removal of the center support is required on units with 21”
wide cabinet. Remove and retain the two (2) screws that
secure the center support to the cabinet. Remove the center
support.