background image

12

12.4 Electrical Connections – Supply Voltage

IMPORTANT NOTE:

 USE COPPER CONDUCTORS ONLY.

Knockouts are provided on the air handler top panel and 

sides of the cabinet to allow for the entry of the supply voltage 

conductors, as shown in Figure 13. If the knockouts on the 

cabinet sides are used for electrical conduit, an adapter ring 

must be used in order to meet UL1995 safety requirements.  An 

NEC or CEC approved strain relief is to be used at this entry 

point.  Some codes/municipalities require the supply wire to be 

enclosed in conduit.  Consult your local codes.

Side of

Cabinet

Top of

Cabinet

KNOCK-OUT FOR ELECTRICAL CONNECTIONS

Figure 13

12.4.1 Air Handler Only (Non-Heat Kit Models)

The power supply connects to the stripped black and red wires 

contained in the air handler electrical compartment.  Attach the 

supply wires to the  air handler conductors as shown in the unit 

wiring diagram using appropriately sized solderless connectors 

or other NEC or CEC approved means. A ground lug is also 

provided in the electrical compartment. The ground wire from 

the power supply must be connected to this ground lug.

12.4.2 Air Handler - Non-Circuit Breaker Heat Kits

A terminal block is provided with the HKS kit to attach the power 

supply and air handler connections. Follow the HKS Installation 

Manual and wiring diagram for complete wiring details. 

12.4.3 Air Handler With Circuit Breaker Heat Kit

The air handler has a soft plastic cover on the upper access 

panel and can be removed to allow the heater kit circuit breaker 

to be installed.  The circuit breakers have lugs for power supply 

connection. See the HKS Installation Instructions for further 

details. 

12.5 Low Voltage Connections

Several combinations of low voltage schemes are possible, 

depending on the presence of a heat kit and whether the 

heat kit is single-stage or multi-stage, whether the outdoor 

section is an air conditioner or heat pump, and whether the 

system is setup with a communicating or traditional thermostat. 

The 24V-control voltage connects the air handler to the 

room thermostat and condenser.  Low voltage wiring must 

be copper conductors. A minimum of 18 AWG wire must be 

used in installations up to 100’. Low voltage wiring must be 

connected through the top of the cabinet or either side.  See 

the “Thermostat Wiring” section of this manual for typical low 

voltage wiring connections.

13  Achieving 1.4% and 2.0% Airflow Low Leakage 

Rate

Ensure all the gaskets remain intact on all surfaces as shipped 

with the unit. These surfaces are areas between the upper tie 

plate and coil access panel, blower access and coil access 

panels, and between the coil access and filter access panels. 

Ensure upon installation, that the plastic breaker cover is sitting 

flush on the blower access panel and all access panels are 

flush with each other and the cabinet.  With these requirements 

satisfied, the unit achieves less than 1.4% airflow leakage at 0.5 

inch wc static pressure and less than 2% airflow leakage a 1inch 

wc static pressure when tested in accordance with ASHRAE 

Standard 193.

14  Start-Up Procedure

HIGH VOLTAGE!

Disconnect ALL power before servicing or installing this 

unit. Multiple power sources may be present. Failure to 

do so may cause property damage, personal injury or 

death.

 

•  Prior to start-up, ensure that all electrical wires are properly 

sized and all connections are properly tightened.

•  All panels must be in place and secured. For Air Tight 

application, gasket must be positioned at prescribed 

locations to achieve low airflow as stated in section 13.

•  Tubing must be leak free.
•  Condensate line must be trapped and pitched to allow for 

drainage.

•  Low voltage wiring is properly connected.
•  Auxiliary drain is installed when necessary and pitched to 

allow for drainage.

•  Unit is protected from vehicular or other physical damage.
•  Return air is not obtained from, nor are there any return 

air duct joints that are unsealed in, areas where there may 

be objectionable odors, flammable vapors or products of 

combustion such as carbon monoxide (CO), which may 

cause serious personal injury or death.

15  Regular Maintenance

The only item required to be maintained on a regular basis by 

the user is the circulating air filter(s).  Filter should be cleaned or 

replaced regularly, typically once per month.  A certified service 

technician must perform all other services.

HIGH VOLTAGE!

Disconnect ALL power before servicing or installing this 

unit. Multiple power sources may be present. Failure to 

do so may cause property damage, personal injury or 

death.

 

IMPORTANT NOTE:

 If thumb screws are used to access the filter, 

ensure the washer installed on the screw behind the access panel 

remains in place after re-installation.

Summary of Contents for DV PTC 14 Series

Page 1: ...ations 3 4 Replacement Parts 3 5 Pre Installation Considerations 3 5 1 Preparation 3 5 2 System Matches 3 5 3 Interconnecting Tubing 4 5 4 Clearances 4 5 5 Horizontal Applications 4 6 Installation Loc...

Page 2: ...E Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death This product is factory shippe...

Page 3: ...g at the cabinet corners 3 Codes Regulations This product is designed and manufactured to comply with applicable national codes Installation in accordance with such codes and or prevailing local codes...

Page 4: ...hat may become wet such as crawl spaces elevate the unit with a sturdy non porous material In installations that may lead to physical damage i e a garage it is advised to install a protective barrier...

Page 5: ...CB14 DV33PTCC14 DV61PTCD14 DV39PTCC14 DV49PTCC14 DFK C DFK D Downflow Kit Downflow Kit Downflow Kit MODEL LIST FOR DOWNFLOW KITS DFK B Downflow Kit Table 2 Refer to Figure 6 and 7 for the location of...

Page 6: ...Center Support Filter Bracket Filter Access Panel INTERNAL PART TERMINOLOGY Figure 6 Blower Access Panel Coil Access Panel Tubing Panel UV Knockout EXTERNAL PART TERMINOLOGY Figure 7 NOTE If removing...

Page 7: ...t be proportional to the size of the tube Service personnel must use the appropriate heat level for the size of the tube being brazed CAUTION NOTE Refrigerant tubing must be routed to allow adequate a...

Page 8: ...superheat is low adjust TXV valve to 7 to 9 superheat and remove charge to lower the subcooling to 7 to 9 F NOTE Do NOT adjust the charge based on suction pressure unless there is a gross undercharge...

Page 9: ...per field constructed P style trap than is shown in Figure 12 to allow proper drainage and prevent condensate overflow Air Handler 2 75 MIN POSITIVE LIQUID SEAL REQUIRED AT TRAP Drain Connection 2 MIN...

Page 10: ...nit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible with a given air handler No other accessory heat kit besides the HKS series may be installed in thes...

Page 11: ...your unit FIRE HAZARD To avoid the risk of property damage personal injury or fire use only copper conductors CAUTION HIGH VOLTAGE Failure to do so may cause property damage personal injury or death D...

Page 12: ...of the cabinet or either side See the Thermostat Wiring section of this manual for typical low voltage wiring connections 13 Achieving 1 4 and 2 0 Airflow Low Leakage Rate Ensure all the gaskets rema...

Page 13: ...ween Y1 and O for Proper Dehumidification Operation and Proper Ramping Profile Operation W2 Typical Single Stage Cooling with Single Stage Heating Figure 14 Air Handler Integrated Control Module Typic...

Page 14: ...CH Figure 19 Legacy mode use In a legacy system Non communicating this feature is not operational Any auxiliary alarm switch must be used to interrupt the Y1 signal either to the indoor or outdoor uni...

Page 15: ...flow for the cooling system Most cooling systems are designed to work with airflows between 350 and 450 CFM per ton Most manufacturers recommend an airflow of about 400 CFM per ton Example 2 5 tons X...

Page 16: ...R NR NR NR NR NR 1750 NR 25 OFF OFF OFF NR NR NR NR NR NR NR NR NR NR NR 1750 NR Note Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation Within...

Page 17: ...s maximum airflow capability is 2000 CFM and 25 continuous fan speed is selected the continuous fan speed will be 0 25 x 2000 CFM 500 CFM 6 The multi speed circulator blower also offers several custo...

Page 18: ...code from being displayed NOTE For installations not indicated in the preceding Temperature Rise Tables the following formula is to be used TR kW x 3412 x Voltage Correction 1 08 x CFM Where TR Tempe...

Page 19: ...ypically do not return information to the thermostat On the other hand the indoor unit outdoor unit and thermostat comprising a Communicating system communicate digitally with one another It is now a...

Page 20: ...to terminal 1 on indoor unit and thermostat and data line terminal 2 from AC HP must connect to terminal 2 on indoor unit and thermostat Verify wires are not reversed ATTENTION INSTALLER IMPORTANT NO...

Page 21: ...led when necessary and pitched to allow for drainage Drain pan and drain tubing has been leak checked Return and supply ducts are sealed Unit is elevated when installed in a garage or where flammable...

Page 22: ...a 1 data 2 wires Check wire connections at terminal block Verify air handler installation type noncommunicating traditional or communicating Check data 1 data 2 voltages Turn power OFF prior to repair...

Page 23: ...tory NOTE Consecutively repeated faults are shown a maximum of 3 times Submenu Item Model Number MOD NUM Displays the modular blower model number Serial Number SER NUM Displays the modular blower seri...

Page 24: ...ENT TRIP OR LOST ROTOR b5 BLOWER MOTOR ROTOR LOCKED b6 OVER UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP b7 INCOMPLETE PARAMETER SENT TO MOTOR b9 LOW INDOOR AIRFLOW C1 LOW STAGE COOL LEGACY MODE ONLY C...

Page 25: ...ROL LOW VOLTAGE 24V FIELD SPLICE INTERNAL TO FIELD GRND OVERCURRENT BK BLACK OR ORANGE BL BLUE PK PINK GY GRAY RD RED WH WHITE PU PURPLE YL YELLOW BR BROWN COLOR CODES GN GREEN NOTES 1 PLACE RED WIRES...

Page 26: ...ERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING Wiring is subject to change Always refer to the wiring diagram on the unit fo...

Page 27: ...uminum tube and fin evaporator coils Even a one time application of these corrosive chemicals can cause premature aluminum evaporator coil failure Any cleaners that contain corrosive chemicals includi...

Page 28: ...F WB F Heating Supply AirTemperature DB F Temperature Rise DB F DeltaT Difference between Supply and Return Temperatures DB F AirHandler Coil InverterMatched INVERTERAH COILONLY Check EEV and EEV wiri...

Page 29: ...29 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 30: ...30 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 31: ...31 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 32: ...register by following this link https daikincomfort com owner support product registration You can also scan the QR code on the right to be directed to the Product Registration page CUSTOMER FEEDBACK...

Reviews: