Daikin DV PTC 14 Series Installation Instructions Manual Download Page 20

20

System

System 

Operating Mode

Airflow Demand 

Source

Cooling

Air Conditioner

Heating

Air Handler

Continuous Fan

Thermostat

Cooling

Heat Pump

Heat Pump Heating 

Only

Heat Pump

HP + Electric Heat 

Strips

> of Heat Pump or Air 

Handler Demand

Electric Heat Strips 

Only

Air Handler

Continuous Fan

Thermostat

Air Condi 

Air Handler

Heat Pump + Air 

Handler

Figure 32

18.3 Control Wiring

NOTE

: Refer to section Electrical Connections for 208/230 volt 

line connections to the air handler.

NOTE

: A plug connector is provided with the control to make 

thermostat wire connections. Wire nuts are recommended to 

ensure one wire is used for each terminal. Failure to do so may 

result in intermittent operation.

Typical 18 AWG thermostat wire may be used to wire the 

system components. One hundred and fifty (150) feet is the 

maximum length of wirerecommended between indoor unit and 

outdoor unit, or between indoor unit and thermostat.

Only the data lines 1 and 2 are requiried between the indoor and 

outdoor units. A 40VA, 208/230 VAC to 24 VAC transformer in 

the outdoor unit to provide 24 VAC power to the outdoor unit’s 

electronic control. 

1

2

C

R

1

2

R

C

Communica ng Thermostat

(In case of Daikin 

One

+ Smart 

Thermostat)

Air Handler Blower

Integrated Control Module

Outdoor Unit

Integrated Control Module

125   (*)

250   (*)

(*) Allowable Maximum Length

1

2

R

C

Figure 33

Please read carefully before installing this unit. 
• 

Power line terminal #C from Indoor unit must connect to 

terminal #C on thermostat and power line terminal #R from 

indoor unit must connect to terminal #R on thermostat. 

Verify wires are not reversed. (Note: The order of the 

terminals of the indoor unit and the Daikin 

ONE

+ thermostat 

may be different.)

• 

Do not attach any wires to the R&C Terminals on the AC/HP, 

as they are not needed for inverter unit. 

• 

Data Line Terminal #1 from AC/HO must connect to terminal 

#1 on indoor unit and thermostat and data line terminal #2 

from AC/HP must connect to terminal #2 on indoor unit and 

thermostat. Verify wires are not reversed. 

ATTENTION INSTALLER - IMPORTANT NOTICE

18.4 Fully Communicating Daikin System Advanced Features

The Communicating system permits access to additional 

system information, advanced set-up features, and advanced 

diagnostic/troubleshooting features. These advanced features 

are organized into a menu structure. If you are using a Daikin 

One+

 Smart Thermostat, please visit website at  

https://www.daikinone.com for instructions.

18.5 Diagnostics

Accessing the air handler’s diagnostics menu provides ready 

access to the last six faults detected by the air handler.  Faults 

are stored most recent to least recent.  Any consecutively 

repeated fault is stored a maximum of three times.  Example: 

A clogged return air filter causes the air handler’s motor to 

repeatedly enter a limiting condition. The control will only store 

this fault the first three consecutive times the fault occurs. 

NOTE:

 It is highly recommended that the fault history be 

cleared after performing maintenance or servicing the air 

handler.  

18.5.1 Network Troubleshooting 

The Communicating system is a fully communicating system, 

and thus, constitutes a network.  Occasionally the need 

to troubleshoot the network may arise.  The integrated air 

handler control has some on-board tools that may be used to 

troubleshoot the network.  These tools are: red communications 

LED, green receive (Rx) LED, and learn button.  Refer to the 

Communications Troubleshooting Chart at the end of this 

manual for error codes, possible causes and corrective actions.

•  Red communications LED – Indicates the status of the 

network.  The table below indicates the LED status and the 

corresponding potential problem.

•  Green receive LED – Indicates network traffic.  The table 

below indicates the LED status and the corresponding 

potential problem.

•  Learn button – Used to reset the network.  Depress the 

button for approximately 2 seconds to reset the network.

Summary of Contents for DV PTC 14 Series

Page 1: ...ations 3 4 Replacement Parts 3 5 Pre Installation Considerations 3 5 1 Preparation 3 5 2 System Matches 3 5 3 Interconnecting Tubing 4 5 4 Clearances 4 5 5 Horizontal Applications 4 6 Installation Loc...

Page 2: ...E Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death This product is factory shippe...

Page 3: ...g at the cabinet corners 3 Codes Regulations This product is designed and manufactured to comply with applicable national codes Installation in accordance with such codes and or prevailing local codes...

Page 4: ...hat may become wet such as crawl spaces elevate the unit with a sturdy non porous material In installations that may lead to physical damage i e a garage it is advised to install a protective barrier...

Page 5: ...CB14 DV33PTCC14 DV61PTCD14 DV39PTCC14 DV49PTCC14 DFK C DFK D Downflow Kit Downflow Kit Downflow Kit MODEL LIST FOR DOWNFLOW KITS DFK B Downflow Kit Table 2 Refer to Figure 6 and 7 for the location of...

Page 6: ...Center Support Filter Bracket Filter Access Panel INTERNAL PART TERMINOLOGY Figure 6 Blower Access Panel Coil Access Panel Tubing Panel UV Knockout EXTERNAL PART TERMINOLOGY Figure 7 NOTE If removing...

Page 7: ...t be proportional to the size of the tube Service personnel must use the appropriate heat level for the size of the tube being brazed CAUTION NOTE Refrigerant tubing must be routed to allow adequate a...

Page 8: ...superheat is low adjust TXV valve to 7 to 9 superheat and remove charge to lower the subcooling to 7 to 9 F NOTE Do NOT adjust the charge based on suction pressure unless there is a gross undercharge...

Page 9: ...per field constructed P style trap than is shown in Figure 12 to allow proper drainage and prevent condensate overflow Air Handler 2 75 MIN POSITIVE LIQUID SEAL REQUIRED AT TRAP Drain Connection 2 MIN...

Page 10: ...nit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible with a given air handler No other accessory heat kit besides the HKS series may be installed in thes...

Page 11: ...your unit FIRE HAZARD To avoid the risk of property damage personal injury or fire use only copper conductors CAUTION HIGH VOLTAGE Failure to do so may cause property damage personal injury or death D...

Page 12: ...of the cabinet or either side See the Thermostat Wiring section of this manual for typical low voltage wiring connections 13 Achieving 1 4 and 2 0 Airflow Low Leakage Rate Ensure all the gaskets rema...

Page 13: ...ween Y1 and O for Proper Dehumidification Operation and Proper Ramping Profile Operation W2 Typical Single Stage Cooling with Single Stage Heating Figure 14 Air Handler Integrated Control Module Typic...

Page 14: ...CH Figure 19 Legacy mode use In a legacy system Non communicating this feature is not operational Any auxiliary alarm switch must be used to interrupt the Y1 signal either to the indoor or outdoor uni...

Page 15: ...flow for the cooling system Most cooling systems are designed to work with airflows between 350 and 450 CFM per ton Most manufacturers recommend an airflow of about 400 CFM per ton Example 2 5 tons X...

Page 16: ...R NR NR NR NR NR 1750 NR 25 OFF OFF OFF NR NR NR NR NR NR NR NR NR NR NR 1750 NR Note Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation Within...

Page 17: ...s maximum airflow capability is 2000 CFM and 25 continuous fan speed is selected the continuous fan speed will be 0 25 x 2000 CFM 500 CFM 6 The multi speed circulator blower also offers several custo...

Page 18: ...code from being displayed NOTE For installations not indicated in the preceding Temperature Rise Tables the following formula is to be used TR kW x 3412 x Voltage Correction 1 08 x CFM Where TR Tempe...

Page 19: ...ypically do not return information to the thermostat On the other hand the indoor unit outdoor unit and thermostat comprising a Communicating system communicate digitally with one another It is now a...

Page 20: ...to terminal 1 on indoor unit and thermostat and data line terminal 2 from AC HP must connect to terminal 2 on indoor unit and thermostat Verify wires are not reversed ATTENTION INSTALLER IMPORTANT NO...

Page 21: ...led when necessary and pitched to allow for drainage Drain pan and drain tubing has been leak checked Return and supply ducts are sealed Unit is elevated when installed in a garage or where flammable...

Page 22: ...a 1 data 2 wires Check wire connections at terminal block Verify air handler installation type noncommunicating traditional or communicating Check data 1 data 2 voltages Turn power OFF prior to repair...

Page 23: ...tory NOTE Consecutively repeated faults are shown a maximum of 3 times Submenu Item Model Number MOD NUM Displays the modular blower model number Serial Number SER NUM Displays the modular blower seri...

Page 24: ...ENT TRIP OR LOST ROTOR b5 BLOWER MOTOR ROTOR LOCKED b6 OVER UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP b7 INCOMPLETE PARAMETER SENT TO MOTOR b9 LOW INDOOR AIRFLOW C1 LOW STAGE COOL LEGACY MODE ONLY C...

Page 25: ...ROL LOW VOLTAGE 24V FIELD SPLICE INTERNAL TO FIELD GRND OVERCURRENT BK BLACK OR ORANGE BL BLUE PK PINK GY GRAY RD RED WH WHITE PU PURPLE YL YELLOW BR BROWN COLOR CODES GN GREEN NOTES 1 PLACE RED WIRES...

Page 26: ...ERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING Wiring is subject to change Always refer to the wiring diagram on the unit fo...

Page 27: ...uminum tube and fin evaporator coils Even a one time application of these corrosive chemicals can cause premature aluminum evaporator coil failure Any cleaners that contain corrosive chemicals includi...

Page 28: ...F WB F Heating Supply AirTemperature DB F Temperature Rise DB F DeltaT Difference between Supply and Return Temperatures DB F AirHandler Coil InverterMatched INVERTERAH COILONLY Check EEV and EEV wiri...

Page 29: ...29 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 30: ...30 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 31: ...31 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 32: ...register by following this link https daikincomfort com owner support product registration You can also scan the QR code on the right to be directed to the Product Registration page CUSTOMER FEEDBACK...

Reviews: