background image

PRODUCT DESIGN

4

DP13GM Package Gas Units are designed for outdoor in-
stallations only in either residential or light commercial appli-
cations and are available in 2 through 5 ton sizes. They are
designed for  208/230 volt single phase applications.  (DP13GM
3, 4 and 5 ton models are also available for 230V 3 phase
applications. See Technical Manual RTD6312005.)

The connecting ductwork (Supply and Return) can be con-
nected for either horizontal or vertical airflow. In the vertical
application, a matching Roof Curb is recommended.

A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible loca-
tion within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Sec-
tion. Under no circumstances should the unit be operated
without return air filters.

A 3/4" pipe is provided for removal of condensate water from
the indoor coil. (Do not reduce the drain line size).

NOTE: 

Tighten drain to a maximum torque of 10 in-lbs.

Refrigerant flow control is achieved by use of restrictor ori-
fices. DP13GM units use the FasTest Access Fitting Sys-
tem which consists of a saddle that is either soldered to the
suction and liquid lines or is fastened with a locking nut to
the access fitting box (core) and then screwed into the saddle.

NOTE: The core must not be removed from the saddle
until the refrigerant charge has been removed. Failure
to do so could result in property damage or personal
injury.

The single phase units use permanent split capacitors (PSC)
design compressors. Starting components are therefore not
required. A low MFD run capacitor assists the compressor
to start and remains in the circuit during operation.

The outdoor fan and indoor blower motors are single phase
permanent split capacitor type motors. DP13GM48***41**
and DP13GM60***41** models are equipped with EEM in-
door blower motors.  EEM motors are constant torque mo-
tors with very low power consumption and are energized by a
24V signal from the ignition control.  The EEM features an
integrated control module.

Air for condensing (cooling cycle) is drawn through the out-
door coil by a propeller fan, and is discharged vertically out
the top of the unit.  The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.

Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.

Some models of the DP13GM series package units use the
Compliant Scroll compressor, there are a number of design
characteristics which are different from the traditional recip-
rocating compressor.

-

Due to their design Scroll compressors are inherently more
tolerant of liquid refrigerant. 

NOTE

: Even though the com-

pressor section of a Scroll compressor is more tolerant
of liquid refrigerant, continued floodback or flooded start
conditions may wash oil from the bearing surfaces caus-
ing premature bearing failure.

-

These Scroll compressors use "POE" or polyester oil
which is NOT compatible with mineral oil based lubricants
like 3GS.  "POE" oil must be used if additional oil is
required.

-

Compliant scroll compressors perform "quiet" shutdowns
that allow the compressor to restart immediately without
the need for a time delay. This compressor will restart
even if the system has not equalized.

-

Operating pressures and amp draws may differ from stan-
dard reciprocating compressors. This information may be
found in the "Cooling Performance Data" section.

Summary of Contents for DP13GM2404541A series

Page 1: ...isted on page 3 DP 13 SEER R 410A Single Phase Package Gas Units RTD6312004r1 March2014 TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL AL AL Copyright 2013 2014 Thi...

Page 2: ...ation Institute AHRI may use this information Attempting to install or repair this unit without such background may result in product damage personal injury or death The model and manufacturing number...

Page 3: ...tions may vary by jurisdiction Should questions arise contact your local EPA office WARNING WARNING Do not connect or use any device that is not design certified by Daikin for use with this unit Serio...

Page 4: ...sists the compressor to start and remains in the circuit during operation The outdoor fan and indoor blower motors are single phase permanent split capacitor type motors DP13GM48 41 and DP13GM60 41 mo...

Page 5: ...TE To ensure proper condensate drainage unit must be installed in a level position WARNING TO PREVENT POSSIBLE PROPERTY DAMAGE THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVI...

Page 6: ...rate by changing orifices or increasing the manifold pressure This can cause poor combustion and equipment failure At all altitudes the manifold pressure must be within 0 3 inches W C of that listed o...

Page 7: ...ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL 22 2...

Page 8: ...Fresh Air Damper Horizontal Application Small Chassis DHZ25FDPGCHMM Manual 25 M Series Fresh Air Damper Horizontal Application Medium Chassis DHZ25FDPGCHML Manual 25 M Series Fresh Air Damper Horizon...

Page 9: ...100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU...

Page 10: ...1 3 3 1 3 3 1 3 3 BLOWER FULL LOAD AMPS 1 5 1 5 1 9 1 9 3 1 MOTOR LOCKED ROTOR AMPS 2 2 2 2 3 1 3 1 4 1 MOTOR SPEED TAP COOLING Med Med Med Med High RPM 952 952 1 015 1 015 910 EVAPORATOR DIAMETER X W...

Page 11: ...1 3 3 3 4 5 BLOWER FULL LOAD AMPS 3 06 3 06 3 06 3 06 5 8 MOTOR LOCKED ROTOR AMPS 4 1 4 1 4 1 4 1 MOTOR SPEED TAP COOLING High High Medium Medium T4 RPM 910 910 910 910 1050 EVAPORATOR DIAMETER X WID...

Page 12: ...Scroll Scroll Scroll Scroll Scroll RATED LOAD AMPS 19 9 19 9 26 4 26 4 26 4 LOCKED ROTOR AMPS 109 0 109 0 134 0 134 0 134 0 CONDENSER HORSEPOWER 1 4 1 4 1 4 1 4 1 4 FAN MOTOR RPM 1100 1100 1100 1100...

Page 13: ...se Range 30 60 LOW MEDIUM HIGH DP13GM307041A Rise Range 35 65 LOW MEDIUM HIGH DP13GM 24 30 41A NR Heating Temperature Rise Not Recommeded NOTE The shaded area indicates ranges in excess of maximum ext...

Page 14: ...41 0 5 823 304 1 29 63 1 073 405 1 73 48 1 188 513 2 34 44 0 6 750 287 1 23 NR 1 008 393 1 71 51 1 090 496 2 22 47 0 7 668 271 1 16 NR 895 371 1 61 58 997 478 2 18 52 0 8 454 238 1 00 NR 760 346 1 49...

Page 15: ...6 619 135 NR 833 214 NR 1176 341 58 1421 431 1509 464 0 7 551 143 NR 770 222 NR 1120 349 61 1370 439 1460 472 0 8 482 151 NR 706 230 NR 1064 357 65 1319 447 1411 480 DP13GM4809041A Rise Range 45 75 F...

Page 16: ...545 58 1583 615 1785 736 0 8 755 153 NR 1100 361 NR 1418 553 60 1534 623 1736 745 CFM WATT RISE CFM WATT RISE CFM WATT RISE CFM WATT CFM WATT 0 1 1100 97 NR 1445 305 71 1762 496 59 1878 566 2080 688...

Page 17: ...0 93 0 83 0 63 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 66 0 43 1 00 0 91 0 69 0 44 1 00 0 92 0 70 0 45 Delta T 22 20 17 12 22 21 17 12 22 21 17 12 23 21 17 12 22 20 17 12 20 19 16 11 890 KW 1 71 1 74 1 7...

Page 18: ...24 135 144 121 128 140 149 127 135 147 157 133 141 154 164 138 146 160 170 MBh 24 8 25 2 26 4 28 2 24 2 24 7 25 8 27 6 23 6 24 1 25 2 26 9 23 0 23 5 24 6 26 2 21 9 22 3 23 4 24 9 20 3 20 7 21 6 23 1 S...

Page 19: ...84 0 63 0 41 0 96 0 86 0 65 0 42 0 99 0 89 0 67 0 43 1 00 0 92 0 70 0 45 1 00 0 93 0 70 0 45 Delta T 21 19 16 11 21 20 16 11 21 20 16 11 21 20 16 11 21 19 16 11 19 18 15 10 1125 KW 2 10 2 14 2 21 2 2...

Page 20: ...137 146 123 131 143 152 129 137 150 160 135 144 157 168 140 149 163 173 MBh 29 5 30 1 31 5 33 6 28 8 29 4 30 8 32 8 28 1 28 7 30 0 32 1 27 5 28 0 29 3 31 3 26 1 26 6 27 8 29 7 24 2 24 6 25 8 27 5 S T...

Page 21: ...0 62 0 40 0 94 0 84 0 64 0 41 0 97 0 87 0 66 0 42 1 00 0 90 0 68 0 44 1 00 0 91 0 69 0 44 Delta T 22 20 16 11 22 20 16 11 22 20 16 11 22 20 17 11 21 20 16 11 20 19 15 11 1350 KW 2 59 2 64 2 72 2 81 2...

Page 22: ...2 475 502 523 LO PR 109 116 127 135 115 123 134 143 120 128 139 148 126 134 146 156 132 140 153 163 137 145 159 169 MBh 36 9 37 7 39 4 42 1 36 1 36 8 38 5 41 1 35 2 35 9 37 6 40 1 34 4 35 0 36 7 39 1...

Page 23: ...0 61 0 39 0 92 0 83 0 62 0 40 0 95 0 85 0 65 0 41 0 99 0 88 0 67 0 43 1 00 0 89 0 68 0 43 Delta T 22 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 21 19 16 11 1440 KW 2 95 3 01 3 09 3 19 3...

Page 24: ...9 451 476 497 LO PR 110 117 128 137 117 124 135 144 121 129 141 150 127 135 148 157 133 142 155 165 138 147 160 171 MBh 41 8 42 6 44 6 47 6 40 8 41 6 43 6 46 5 39 9 40 6 42 5 45 4 38 9 39 6 41 5 44 3...

Page 25: ...62 0 40 0 94 0 84 0 64 0 41 0 97 0 87 0 66 0 42 1 00 0 90 0 68 0 44 1 00 0 91 0 69 0 44 Delta T 22 20 17 12 22 21 17 12 22 21 17 12 23 21 17 12 22 21 17 12 20 19 16 11 1700 KW 3 30 3 37 3 46 3 57 3 5...

Page 26: ...8 460 486 507 LO PR 113 120 131 140 120 127 139 148 124 132 144 154 131 139 152 162 137 146 159 169 142 151 164 175 MBh 47 8 48 7 51 0 54 4 46 7 47 6 49 8 53 2 45 6 46 5 48 7 51 9 44 5 45 3 47 5 50 6...

Page 27: ...0 61 0 39 0 92 0 83 0 63 0 40 0 95 0 85 0 65 0 42 0 99 0 89 0 67 0 43 1 00 0 89 0 68 0 43 Delta T 23 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 21 19 16 11 2035 KW 4 30 4 38 4 51 4 65 4...

Page 28: ...7 460 486 506 LO PR 107 114 124 132 113 120 131 140 117 125 136 145 123 131 143 152 129 137 150 160 134 142 155 165 MBh 59 3 60 5 63 3 67 6 58 0 59 1 61 9 66 0 56 6 57 7 60 4 64 4 55 2 56 3 58 9 62 9...

Page 29: ...ature drop Delta T Low and high side pressures and power will not change 2 As indoor CFM decreases a slight increase will occur in indoor temperature drop Delta T A slight decrease will occur in low a...

Page 30: ...TALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer to the wiring diagram on the unit f...

Page 31: ...the unit for the most up to date wiring WARNING HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DA...

Page 32: ...4V BL TRANS 240 GR PU BL BL BL BL PU R C S COMP PU PU LS BR CM BR BR EM 4 5 YL 1 2 3 LOW RD BL MEDIUM OPTIONAL 3 SPEED EM CAP 2 BR PU HIGH CAP2 NOTE 4 RD PU L2 BL BK PU 4 SPEED MOTOR HPS CH OPTIONAL C...

Page 33: ...GN IGNITOR LS LIMIT SWITCH PL PLUG PS PRESSURE SWITCH RS ROLLOUT SWITCH THC THERMOSTAT HEAT COOL TRANS TRANSFORMER VM VENT MOTOR HPS HIGH PRESSURE SWITCH BL PK BLUE PINK 9 8 7 HPS 3 BLINKS 6 BLINKS 2...

Page 34: ...TALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer to the wiring diagram on the unit f...

Page 35: ...he most up to date wiring WARNING HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL I...

Page 36: ...BL BL BR BR RD OR BL BL BL BL RD RD RD RD PU WH OR RD PLF YL YL YL GR PU YL Y Y2 Y1 1 2 3 IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 ECON F1 FUSE 3 A...

Page 37: ...PLIED ON ALL UNITS 4 FOR DIFFERENTTHAN FACTORY SPEED TAP CHANGE COOLING SPEED AT MOTOR T4 AND T5 TERMINALS CHANGE HEATING SPEED AT MOTOR T1 T2 AND T3 TERMINALS COOLING SPEED YELLOW WIRE HEATING SPEED...

Reviews: