![Daikin DP13GM2404541A series Technical Manual Download Page 15](http://html1.mh-extra.com/html/daikin/dp13gm2404541a-series/dp13gm2404541a-series_technical-manual_2460482015.webp)
15
BLOWER PERFORMANCE DATA
CFM
WATT
RISE
CFM
WATT
RISE
CFM
WATT
RISE
CFM
WATT
CFM
WATT
0.1
---
---
---
---
---
---
---
---
---
---
---
---
---
0.2
892
104
NR
1088
183
NR
1401
310
61
1624
400
1704
433
0.3
824
112
NR
1024
191
NR
1345
318
63
1573
408
1655
440
0.4
756
120
NR
960
199
NR
1289
326
66
1522
416
1606
448
0.5
687
128
NR
897
207
NR
1233
333
67
1472
424
1558
456
0.6
619
135
NR
833
214
NR
1176
341
72
1421
431
1509
464
0.7
551
143
NR
770
222
NR
1120
349
NR
1370
439
1460
472
0.8
482
151
NR
706
230
NR
1064
357
NR
1319
447
1411
480
DP13GM4811541A* - Rise Range: 45° - 75° F
E.S.P
T1 HEATING SPEED
T2 HEATING SPEED
T3 HEATING SPEED
T4 COOLING T5 COOLING
CFM
WATT
RISE
CFM
WATT
RISE
CFM
WATT
RISE
CFM
WATT
CFM
WATT
0.1
---
---
---
---
---
---
---
---
---
---
---
---
---
0.2
892
104
75
1088
183
62
1401
310
49
1624
400
1704
433
0.3
824
112
NR
1024
191
67
1345
318
51
1573
408
1655
440
0.4
756
120
NR
960
199
71
1289
326
53
1522
416
1606
448
0.5
687
128
NR
897
207
NR
1233
333
54
1472
424
1558
456
0.6
619
135
NR
833
214
NR
1176
341
58
1421
431
1509
464
0.7
551
143
NR
770
222
NR
1120
349
61
1370
439
1460
472
0.8
482
151
NR
706
230
NR
1064
357
65
1319
447
1411
480
DP13GM4809041A* - Rise Range: 45° - 75° F
T4 COOLING T5 COOLING
E.S.P
T1 HEATING SPEED
T2 HEATING SPEED
T3 HEATING SPEED
CFM
WATT
RISE
CFM
WATT
RISE
CFM
WATT
RISE
CFM
WATT
CFM
WATT
0.1
---
---
---
---
---
---
---
---
---
---
---
---
---
0.2
892
104
59
1088
183
48
1401
310
37
1624
400
1704
433
0.3
824
112
64
1024
191
51
1345
318
39
1573
408
1655
440
0.4
756
120
NR
960
199
55
1289
326
41
1522
416
1606
448
0.5
687
128
NR
897
207
58
1233
333
42
1472
424
1558
456
0.6
619
135
NR
833
214
63
1176
341
45
1421
431
1509
464
0.7
551
143
NR
770
222
NR
1120
349
47
1370
439
1460
472
0.8
482
151
NR
706
230
NR
1064
357
49
1319
447
1411
480
DP13GM4807041A* - Rise Range: 35° - 65° F
T2 HEATING SPEED
T3 HEATING SPEED
E.S.P
T1 HEATING SPEED
T4 COOLING
T5 COOLING
DP13G48***41A*
NR = Heating Temperature Rise Not Recommeded.
NOTE:
The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,
external static pressure should not exceed 0.5" w.c.