PACKAGE GAS SPECIFICATIONS
11
DP13GM36070
41A*
DP13GM36090
41A*
DP13GM42070
41A*
DP13GM42090
41A*
DP13GM48070
41A*
COOLING
COOLING CAPACITY, BTUH
35,000
35,000
40,500
40,500
46,000
CAPACITY
SEER / EER
13.0 / 11.0
13.0 / 11.0
13.0 / 11.0
13.0 / 11.0
13.0 / 11.0
HEATING INPUT BTUH (U.S. & CANADIAN)
69,000
92,000
69,000
92,000
69,000
HEATING
HEATING OUTPUT BTUH (U.S. & CANADIAN)
55,000
73,600
55,000
73,600
55,000
CAPACITY
AFUE (%)
80
80
80
80
80
TEMPERATURE RISE (°F)
35 - 65
45 - 75
35 - 65
45 - 75
35 - 65
UNIT
VOLTAGE (NAMEPLATE)
208/230
208/230
208/230
208/230
208/230
ELECTRICAL
UNIT AMPS (TOTAL)
21.2
21.2
22.3
22.3
27.1
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
25.4
25.4
26.8
26.8
32.1
MAXIMUM OVERCURRENT PROTECTION
40
40
40
40
50
HEATING
NUMBER OF BURNERS
3
4
3
4
3
SECTION
ORIFICE SIZE NATURAL
43
43
43
43
43
ORIFICE SIZE LP
55
55
55
55
55
COMPRESSOR
TYPE
Scroll
Scroll
Scroll
Scroll
Scroll
RATED LOAD AMPS
16.7
16.7
17.9
17.9
19.9
LOCKED ROTOR AMPS
79.0
79.0
112.0
112.0
109.0
CONDENSER
HORSEPOWER
1/4
1/4
1/4
1/4
1/4
FAN MOTOR
RPM
830
830
1100
1100
1100
FULL LOAD AMPS
1.5
1.5
1.4
1.4
1.4
LOCKED ROTOR AMPS
3.0
3.0
2.9
2.9
2.9
CONDENSER
BLADE DIAMETER (INCHES)
22
22
22
22
22
FAN
NUMBER OF BLADES
3
3
3
3
3
CFM
2400
2400
3500
3500
3500
CONDENSER
FACE AREA - SQ. FT.
8.77
8.77
15.3
15.3
15.3
COIL
NUMBER OF ROWS
2
2
1
1
1
FINS PER INCH
27
27
24
24
24
EVAPORATOR
HORSEPOWER - NO. OF SPEEDS
1/3 - 3
1/3 - 3
1/3 - 3
1/3 - 3
3/4 - 5
BLOWER
FULL LOAD AMPS
3.06
3.06
3.06
3.06
5.8
MOTOR
LOCKED ROTOR AMPS
4.1
4.1
4.1
4.1
--
MOTOR SPEED TAP - COOLING
High
High
Medium
Medium
T4
RPM 910
910
910
910
1050
EVAPORATOR
DIAMETER X WIDTH (INCHES)
10” x 9”
10” x 9”
10” x 10”
10” x 10”
11” x 10”
BLOWER
RATED SCFM COOLING
1200
1200
1300
1300
1550
MAX EXTERNAL STATIC PRESS ("w.c.)
0.5
0.5
0.5
0.5
0.5
EVAPORATOR
FACE AREA - SQ. FT.
4.33
4.33
5.67
5.67
5.67
COIL
NUMBER OF ROWS
4
4
4
4
4
FINS PER INCH
14
14
14
14
14
FILTER SIZE - SQ. FT.
(2)
4.2
4.2
4.7
4.7
5.1
DRAIN SIZE (INCHES)
3/4
3/4
3/4
3/4
3/4
HEATING
PRIMARY LIMIT SETTING (°F)
160
160
170
170
170
LIMITS
AUXILIARY LIMIT SETTING (°F)
150
150
150
150
150
ROLLOUT LIMIT SETTING (°F)
350
350
350
350
350
GENERAL
PISTON EXPANSION DEVICE
Orifice (.068)
Orifice (.068)
Orifice (.072)
Orifice (.072)
Orifice (.076)
INFORMATION
REFRIGERANT CHARGE R-410A (Oz.)
70
70
99
99
87
POWER SUPPLY ENTRANCE SIZE (INCHES)
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
LOW VOLTAGE ENTRANCE SIZE (INCHES)
7/8
7/8
7/8
7/8
7/8
SHIPPING WEIGHT LBS.
475
480
515
520
540
OPERATING WEIGHT LBS.
453
458
493
496
518
DP13GM[36-48]***41A*
(1)
Units installed in Canada are certifed only to 4500 feet.
(2)
Calculated external filter size based on air velocity of 300 ft/min. and applies to disposable filters
only.
(3)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/
circuit breakers in accordance with the National Electrical Code and/or all local codes.