background image

8 Disposal

Installation manual

10

DCC601A51

intelligent Tablet Controller

4P414342-1D – 2020.12

6

Once  all  wiring  has  been  completed  and  double-checked,  turn
on the power supply.

CAUTION

The power supply is 

ONLY

 guaranteed when the "DC OK"

LED  on  the  WAGO  PSU 

and

  the  "CPU  ALIVE"  LEDs  on

both

 the CPU module and the I/O module are blinking.

If  one  or  more  of  the  above  LEDs  are  NOT  lighting  up,
check for faulty wiring.

INFORMATION

A  new  CPU  module  does  NOT  come  with  application
software  installed.  Therefore,  the  "ALARM"  LED  will  be  lit
red.  This  is  as  expected,  see  the  table  under 

"6.4.1  CPU

module"

  [

4

  6].  Application  software  will  be  installed  during

the  commissioning  phase.  For  more  information  about
commissioning, see the installer reference guide.

7.2.4

Connecting the LAN cable

For all wiring requirements see 

"7.2.1 Wiring requirements"

 [

4

 7].

Do  NOT  connect  the  LAN  cable  until  you  start  commissioning  the
intelligent  Tablet  Controller.  Otherwise,  a  network  address  conflict
may occur. For more information about commissioning the intelligent
Tablet Controller setup, see the installer reference guide.

7.3

About the installation of the Daikin-
supplied router

For information on the installation, see the manual provided with the
Daikin-supplied  router.  For  information  on  when  to  use  the  Daikin-
supplied  router,  see 

"5.4  Additional  components  in  the  intelligent

Tablet Controller solution"

 [

4

 4].

The  following  table  gives  an  overview  of  the  most  relevant
information.

Requirement

Information

Default WiFi name (SSID)

ASUS

Default WiFi password (access
key)

To be found on the sticker at the
back of the router.

Router configuration URL

Use one of the following:

▪ http://192.168.1.1

▪ http://router.asus.com

Router configuration password

Not set. You will set this when
you start the router’s "Quick
internet setup (Quick internet
setup)" feature.

8

Disposal

DANGER: RISK OF EXPLOSION

There  is  a  risk  of  explosion  if  the  internal  battery  is
replaced by an incorrect type.

Replace  the  battery  according  to  the  instruction  in  To
replace the data backup battery

▪ Both  intelligent  Tablet  Controller  modules  are  marked  with  the

following symbol:

This  means  that  electrical  and  electronic  products  may  not  be
mixed  with  unsorted  household  waste.  Do  NOT  try  to  dismantle
the  system  yourself:  the  dismantling  of  the  system,  treatment  of

the  refrigerant,  of  oil  and  of  other  parts  must  be  done  by  an
authorized installer and must comply with applicable legislation.

Units must be treated at a specialized treatment facility for reuse,
recycling  and  recovery.  By  ensuring  this  product  is  disposed  of
correctly, you will help to prevent potential negative consequences
for  the  environment  and  human  health.  For  more  information,
contact your installer or local authority.

▪ The CPU module contains a replaceable battery, marked with the

following symbol:

This  means  that  the  battery  may  not  be  mixed  with  unsorted
household  waste.  If  a  chemical  symbol  is  printed  beneath  the
symbol,  this  chemical  symbol  means  that  the  battery  contains  a
heavy metal above a certain concentration.

Possible chemical symbols are: Pb: lead (>0.004%).

Waste batteries must be treated at a specialized treatment facility
for  reuse.  By  ensuring  waste  batteries  are  disposed  of  correctly,
you  will  help  to  prevent  potential  negative  consequences  for  the
environment and human health.

9

Copyright and trademarks

SDHC Logo is a trademark of SD-3DC, LLC.

10

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

10.1

Environmental conditions

Item

Specification

Operating air temperature

–10~+50°C

Storage temperature

–20~+60°C

Relative humidity

10~85% RH (without
condensation)

10.2

Electrical cabinet

For  the  specifications  of  the  electrical  cabinet,  see 

"6.3.1  About

installation place and mounting direction"

 [

4

 5].

10.3

Power consumption specifications

Item

Specification

Related input voltage

110~220 V AC

Input power frequency

50~60 Hz

Power consumption CPU module
+ I/O module

▪ Max.: 13 W (11 W+2 W)

▪ Typical: 5.5 W (4 W+1.5 W)

For more detailed specifications of the WAGO power supply, refer to
the manual provided with the WAGO power supply.

Summary of Contents for DCC601A51

Page 1: ...Installation manual intelligent Tablet Controller English Installation manual intelligent Tablet Controller DCC601A51 ...

Page 2: ...t audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Preparation of the installation reference data Format Digital files on http www daikineurope com support and manuals product information Latest revisions of the supplied ...

Page 3: ... performed in accordance with the wiring diagram supplied with the product Make sure to install earth wiring Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required fuses or circuit breakers Make sure to inst...

Page 4: ...ller kit see 10 5 Schematic setup of the intelligent Tablet Controller 4 11 Before installing the intelligent Tablet Controller kit modules draw up an efficient plan of work using this schematic and based on the real environment it needs to be installed in 5 3 Compatible Daikin equipment The intelligent Tablet Controller solution can connect to certain Daikin units that provide a DIII NET communic...

Page 5: ...ments Location Indoor inside an electrical cabinet The electrical cabinet must be lockable or designed to be opened only with a special tool The key or tool should be available only to service personnel must be installed in a space with no access for the general public must comply with the applicable legislation must have ingress protection class of IP4X or higher however make sure enough ventilat...

Page 6: ...itches a RESET Button for restarting the CPU module and I O module k DIP SW Reserved for servicing Factory default all switches are set to OFF OFF n BACKUP Switch for turning on off the backup power supply for retaining the current settings provided by the internal battery Factory default OFF OFF This will be set to the ON ON position during commissioning q Lever To assist mounting dismounting the...

Page 7: ...perating condition CPU ALIVE ALARM Normal Blink OFF Hardware failure OFF ON Power interruption OFF OFF Communication failure between CPU module and I O module for 10 seconds or more ON Blink 7 Installation 7 1 Installation of the intelligent Tablet Controller hardware The intelligent Tablet Controller components are to be mounted onto a 35 mm DIN rail inside an electrical cabinet For more informat...

Page 8: ...on terminal sized for maximum 4 mm According to applicable legislation Solid or stranded wire allowed The internal protection of the WAGO PSU is fused at 2 5 A 250 V 24 V DC power supply to the CPU module According to applicable legislation Solid or stranded wire allowed USB cable 5 m Commercial USB 2 0 cable type A to type B connector provided in the intelligent Tablet Controller kit a Total leng...

Page 9: ...ternally So you can use any one of them However you can only connect up to 2 wires simultaneously to each COM terminal If applicable connect the I O module s COM terminal to the negative side of the device terminals 7 2 3 Connecting the power supply to all modules For all wiring requirements see 7 2 1 Wiring requirements 47 To connect the power supply to all modules 1 Connect the power supply to t...

Page 10: ...e data backup battery Both intelligent Tablet Controller modules are marked with the following symbol This means that electrical and electronic products may not be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts must be done by an authorized installer and must comply with applicable...

Page 11: ...chematic setup of the intelligent Tablet Controller USB 230 V AC RJ 45 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 OUT IN F1 F2 http cloud daikineurope com DIII NET POWER I O IF CPU IF LAN F1 F2 Di1 Di4 d e f i i i h j k 24 V DC c b g a l l L N a WAGO power supply unit b CPU module c I O module d Optional Daikin supplied tablet e Daikin Cloud Service f Daikin Cloud Service g LAN gateway optional Dai...

Page 12: ...4P414342 1D 2020 12 Copyright 2015 Daikin 4P414342 1 D 0000000Y Verantwortung für Energie und Umwelt ...

Reviews: