background image

6 Preparation

Installation manual

5

DCC601A51
intelligent Tablet Controller
4P414342-1D – 2020.12

5.4.2

Daikin-supplied tablet (ASUS ZenPad 8.0
Z380M)

If  you  choose  the  local  function  mode  you  have  to  use  a  Daikin-
supplied tablet to run the intelligent Tablet Controller app.

The  intelligent  Tablet  Controller  app  can  be  installed  from  Google
Play.

6

Preparation

6.1

Before installation

Before  you  start  installing  the  intelligent  Tablet  Controller,  complete
the following preparations:

▪ Check  that  the  intelligent  Tablet  Controller  kit  comes  with  all

accessories, see 

"4.1 Contents of the kit"

 [

4

 3].

▪ Check  that  you  have  all  equipment  necessary  to  install  the

intelligent  Tablet  Controller  kit  modules,  see 

"6.2  Necessary

equipment"

 [

4

 5].

▪ Check that an appropriate space for installing the intelligent Tablet

Controller  modules  is  available,  see 

"6.3  Determining  installation

place"

 [

4

 5].

▪ Familiarise yourself with the location of the terminals and switches

of  the  intelligent  Tablet  Controller  modules,  see 

"6.4  About  the

location of terminals and switches"

 [

4

 6].

6.2

Necessary equipment

Use the following equipment to install the intelligent Tablet Controller
kit modules:

▪ A flat-blade screwdriver

▪ A Phillips screwdriver

▪ The  necessary  amount  of  electrical  wires  and  appropriate  wiring

tools.  For  more  info  on  what  wires  to  use,  see 

"7.2.1  Wiring

requirements"

 [

4

 7].

6.3

Determining installation place

Make sure to install the intelligent Tablet Controller components in a
place  that  complies  with  the  conditions  described  in  the  following
sections.

6.3.1

About installation place and mounting
direction

Make  sure  the  installation  place  complies  with  the  following
requirements:

▪ Location: Indoor, inside an electrical cabinet.

▪ The electrical cabinet:

▪ must be lockable or designed to be opened only with a special

tool.  The  key  or  tool  should  be  available  only  to  service
personnel.

▪ must  be  installed  in  a  space  with  no  access  for  the  general

public.

▪ must comply with the applicable legislation.

▪ must have ingress protection class of IP4X or higher (however,

make  sure  enough  ventilation  is  provided  to  prevent
overheating of the equipment).

▪ must  have  impact  protection  class  of  IK07  or  higher  (see

international standard IEC 62262‑2002).

▪ must have a minimum height of 290 mm and minimum width of

410  mm  to  allow  for  the  clearance  specified  in 

"6.3.2  About

required space"

 [

4

 5].

▪ Mounting direction: vertical only

▪ Make  sure  the  installation  place  complies  with  the  environmental

conditions, specified in 

"10.1 Environmental conditions"

 [

4

 10].

6.3.2

About required space

The  following  figure  indicates  the  minimum  space  required  for
installation.

▪ Make sure there is a minimum clearance of 60 mm between both

the  CPU  module,  the  I/O  module  and  the  wiring  ducts  and  a
minimum  clearance  of  80  mm  between  the  modules  and  the
electrical cabinet in the vertical direction.

▪ Make  sure  there  is  a  minimum  vertical  clearance  of  70  mm

between the WAGO PSU and the wiring ducts.

▪ The  CPU  module  and  I/O  module  can  be  installed  without

clearance  in  the  horizontal  direction,  but  make  sure  there  is  a
minimum  clearance  of  20  mm  between  the  modules  and  the
electrical cabinet.

▪ The WAGO PSU requires a minimum clearance of 15 mm on both

sides in the horizontal direction.

≥60

≥80

≥70

≥60

≥70

50

136

130

152

≥15

≥15

152

a

b

a

≥80

≥20

I/O

CPU

+ + - -

L N

(mm)

a

Wire duct

b

Electrical cabinet

Observe the depth of these modules and make sure you provide the
necessary amount of space in depth in the electrical cabinet.

Module

Depth

CPU module

45 mm

I/O module

39 mm

WAGO PSU

92 mm

Summary of Contents for DCC601A51

Page 1: ...Installation manual intelligent Tablet Controller English Installation manual intelligent Tablet Controller DCC601A51 ...

Page 2: ...t audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Preparation of the installation reference data Format Digital files on http www daikineurope com support and manuals product information Latest revisions of the supplied ...

Page 3: ... performed in accordance with the wiring diagram supplied with the product Make sure to install earth wiring Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required fuses or circuit breakers Make sure to inst...

Page 4: ...ller kit see 10 5 Schematic setup of the intelligent Tablet Controller 4 11 Before installing the intelligent Tablet Controller kit modules draw up an efficient plan of work using this schematic and based on the real environment it needs to be installed in 5 3 Compatible Daikin equipment The intelligent Tablet Controller solution can connect to certain Daikin units that provide a DIII NET communic...

Page 5: ...ments Location Indoor inside an electrical cabinet The electrical cabinet must be lockable or designed to be opened only with a special tool The key or tool should be available only to service personnel must be installed in a space with no access for the general public must comply with the applicable legislation must have ingress protection class of IP4X or higher however make sure enough ventilat...

Page 6: ...itches a RESET Button for restarting the CPU module and I O module k DIP SW Reserved for servicing Factory default all switches are set to OFF OFF n BACKUP Switch for turning on off the backup power supply for retaining the current settings provided by the internal battery Factory default OFF OFF This will be set to the ON ON position during commissioning q Lever To assist mounting dismounting the...

Page 7: ...perating condition CPU ALIVE ALARM Normal Blink OFF Hardware failure OFF ON Power interruption OFF OFF Communication failure between CPU module and I O module for 10 seconds or more ON Blink 7 Installation 7 1 Installation of the intelligent Tablet Controller hardware The intelligent Tablet Controller components are to be mounted onto a 35 mm DIN rail inside an electrical cabinet For more informat...

Page 8: ...on terminal sized for maximum 4 mm According to applicable legislation Solid or stranded wire allowed The internal protection of the WAGO PSU is fused at 2 5 A 250 V 24 V DC power supply to the CPU module According to applicable legislation Solid or stranded wire allowed USB cable 5 m Commercial USB 2 0 cable type A to type B connector provided in the intelligent Tablet Controller kit a Total leng...

Page 9: ...ternally So you can use any one of them However you can only connect up to 2 wires simultaneously to each COM terminal If applicable connect the I O module s COM terminal to the negative side of the device terminals 7 2 3 Connecting the power supply to all modules For all wiring requirements see 7 2 1 Wiring requirements 47 To connect the power supply to all modules 1 Connect the power supply to t...

Page 10: ...e data backup battery Both intelligent Tablet Controller modules are marked with the following symbol This means that electrical and electronic products may not be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts must be done by an authorized installer and must comply with applicable...

Page 11: ...chematic setup of the intelligent Tablet Controller USB 230 V AC RJ 45 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 OUT IN F1 F2 http cloud daikineurope com DIII NET POWER I O IF CPU IF LAN F1 F2 Di1 Di4 d e f i i i h j k 24 V DC c b g a l l L N a WAGO power supply unit b CPU module c I O module d Optional Daikin supplied tablet e Daikin Cloud Service f Daikin Cloud Service g LAN gateway optional Dai...

Page 12: ...4P414342 1D 2020 12 Copyright 2015 Daikin 4P414342 1 D 0000000Y Verantwortung für Energie und Umwelt ...