background image

3 Specific installer safety instructions

Installation manual

3

DCC601A51
intelligent Tablet Controller
4P414342-1D – 2020.12

WARNING

Improper  installation  or  attachment  of  equipment  or
accessories  could  result  in  electrical  shock,  short-circuit,
leaks,  fire  or  other  damage  to  the  equipment.  Only  use
accessories,  optional  equipment  and  spare  parts  made  or
approved by Daikin.

WARNING

Make  sure  installation,  testing  and  applied  materials
comply  with  applicable  legislation  (on  top  of  the
instructions described in the Daikin documentation).

CAUTION

Wear  adequate  personal  protective  equipment  (protective
gloves,  safety  glasses,…)  when  installing,  maintaining  or
servicing the system.

WARNING

Tear apart and throw away plastic packaging bags so that
nobody,  especially  children,  can  play  with  them.  Possible
risk: suffocation.

2.2

Installation site

Do NOT install the equipment in a potentially explosive atmosphere.

2.3

Electrical

DANGER: RISK OF ELECTROCUTION

▪ Turn OFF all power supply before connecting electrical

wiring or touching electrical parts.

▪ Disconnect the power supply for more than 10 minutes,

and measure the voltage at the terminals of main circuit
capacitors  or  electrical  components  before  servicing.
The  voltage  MUST  be  less  than  50  V  DC  before  you
can touch electrical components. For the location of the
terminals, see the wiring diagram.

▪ Do NOT touch electrical components with wet hands.

▪ Do  NOT  leave  the  unit  unattended  when  the  service

cover is removed.

WARNING

A  main  switch  or  other  means  for  disconnection,  having  a
contact  separation  in  all  poles  providing  full  disconnection
under  overvoltage  category  III  condition,  shall  be  installed
in the fixed wiring.

WARNING

▪ ONLY use copper wires.

▪ Make sure the field wiring complies with the applicable

legislation.

▪ All  field  wiring  must  be  performed  in  accordance  with

the wiring diagram supplied with the product.

▪ Make sure to install earth wiring. Do NOT earth the unit

to  a  utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earth may cause electrical shock.

▪ Make  sure  to  use  a  dedicated  power  circuit.  NEVER

use a power supply shared by another appliance.

▪ Make  sure  to  install  the  required  fuses  or  circuit

breakers.

▪ Make sure to install an earth leakage protector. Failure

to do so may cause electric shock or fire.

WARNING

▪ After  finishing  the  electrical  work,  confirm  that  each

electrical  component  and  terminal  inside  the  electrical
components box is connected securely.

▪ Make sure all covers are closed before starting up the

unit.

3

Specific installer safety
instructions

Always observe the following safety instructions and regulations.

DANGER: RISK OF EXPLOSION

There  is  a  risk  of  explosion  if  the  internal  battery  is
replaced by an incorrect type.

Replace  the  battery  according  to  the  instruction  in  To
replace the data backup battery

WARNING

All  field  wiring  and  components  MUST  be  installed  by  a
licensed  electrician  and  MUST  comply  with  the  applicable
legislation.

WARNING

▪ Do  NOT  turn  on  the  power  supply  before  all  wire

connections are completed. Not doing so may cause an
electric shock.

▪ After  the  wiring  is  completed,  double-check  that  all

wires  are  connected  correctly  before  turning  on  the
power supply.

▪ All  field  supplied  parts,  materials  and  electric  works

MUST comply with the applicable legislation.

CAUTION

The power supply is 

ONLY

 guaranteed when the "DC OK"

LED  on  the  WAGO  PSU 

and

  the  "CPU  ALIVE"  LEDs  on

both

 the CPU module and the I/O module are blinking.

If  one  or  more  of  the  above  LEDs  are  NOT  lighting  up,
check for faulty wiring.

4

About the box

4.1

Contents of the kit

Based  on  the  following  accessory  list,  check  that  all  parts  and
accessories  for  the  intelligent  Tablet  Controller  are  included  in  the
kit. If there is any missing or defective part, contact the dealer where
you purchased this product.

Summary of Contents for DCC601A51

Page 1: ...Installation manual intelligent Tablet Controller English Installation manual intelligent Tablet Controller DCC601A51 ...

Page 2: ...t audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Preparation of the installation reference data Format Digital files on http www daikineurope com support and manuals product information Latest revisions of the supplied ...

Page 3: ... performed in accordance with the wiring diagram supplied with the product Make sure to install earth wiring Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required fuses or circuit breakers Make sure to inst...

Page 4: ...ller kit see 10 5 Schematic setup of the intelligent Tablet Controller 4 11 Before installing the intelligent Tablet Controller kit modules draw up an efficient plan of work using this schematic and based on the real environment it needs to be installed in 5 3 Compatible Daikin equipment The intelligent Tablet Controller solution can connect to certain Daikin units that provide a DIII NET communic...

Page 5: ...ments Location Indoor inside an electrical cabinet The electrical cabinet must be lockable or designed to be opened only with a special tool The key or tool should be available only to service personnel must be installed in a space with no access for the general public must comply with the applicable legislation must have ingress protection class of IP4X or higher however make sure enough ventilat...

Page 6: ...itches a RESET Button for restarting the CPU module and I O module k DIP SW Reserved for servicing Factory default all switches are set to OFF OFF n BACKUP Switch for turning on off the backup power supply for retaining the current settings provided by the internal battery Factory default OFF OFF This will be set to the ON ON position during commissioning q Lever To assist mounting dismounting the...

Page 7: ...perating condition CPU ALIVE ALARM Normal Blink OFF Hardware failure OFF ON Power interruption OFF OFF Communication failure between CPU module and I O module for 10 seconds or more ON Blink 7 Installation 7 1 Installation of the intelligent Tablet Controller hardware The intelligent Tablet Controller components are to be mounted onto a 35 mm DIN rail inside an electrical cabinet For more informat...

Page 8: ...on terminal sized for maximum 4 mm According to applicable legislation Solid or stranded wire allowed The internal protection of the WAGO PSU is fused at 2 5 A 250 V 24 V DC power supply to the CPU module According to applicable legislation Solid or stranded wire allowed USB cable 5 m Commercial USB 2 0 cable type A to type B connector provided in the intelligent Tablet Controller kit a Total leng...

Page 9: ...ternally So you can use any one of them However you can only connect up to 2 wires simultaneously to each COM terminal If applicable connect the I O module s COM terminal to the negative side of the device terminals 7 2 3 Connecting the power supply to all modules For all wiring requirements see 7 2 1 Wiring requirements 47 To connect the power supply to all modules 1 Connect the power supply to t...

Page 10: ...e data backup battery Both intelligent Tablet Controller modules are marked with the following symbol This means that electrical and electronic products may not be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts must be done by an authorized installer and must comply with applicable...

Page 11: ...chematic setup of the intelligent Tablet Controller USB 230 V AC RJ 45 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 OUT IN F1 F2 http cloud daikineurope com DIII NET POWER I O IF CPU IF LAN F1 F2 Di1 Di4 d e f i i i h j k 24 V DC c b g a l l L N a WAGO power supply unit b CPU module c I O module d Optional Daikin supplied tablet e Daikin Cloud Service f Daikin Cloud Service g LAN gateway optional Dai...

Page 12: ...4P414342 1D 2020 12 Copyright 2015 Daikin 4P414342 1 D 0000000Y Verantwortung für Energie und Umwelt ...

Reviews: