5 Unit installation

Installation manual

8

FVXM25~50A2V1B

Split system air conditioners

3P477070-2H – 2020.06

2

Remove  an  burrs  along  the  cut  section  using  a  half  round
needle file.

5.3.4

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe  length.

  Keep  drain  piping  as  short  as  possible.  Minimum  is

3 m.

Pipe  size.

  Use  rigid  polyvinyl  chloride  pipe  with  20  mm  nominal

diameter and 26 mm outer diameter.

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose. 

Drain  hose  (accessory)  is  220  mm  long  and  with

18 mm outer diameter on the connecting side.

Extension  hose.

  Use  rigid  polyvinyl  chloride  pipe  (field  supply)

with  20  mm  nominal  diameter  as  extension  hose.  When
connecting an extension hose, use a polyvinyl adhesive agent for
glueing.

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  (accessory)  as  far  as  possible  over  the
drain socket and fix it with 1 screw (accessory).

d

c

a

b

a

Drain pan

b

Drain socket

c

Drain hose (accessory)

d

Screw (accessory)

2

Check for water leaks (see 

"To check for water leaks" 

[

4

 8]).

3

Insulate  the  indoor  drain  socket  and  drain  hose  with  ≥10  mm
insulation material to prevent condensation.

4

Connect the drain piping to the drain hose. Insert the drain hose
≥50 mm, so it will not be pulled out of the drain pipe.

100

a

≥50

220

150

100

(mm)

c

d

b

a

a

Drain hose (accessory)

b

Vinyl chloride drain pipe (VP-30) (field supply)

c

Reducer (field supply)

d

Vinyl chloride drain pipe (VP-20) (field supply)

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

Summary of Contents for CVXM20A2V1B

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners CVXM20A2V1B FVXM25A2V1B FVXM35A2V1B FVXM50A2V1B...

Page 2: ...ical data 11 11 1 Wiring diagram 12 11 1 1 Unified wiring diagram legend 12 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask...

Page 3: ...ticularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install...

Page 4: ...0 mA 4 1 3 Setting the wireless LAN The customer is responsible for providing Smartphone or tablet with minimum supported version of Android or iOS specified on http www onlinecontroller daikineurope...

Page 5: ...trical wiring box cover 1 Open the terminal block 2 Remove 1 screw from the electrical wiring box 3 Unhook the 2 tabs on the electrical wiring box cover and remove it b a c c b a Screw b Wiring box co...

Page 6: ...iping hole location g Left bottom piping hole location h Right bottom piping hole location 6 Temporarily secure the mounting plate on the wall 7 Make sure the mounting plate is level 8 Mark the centre...

Page 7: ...it 44 22 Secure the unit to the extra filler board and to the floor using 6 screws M4 25L field supply 6 23 When the complete installation is finished attach the front panel and the front grille in th...

Page 8: ...extension hose use a polyvinyl adhesive agent for glueing Condensation Take measures against condensation Insulate the complete drain piping in the building To connect the drain piping to the indoor...

Page 9: ...higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation 6 2 Connecting the re...

Page 10: ...Pull the wires to make sure that they are securely attached then retain the wires with the cable clamp 6 Make sure that the wires do not come in contact with the metal parts of the heat exchanger 7 I...

Page 11: ...performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit to make sure that all functions and parts are working properl...

Page 12: ...ght emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live Symbol Me...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...3P477070 2H 2020 06 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: