background image

 

D-EIMWC00908-16EN - 28/52 

Operation 

 

Operator’s responsibilities 

It  is  important  that  the  operator  is  appropriately  trained  and  becomes  familiar  with  the  system  before  operating  the 
machine. In addition to reading this manual, the operator must study the microprocessor operating manual and the wiring 
diagram in order to understand start-up sequence, operation, shutdown sequence and operation of all the safety devices.  
During  the  machine’s  initial  start-up  phase,  a  technician  authorized  by  the  manufacturer  is  available  to  answer  any 
questions and to give instructions as to the correct operating procedures. 
The  operator  is  advised  to  keep  a  record  of  operating data  for  every  installed machine. Another  record should  also be 
kept of all the periodical maintenance and servicing activities. 
If the operator notes abnormal or unusual operating conditions, he is advised to consult the technical service authorized 
by the manufacturer. 

Compressor Operation  

The  EEWD  FZ  compressors  are  two-stage.  Suction  gas  enters  the  compressor  through  inlet  guide  vanes  that  can  be 
opened and closed to control refrigerant flow as the cooling load changes. The suction gas enters the first stage impeller, 
is  compressed,  and  travels  through  the  vaned  radial  diffuser  to  the  second  stage  impeller  where  compression  is 
completed. The gas travels to the condenser via the discharge volute, which converts any remaining velocity pressure to 
static pressure.  
Motor  cooling  is  accomplished  by  utilizing  the  refrigerant  effect  of  high-pressure  liquid  refrigerant  from  the  condenser 
expanded to a gas within the compressor. The refrigerant cools VFD heat sinks and the motor.  
A five-axis magnetic bearing system supports the motor/compressor shaft, resisting radial and thrust forces. The bearing 
control system uses shaft position feedback to continually adjust the bearing to keep the shaft in the correct position. In 
the event of a power failure, the compressor motor acts as a generator and powers the bearing support system during 
coastdown. There is also a system to gently de-levitate the shaft.  
Many  controls  are  mounted  directly  on  the  compressor  where  they  monitor  and  control  compressor  operation.  These 
compressor  controls  are  interfaced  with  the  conventional  MicroTech  II  controls  to  provide  a  complete  chiller  control 
system. 

System Water Volume  

It  is  important  to  have  adequate  water  volume  in  the  system  to  provide  an  opportunity  for  the  chiller  to  sense  a  load 
change, adjust to the change, and stabilize. As the expected load change becomes more rapid, a greater water volume 
is needed. The system water volume is the total amount of water in the evaporator, air handling products and associated 
piping. If the water volume is too low, operational problems can occur including rapid compressor cycling, rapid loading 
and unloading of compressors, erratic refrigerant flow in the chiller, improper motor cooling, shortened equipment life and 
other undesirable consequences.  
Some  of  the  things  the  designer  should  consider  when  looking  at  water  volume  are  the  minimum  cooling  load,  the 
minimum chiller plant capacity during the low load period and the desired cycle time for the compressors.  
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of 
“liters of water volume equal to 120 to 180 times the chilled water flow rate in liter/sec” is often used.  
For  process  applications  where  the  cooling  load  can  change  rapidly,  additional  system  water  volume  is  needed.  A 
process  example  would  be  a  quenching  tank.  The  load  would  be  very  stable  until  the  hot  material  is  immersed  in  the 
water  tank.  Then,  the  load  would  increase  drastically.  For  this  type  of  application,  system  volume  may  need  to  be 
increased.  
Since  there  are  many  other  factors  that  can  influence  performance,  systems  may  successfully  operate  below  these 
suggestions. However, as the water volume decreases below these suggestions, the possibility of problems increases. 

Variable Speed Pumping  

Variable water flow involves inversely changing the water flow through the evaporator as the load changes.  Cchillers are 
designed for this duty provided that the rate of change in water flow is slow and the minimum and maximum flow rates for 
the vessel, as shown in the vessel pressure drops figures, are not exceeded.  
The  recommended maximum change  in  water  flow  is  5% of  the  allowable  flow  change  per  minute.  Flow  is  usually  not 
reduced below 50 percent of design flow (provided vessel minimum flow rates are not exceeded). 

MicroTech II Control  

Chillers are equipped with the MicroTech II control system consisting of:  
 

  Operator interface touchscreen panel with a 15-inch Super VGA color screen.  

  Control Panel containing the MicroTech II unit controller, two MicroTech II compressor controllers with connections to 

the compressor-mounted controls, and various switches and field connection terminals.  

 
Operating instructions for the MicroTech II controller are contained in Operating Manual.  
 

 

Summary of Contents for C10FZXS

Page 1: ...nual Installation Operation and Maintenance Manual Frictionless Centrifugal Chiller EWWD320 C10FZXS Cooling capacity from 114 to 1048 kW Refrigerant R 134a Original Instructions Installation Operation...

Page 2: ...assume no liability whatsoever for any direct or indirect damage in the widest sense of the term ensuing from or connected with the use and or interpretation of this Manual The entire content is prote...

Page 3: ...nel for 1 and 2 compressors unit 8 9 Label Identification 1 Non flammable gas symbol 6 Cable tightening warning 2 Manufacturer s logo 7 Water circuit filling warning 3 Gas type 8 Lifting instructions...

Page 4: ...22 Field Wiring Diagram Notes 24 Control Wiring 24 VFD Line Harmonics 24 Current Harmonics 24 Voltage Harmonics 24 Line Reactors 24 Harmonic Filter 25 EMI Electro Magnetic Interference and RFI Radio F...

Page 5: ...gerant used 47 Disposal 47 Index of tables Table 1 Acceptable water quality limits 14 Table 2 Electrical data 21 Table 3 Pwer wiring recommended fuses and cables 22 Table 4 Electrical data 26 Table 5...

Page 6: ...automatically controlled fluid chilling units featuring oil free magnetic bearing compressors Each unit is completely assembled and factory tested before shipment Magnitude chillers are equipped with...

Page 7: ...eat recovery Refrigerant D R 134a P R 407c Q R 410a Capacity class in kW Cooling Always 3 digit code Model series Letter A B major modification Inverter Non inverter Z Inverter Efficiency level S Stan...

Page 8: ...pressure drop 4 kPa 24 3 24 5 28 2 23 7 25 3 29 3 Insulation material None available as an option Compressor Type Frictioneless Centrifugal Compressor Oil free Sound level Sound Power Cooling dB A 89...

Page 9: ...line ATTENTION Storing in condensing atmosphere may damage the electronic components Operation ATTENTION Daikin EWWD FZ chillers are suitable for stationary installations only For any moving or marine...

Page 10: ...D EIMWC00908 16EN 10 52 Figure 1 Operating limits Other limits are Maximum startup evaporator inlet fluid temperature 32 C Maximum non operating inlet fluid temperature 38 C...

Page 11: ...jury Avoid introducing solid objects into the water pipes while the machine is connected to the system A mechanical filter must be installed on the water pipe connected to the heat exchanger inlet The...

Page 12: ...ground prepare a strong cement base that is at least 250 mm wider and longer than the machine Also this base must be strong enough to support the weight of the machine as stated in the technical spec...

Page 13: ...em during service 3 Manual or automatic air venting device at the system s highest point drain device at the system s lowest point Neither the evaporator nor the heat recovery device must be positione...

Page 14: ...quipment caused by failure to treat water or by improperly treated water Figure 3 Water piping connection for evaporator and condenser Legend translation Gauge Gauge Flexible connector Flexible connec...

Page 15: ...ult in damage to some of the machine s components Damage caused by freezing is not covered by the warranty Loss of flow protection All chiller are equipped with redundant differential pressure switche...

Page 16: ...D EIMWC00908 16EN 16 52 Figure 4 Evaporator pressure drop...

Page 17: ...D EIMWC00908 16EN 17 52...

Page 18: ...D EIMWC00908 16EN 18 52 Figure 5 Condenser pressure drop...

Page 19: ...D EIMWC00908 16EN 19 52 Figure 4 and 5 legend Label Size Label Size A 320FZ D 640FZ B 430FZ E 860FZ C 520FZ F C10FZ...

Page 20: ...e event of certain malfunctions ATTENTION This unit is designed for indoor installation Check that there is sufficient air circulation through the machine Possible damage from inhalation of refrigeran...

Page 21: ...charged with high voltage for a short period of time The unit can be worked on again after it has been switched of for 10 minutes Please consult the compressor manual for further details CAUTION The...

Page 22: ...ith copper wire and copper lugs only The table below is a reference only for dimensioning protection devices and wiring Due to different needs and local codes the customer may select different compone...

Page 23: ...low Switch Remote Start Stop Mode Switch Analog Input Terminals Leaving Water Reset Demand Limit Evap GPM Condens GPM Digital Output Terminals Evap Water Pump 1 2 Condens Water Pump 1 2 Tower Stage 1...

Page 24: ...supplied from a factory wired transformer located in the electrical box Control wiring must be of suitable size in accordance with local regulations VFD Line Harmonics Despite their many benefits car...

Page 25: ...EMC directives in a compact efficient light weight design The high common mode and differential mode reduction in the critical 150kHz to 30MHz frequencies assures that potential interference from AC d...

Page 26: ...t J11 the shield connects to GND the blue white wire to the connection and the white blue to the connection Note that Chiller B does not have or need an isolation board 5 Verify correct nodes on each...

Page 27: ...nd the compressor with maximum hours will stop first and so on Units with higher numbers will stage on in sequence The Modes setpoints will do several different types of operation Normal Efficiency St...

Page 28: ...stem to provide an opportunity for the chiller to sense a load change adjust to the change and stabilize As the expected load change becomes more rapid a greater water volume is needed The system wate...

Page 29: ...tically when the start to start timer expires Transfer Back to Grid Power Proper transfer from stand by generator power back to grid power is essential to avoid compressor damage ATTENTION Stop the ch...

Page 30: ...essors and compressed The high pressure refrigerant gas is sent to the condenser where flowing shell side the superheated refrigerant vapour cools down and starts to condense and then the liquid is su...

Page 31: ...D EIMWC00908 16EN 31 52 Figure 9 Refrigeration cycle a Single compressor unit b Dual compressor unit...

Page 32: ...ass Evaporator and condenser differential pressure switches Safety valve Valve Mechanical filter flare connection Check valve WOC Condenser leaving water centerature sensor WIC Condenser water inlet t...

Page 33: ...r speed adjusts to changes in load and or condensing temperature As compressor speed reduces due to lower loads and or condensing temperatures energy consumption dramatically reduces Part load energy...

Page 34: ...D EIMWC00908 16EN 34 52 Figure 12 Compressor overview...

Page 35: ...ck disconnector switch terminals The power supply voltage must be the same as that on the nameplate Maximum allowed tolerance 10 Voltage unbalance between the three phases must not exceed 3 Fill the w...

Page 36: ...uld cause malfunction of the control components and undesired triggering of the thermal protection devices along with a considerable reduction in the life of the contactors and electric motors Unbalan...

Page 37: ...em operated and flow balanced to meet unit requirements Electrical Power leads connected to the unit power panel s All interlock wiring complete between control panel and complies with specifications...

Page 38: ...the chiller is not The following procedures therefore must take the peculiarities of the entire system into account Shutdown If the unit is to be secured for several days and is already off due to la...

Page 39: ...way 3 Open the compressor disconnect switch Set the manual COMPRESSOR and UNIT ON OFF switches in the Unit Control Panel to the OFF position 4 Check for corrosion and clean and paint rusted surfaces 5...

Page 40: ...rheat low super cooling value Additionally a low level of liquid refrigerant inside the evaporator may be recognized In this case add R134a refrigerant only The system has been provided with a charge...

Page 41: ...for units that run for a season of approximately 90 days year at seasonal start up It is important that during initial start up and periodically during operation routine verifications and checks are...

Page 42: ...include all the weekly ones 2 The annual or early season activities include all weekly and monthly activities 3 Machine operating values should be read on a daily basis thus keeping high observation s...

Page 43: ...t the rated conditions Note When the load or the cooling water temperature vary for example due to cooling tower fans starting stopping so does the subcooling and it requires several minutes to stabil...

Page 44: ...etween 0 5 and 1 C 4 Check the subcooling value The subcooling value must be between 4 and 6 C a With reference to the above mentioned values the subcooling will be lower at 70 100 load and higher at...

Page 45: ...is sensor is located on the evaporator inlet water connection and is used for monitoring the return water temperature Evaporator differential pressure switches Two sensors are located between the evap...

Page 46: ...r Entering water temperature C _________ Condenser Pressure drop kPa _________ Condenser Water flow rate m 3 h _________ Refrigerant side measurements Compressors Compressor 1 Load _____ Compressor 2...

Page 47: ...l power supply must be within the voltage limits and without voltage harmonics or sudden changes 5 The three phase power supply must not have un unbalance between phases exceeding 3 The machine must s...

Page 48: ...gerant charge Factory Field h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The...

Page 49: ...osal The unit is made of metal and plastic parts All these parts must be disposed of in accordance with the local regulations in terms of disposal Lead batteries must be collected and taken to specifi...

Page 50: ...D EIMWC00908 16EN 50 52...

Page 51: ...D EIMWC00908 16EN 51 52...

Page 52: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...

Reviews: