D-EIMWC00908-16EN - 15/52
Unless the heat exchangers are completely emptied and cleaned with anti-freeze solution, they have to be protected
against freezing.
Two or more of below protection methods should be considered when designing the system as a whole:
1. Continuous water flow circulation inside piping and exchangers
2. Addition of an appropriate amount of glycol inside the water circuit
3. Additional heat insulation and heating of exposed piping
4. Emptying and cleaning of the heat exchanger during the winter season
ATTENTION
It is the responsibility of the installer and/or of local maintenance personnel to ensure that two or more of the
described anti-freeze methods are used. Make sure that appropriate anti-freeze protection is maintained at all
times. Failure to follow the instructions above could result in damage to some of the machine’s components.
Damage caused by freezing is not covered by the warranty.
Loss of flow protection
All chiller are equipped with redundant differential pressure switches factory mounted to protect evaporator and
condenser from loss of flow
Cooling Towers
The condenser water flow rate must be checked to be sure that it conforms to the system design. A tower bypass valve,
controlled by the unit controller, is required to control the minimum condenser entering temperature. Unless the system
and chiller unit are specifically designed for them,
condenser bypass
or variable condenser flow is not recommended,
since low condenser flow rates can cause unstable operation and excessive tube fouling.
Cooling towers are normally selected for condenser water inlet water temperatures between 24°C and 32°C.
ATTENTION
Tower water treatment is essential for continued efficient and reliable unit operation. If not available in-house,
competent water treatment specialists should be contracted.
Summary of Contents for C10FZXS
Page 16: ...D EIMWC00908 16EN 16 52 Figure 4 Evaporator pressure drop...
Page 17: ...D EIMWC00908 16EN 17 52...
Page 18: ...D EIMWC00908 16EN 18 52 Figure 5 Condenser pressure drop...
Page 34: ...D EIMWC00908 16EN 34 52 Figure 12 Compressor overview...
Page 50: ...D EIMWC00908 16EN 50 52...
Page 51: ...D EIMWC00908 16EN 51 52...