Service and limited warranty
All machines are factory-tested and guaranteed for 12 months as of the first start-up or 18 months as of delivery.
These machines have been developed and constructed according to high quality standards ensuring years of failure-free
operation. It is important, however, to ensure proper and periodical maintenance in accordance with all the procedures
listed in this manual.
We strongly advise stipulating a maintenance contract with a service authorized by the manufacturer in order to ensure
efficient and problem-free service, thanks to the expertise and experience of our personnel.
It must also be taken into consideration that the unit requires maintenance also during the warranty period.
It must be borne in mind that operating the machine in an inappropriate manner, beyond its operating limits or not
performing proper maintenance according to this manual can void the warranty.
Observe the following points in particular, in order to conform to warranty limits:
1.
The machine must be installed accordingly to the requirements of this manual
2.
The machine must be started accordingly to the requirements of this manual
3.
The machine cannot function beyond the specified limits
4.
The electrical power supply must be within the voltage limits and without voltage harmonics or sudden changes.
5.
The three-phase power supply must not have un unbalance between phases exceeding 3%. The machine must
stay turned off until the electrical problem has been solved.
6.
No safety device, either mechanical, electrical or electronic must be disabled or overridden.
7.
The water used for filling the water circuits must be clean and suitably treated. A mechanical filter must be installed
at the point closest to the Condenser inlet.
8.
Unless there is a specific agreement at the time of ordering, the Condenser water flow rate must never be above
120% and below 80% of the nominal flow rate.
Periodic obligatory checks and starting up of appliances under
Pressure
The units are included in category IV of the classification according to European Directive PED 2014/68/EU.
For chillers belonging to this category, some local regulations require a periodic inspection by an authorized agency.
Please check with your local requirements.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.
Refrigerant type:
R134a
GWP(1) value:
1430
(1) GWP =
Global Warming Potential
The refrigerant quantity is indicated on the unit name plate.
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact
your local dealer for more information.
Summary of Contents for C10FZXS
Page 16: ...D EIMWC00908 16EN 16 52 Figure 4 Evaporator pressure drop...
Page 17: ...D EIMWC00908 16EN 17 52...
Page 18: ...D EIMWC00908 16EN 18 52 Figure 5 Condenser pressure drop...
Page 34: ...D EIMWC00908 16EN 34 52 Figure 12 Compressor overview...
Page 50: ...D EIMWC00908 16EN 50 52...
Page 51: ...D EIMWC00908 16EN 51 52...