background image

English

16

NOTES

Use ring-type crimp style terminal for connections to the 
power terminal block. (

Refer to Fig. 6

)

Also, insulate the crimped area by attaching an insula-
tion sleeve, etc.
If these are not available, see the following section.
(a) Wiring of different thicknesses cannot be connected 

to the power terminal block.
(A loose connection could cause abnormal heating.)

(b) When connecting wire of the same diameter, make 

the connection as shown in the figure 7.

Use an appropriate screwdriver for tightening the termi-
nal screw.
Using a screwdriver that is too small could damage the 
screw head and prevent proper tightening.

Over tightening the terminal screw could damage the 
screw.
Refer to the Table 4 for the terminal screw tightening 
torque.

When fastening the wire, use the included clamp 2)-1 
so as not to apply tensile force to the wire connection and then securely fasten the wire. Also, after wiring 
is completed, organize the wiring so that the Electrical Components Box lid does not pop up and then prop-
erly replace the Electrical Components Box lid.
Make sure no wires are pinched when replacing the Electrical Components Box lid.
Always use the wire through hole to protect the wires.

Do not pass the transmission wiring and power supply wiring through the same locations and outside of the 
unit keep them separated by at least 2 in..
Not doing so could cause the transmission wiring to pick up electric noise (external noise) and result in a 
malfunction or breakdown.

After the wiring working is complete, use sealer (field supply) to seal closed the wire through hole.
(Entry by small animals, etc., could cause a malfunction.)

8. INITIAL SETTING

When the refrigerant piping and wire installation work is completed, make the following settings as required.

1. Setting for when connecting the COOL/HEAT SELECTOR to the BS unit.

Setting description

Set the input signal from the COOL/HEAT SELECTOR (sold separately) to ON/OFF.

Setting method

Set the dip switches (DS1-1) on PCB (A1P) as shown at left before turning on the power to the BS unit.

NOTES

This setting is read by the microcomputer when the BS unit power is turned on.

Be sure to make the setting before turning on the power.

Always close the Electrical Components Box lid after making the setting.

2. Setting when changing the “Automatic mode differential” in the Cooling/Heating Automatic Oper-

ation Mode.

Insulation sleeve

Electric wire

Ring-type crimp 
style terminal

Fig. 6

Connect wires of the 
same gauge to both 
sides.

Do not connect 
wires of the same 
gauge to one side.

Do not connect 
wires of different 
gauges.

Fig. 7

Terminal screw size

M3.5 (COOL/HEAT SELECTOR/transmission 

wiring terminal block (A1P))

M4 (Power supply terminal block)
M4 (Ground terminal)

0.58-0.71

0.87-1.06
1.12-1.37

Tightening torque (ft · lbf)

Table 4

Turn on DS1-1.

ON

OFF

DS1-1

ON

OFF

DS1-2

Summary of Contents for BSVQ36PVJU

Page 1: ...erence This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn...

Page 2: ...DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in...

Page 3: ...ing is secured that specified wires are used and that no external forces act on the terminal connections or wires Improper connections or installation may result in fire When wiring position the wires...

Page 4: ...not install the air conditioner in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in...

Page 5: ...nected Normal operation is not possible when connected to other units 2 2 PRECAUTIONS Hold the unit by the Hanging brackets 4 points when opening the box and moving it and do not lift it hold ing on t...

Page 6: ...cations where an inspection hole Refer to Fig 2 can be installed to Electrical Components Box side See Note Where the total piping length involving indoor unit and outside unit is below the allowable...

Page 7: ...e Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are ke...

Page 8: ...pension bolts Be sure to use the nuts M8 or M10 3 pcs 4 locations and washers field supply from both the top and bottom sides of the hanging bracket and make sure they are tightened correctly NOTES Th...

Page 9: ...R410A dur ing installation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outside...

Page 10: ...2 below and Table 1 2 select the piping size between the outside unit refrigerant branch kit and BS unit and between the BS unit and the indoor unit refrigerant branch kit Example of connection 1 Whe...

Page 11: ...Q 54 5 8 1 2 3 8 5 8 3 8 54 Q 72 3 4 5 8 3 4 72 Q 96 7 8 3 4 7 8 in Capacity type of indoor units Piping size outer diameter Gas pipe Liquid pipe 07 09 12 18 1 2 1 4 24 30 36 48 5 8 3 8 72 3 4 96 7 8...

Page 12: ...pe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping Liquid pipe Site piping Accessory pipes 1 2 Accessory pipes 1 2 Accessory pipes 1 1 BSVQ96P t...

Page 13: ...sulation field supply with the seams facing up See figure at right BSVQ36 60P type BS unit Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2...

Page 14: ...units Mark each BS unit as unit A unit B and be sure the terminal board wiring to the outside unit and indoor unit are properly matched If wiring and piping between the out side unit BS unit and an in...

Page 15: ...the following ranges Exceeding these limits could cause a transmission error 1 Between an outside unit and BS unit Between a BS unit and indoor unit and Between a BS unit and BS unit Maximum wiring le...

Page 16: ...s both the power supply wire and the ground wire together through the wire through hole right and into the Electrical Components Box and use the included clamps 2 to securely hold the wires in 2 place...

Page 17: ...t keep them separated by at least 2 in Not doing so could cause the transmission wiring to pick up electric noise external noise and result in a malfunction or breakdown After the wiring working is co...

Page 18: ...ed by the operation remote controller while the indoor unit power is turned on When the indoor unit outside unit and BS unit installation work is completed confirm that it is safe even with the power...

Page 19: ...3P194121 3M EM07A062C 0909 FS...

Reviews: