9

English

6-3 PIPING CONNECTION WORK PRECAUTIONS

When brazing refrigerant piping, begin working after replacing the nitrogen (*1) or perform brazing while 
nitrogen is flowing in the refrigerant piping (*2) (

Refer to Fig. 5

), and at the end made the indoor unit and 

BS unit flare or flange connections.
(*1) For details on nitrogen replacement, see the “VRV Installation Manual” (available at any Daikin dealer).
(*2) The pressure regulator for the nitrogen released when doing the brazing should be set to about 

2.9 psi (Enough to feel a slight breeze on your cheek).

NOTES

Do not use an anti-oxidizing agent when brazing the piping. Residual debris could clog the piping or cause 
parts to malfunction.

Do not use a flux when brazing the refrigerant pipe joints.
Using a chlorine flux may cause the pipes to corrode, and if it contains fluoride it may cause the refrigerant 
lubricant to deteriorate, adversely affecting the refrigerant piping system.
Use phosphor copper brazing (B-Cu93P-710/795: ISO 3677) which does not require flux.

6-4 PIPING SIZE SELECTION

From 

Example of connection 1

 and 

2

 below and 

Table 1

2

, select the piping size between the outside unit 

(refrigerant branch kit) and BS unit, and between the BS unit and the indoor unit (refrigerant branch kit).

Example of connection 1: When 1 indoor unit is connected downstream from the BS unit

Example of connection 2: When there is a branch downstream from the BS unit

Refrigerant piping

Valve

Pressure-reducing valve

Part to be brazed

Taping

Nitrogen

Nitrogen

Fig. 5

To refrigerant branch 
kit or outside unit

*

Suction gas pipe

<Upstream>

<Downstream>

Gas pipe

Indoor unit

Liquid pipe

HP/LP gas pipe

Liquid pipe

Determine using 

Table 1

 based 

on the total capacity of the indoor 
units connected downstream.

Select from 

Table 2

 depending 

on the capacity type of the 
indoor unit.

BS

unit

Indoor unit

Indoor unit

Indoor unit

Gas pipe

Liquid pipe

Determine using 

Table 1

 based 

on the total capacity of the indoor 
units connected downstream.

For information on selecting the size of piping between 
the refrigerant branch kits and between a refrigerant 
branch kit and the indoor unit, refer to the Installation 
Manual that came with the outside unit or Engineering 
data book.

To refrigerant branch 
kit or outside unit

Suction gas pipe

HP/LP gas pipe

Liquid pipe

BS

unit

Refrigerant branch kit

<Upstream>

<Downstream>

Summary of Contents for BSVQ36PVJU

Page 1: ...erence This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn...

Page 2: ...DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in...

Page 3: ...ing is secured that specified wires are used and that no external forces act on the terminal connections or wires Improper connections or installation may result in fire When wiring position the wires...

Page 4: ...not install the air conditioner in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in...

Page 5: ...nected Normal operation is not possible when connected to other units 2 2 PRECAUTIONS Hold the unit by the Hanging brackets 4 points when opening the box and moving it and do not lift it hold ing on t...

Page 6: ...cations where an inspection hole Refer to Fig 2 can be installed to Electrical Components Box side See Note Where the total piping length involving indoor unit and outside unit is below the allowable...

Page 7: ...e Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are ke...

Page 8: ...pension bolts Be sure to use the nuts M8 or M10 3 pcs 4 locations and washers field supply from both the top and bottom sides of the hanging bracket and make sure they are tightened correctly NOTES Th...

Page 9: ...R410A dur ing installation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outside...

Page 10: ...2 below and Table 1 2 select the piping size between the outside unit refrigerant branch kit and BS unit and between the BS unit and the indoor unit refrigerant branch kit Example of connection 1 Whe...

Page 11: ...Q 54 5 8 1 2 3 8 5 8 3 8 54 Q 72 3 4 5 8 3 4 72 Q 96 7 8 3 4 7 8 in Capacity type of indoor units Piping size outer diameter Gas pipe Liquid pipe 07 09 12 18 1 2 1 4 24 30 36 48 5 8 3 8 72 3 4 96 7 8...

Page 12: ...pe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping Liquid pipe Site piping Accessory pipes 1 2 Accessory pipes 1 2 Accessory pipes 1 1 BSVQ96P t...

Page 13: ...sulation field supply with the seams facing up See figure at right BSVQ36 60P type BS unit Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2...

Page 14: ...units Mark each BS unit as unit A unit B and be sure the terminal board wiring to the outside unit and indoor unit are properly matched If wiring and piping between the out side unit BS unit and an in...

Page 15: ...the following ranges Exceeding these limits could cause a transmission error 1 Between an outside unit and BS unit Between a BS unit and indoor unit and Between a BS unit and BS unit Maximum wiring le...

Page 16: ...s both the power supply wire and the ground wire together through the wire through hole right and into the Electrical Components Box and use the included clamps 2 to securely hold the wires in 2 place...

Page 17: ...t keep them separated by at least 2 in Not doing so could cause the transmission wiring to pick up electric noise external noise and result in a malfunction or breakdown After the wiring working is co...

Page 18: ...ed by the operation remote controller while the indoor unit power is turned on When the indoor unit outside unit and BS unit installation work is completed confirm that it is safe even with the power...