NOTE

The refrigerant R410A requires strict cautions for keeping the system clean, dry and tight.
A. Clean and dry

Foreign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from 
getting mixed into the system.

B. Tight

R410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the 
earth’s protection against harmful ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it is released. Therefore we should take spe-
cial attention to check the tightness of the installation.
Read the chapter “Refrigerant piping work” carefully and follow these procedures correctly.

2. BEFORE INSTALLATION

2-1 CAUTION CONCERNING NEW REFRIGERANT SERIES

Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. (If 
the refrigerant is charged in a state of gas, its composition changes and the system will not work properly.)
The indoor/outside unit is for R410A. See the catalog for indoor/outside unit models which can be connected.
(Normal operation is not possible when connected to other units.)

2-2 PRECAUTIONS

Hold the unit by the Hanging brackets (4 points) when opening the box and moving it, and do not lift it hold-
ing on to any other part especially the refrigerant piping.

About installation of outside and indoor unit, refer to the installation manual provided with the outside and 
the indoor unit.

This unit, both indoor and outside, is suitable for installation in a commercial and light industrial environment.
If installed as a household appliance it could cause electromagnetic interference.

2-3 ACCESSORIES

Check the following accessories are included with your unit.

NOTE

Do not throw away any of the accessories until installation is complete.

BSVQ36 · 60PVJU

BSVQ96PVJU

Name

1) Accessory pipes

1) Accessory pipes

2) Clamp

3) Insulation tube

Explanation 

Document

(BSVQ36 only)

(BSVQ60 only)

Quantity

1 pc.

1 pc.

1 pc.

2 pcs.

6 pcs.

10 pcs.

2 pcs.

3 pcs.

1 copy

Shape

1)-1

φ

3/8

1)-2

φ

5/8

1)-1

φ

1/2

1)-2

φ

5/8

2)-1

(Small)

2)-2

(Large)

3)-1

(Small)

3)-2

(Large)

Installation 
manual

Name

1) Accessory pipes

2) Clamp

3) Insulation tube

Explanation 

Document

Quantity

1 pc.

2 pcs.

6 pcs.

10 pcs.

2 pcs.

2 pcs.

1 pc.

1 copy

Shape

1)-1

φ

3/4

1)-2

φ

3/4

2)-1

(Small)

2)-2

(Large)

3)-1

(Small)

3)-2

(Medium)

3)-3

(Large)

Installation 
manual

Summary of Contents for BSVQ36PVJU

Page 1: ...erence This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn...

Page 2: ...DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in...

Page 3: ...ing is secured that specified wires are used and that no external forces act on the terminal connections or wires Improper connections or installation may result in fire When wiring position the wires...

Page 4: ...not install the air conditioner in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in...

Page 5: ...nected Normal operation is not possible when connected to other units 2 2 PRECAUTIONS Hold the unit by the Hanging brackets 4 points when opening the box and moving it and do not lift it hold ing on t...

Page 6: ...cations where an inspection hole Refer to Fig 2 can be installed to Electrical Components Box side See Note Where the total piping length involving indoor unit and outside unit is below the allowable...

Page 7: ...e Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are ke...

Page 8: ...pension bolts Be sure to use the nuts M8 or M10 3 pcs 4 locations and washers field supply from both the top and bottom sides of the hanging bracket and make sure they are tightened correctly NOTES Th...

Page 9: ...R410A dur ing installation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outside...

Page 10: ...2 below and Table 1 2 select the piping size between the outside unit refrigerant branch kit and BS unit and between the BS unit and the indoor unit refrigerant branch kit Example of connection 1 Whe...

Page 11: ...Q 54 5 8 1 2 3 8 5 8 3 8 54 Q 72 3 4 5 8 3 4 72 Q 96 7 8 3 4 7 8 in Capacity type of indoor units Piping size outer diameter Gas pipe Liquid pipe 07 09 12 18 1 2 1 4 24 30 36 48 5 8 3 8 72 3 4 96 7 8...

Page 12: ...pe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping Liquid pipe Site piping Accessory pipes 1 2 Accessory pipes 1 2 Accessory pipes 1 1 BSVQ96P t...

Page 13: ...sulation field supply with the seams facing up See figure at right BSVQ36 60P type BS unit Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2...

Page 14: ...units Mark each BS unit as unit A unit B and be sure the terminal board wiring to the outside unit and indoor unit are properly matched If wiring and piping between the out side unit BS unit and an in...

Page 15: ...the following ranges Exceeding these limits could cause a transmission error 1 Between an outside unit and BS unit Between a BS unit and indoor unit and Between a BS unit and BS unit Maximum wiring le...

Page 16: ...s both the power supply wire and the ground wire together through the wire through hole right and into the Electrical Components Box and use the included clamps 2 to securely hold the wires in 2 place...

Page 17: ...t keep them separated by at least 2 in Not doing so could cause the transmission wiring to pick up electric noise external noise and result in a malfunction or breakdown After the wiring working is co...

Page 18: ...ed by the operation remote controller while the indoor unit power is turned on When the indoor unit outside unit and BS unit installation work is completed confirm that it is safe even with the power...

Page 19: ...3P194121 3M EM07A062C 0909 FS...

Reviews: