Table 3 

MCA: Min. Circuit Amps (A); 

MFA: Max. Fuse Amps (A)

NOTES

The above Table 3 of Electrical Characteristics refers to one BS unit.

See the Engineering data book for other details.

7-4 WIRING EXAMPLE

Here is shown a wiring example for one system transmission wiring.

Connect terminals F1 and F2 (TO IN/D UNIT) on the control PCB (A1P) in the outside unit Electrical Com-
ponents Box and terminals F1 and F2 (TO OUT/D UNIT) of the control PCB (A1P) of the first BS unit A.

NOTE

1.

Connect cooling-dedicated air conditioners to terminals F1 and F2 (TO OUT/D UNIT) of the final BS unit.

2.

Use 2-core wire for the transmission wiring. Using a multi-core wire with 3 or more cores when two or more 
indoor units are used at once could cause abnormal stoppage. (Only use 3-core wire in the COOL/HEAT 
SELECTOR.)

3.

Absolutely do not connect the power supply wiring to the transmission wiring terminal block. Doing so 
could damage the entire system.

4.

For the transmission wiring, use wire that is within the following ranges. Exceeding these limits could 
cause a transmission error.

(1)

Between an outside unit and BS unit,
Between a BS unit and indoor unit, and
Between a BS unit and BS unit

Maximum wiring length: 3280 ft or less
Total wiring length: 6560 ft or less
Branch point max: 16 branch points

(2)

Between a BS unit and COOL/HEAT SELECTOR

Maximum wiring length: 1640 ft or less

Units

Power supply

Model

Type

Hz

Voltage

Min.

Max.

MCA

MFA

BSVQ36P
BSVQ60P
BSVQ96P

VJ

60

208~230

187

253

0.1

15

F1 F2

F1

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F2 F1 F2

F1 F2

F1 F2 F1 F2

F1 F2 F1 F2

A

A

B C

A

B C

A

B C

B

C

A

B

C

A

B

C

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(2)

(2)

(2)

Absolutely do not 
connect the power 
supply wiring.

Transmission wiring

Use 2-core wires.
(There is no polarity.)

COOL/HEAT SELECTOR wiring

Use 3-core wires. (There is polarity. 
Match the terminal numbers.)

Cooling/Heating selectable indoor unit

Cooling-dedicated 

indoor unit

Outside unit

BS unit A

BS unit B

Final BS unit

C/H SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

C/H SELECTOR

C/H SELECTOR

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

branch

Sub-branching

Summary of Contents for BSVQ36PVJU

Page 1: ...erence This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn...

Page 2: ...DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in...

Page 3: ...ing is secured that specified wires are used and that no external forces act on the terminal connections or wires Improper connections or installation may result in fire When wiring position the wires...

Page 4: ...not install the air conditioner in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off or result in...

Page 5: ...nected Normal operation is not possible when connected to other units 2 2 PRECAUTIONS Hold the unit by the Hanging brackets 4 points when opening the box and moving it and do not lift it hold ing on t...

Page 6: ...cations where an inspection hole Refer to Fig 2 can be installed to Electrical Components Box side See Note Where the total piping length involving indoor unit and outside unit is below the allowable...

Page 7: ...e Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are ke...

Page 8: ...pension bolts Be sure to use the nuts M8 or M10 3 pcs 4 locations and washers field supply from both the top and bottom sides of the hanging bracket and make sure they are tightened correctly NOTES Th...

Page 9: ...R410A dur ing installation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outside...

Page 10: ...2 below and Table 1 2 select the piping size between the outside unit refrigerant branch kit and BS unit and between the BS unit and the indoor unit refrigerant branch kit Example of connection 1 Whe...

Page 11: ...Q 54 5 8 1 2 3 8 5 8 3 8 54 Q 72 3 4 5 8 3 4 72 Q 96 7 8 3 4 7 8 in Capacity type of indoor units Piping size outer diameter Gas pipe Liquid pipe 07 09 12 18 1 2 1 4 24 30 36 48 5 8 3 8 72 3 4 96 7 8...

Page 12: ...pe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping Liquid pipe Site piping Accessory pipes 1 2 Accessory pipes 1 2 Accessory pipes 1 1 BSVQ96P t...

Page 13: ...sulation field supply with the seams facing up See figure at right BSVQ36 60P type BS unit Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2...

Page 14: ...units Mark each BS unit as unit A unit B and be sure the terminal board wiring to the outside unit and indoor unit are properly matched If wiring and piping between the out side unit BS unit and an in...

Page 15: ...the following ranges Exceeding these limits could cause a transmission error 1 Between an outside unit and BS unit Between a BS unit and indoor unit and Between a BS unit and BS unit Maximum wiring le...

Page 16: ...s both the power supply wire and the ground wire together through the wire through hole right and into the Electrical Components Box and use the included clamps 2 to securely hold the wires in 2 place...

Page 17: ...t keep them separated by at least 2 in Not doing so could cause the transmission wiring to pick up electric noise external noise and result in a malfunction or breakdown After the wiring working is co...

Page 18: ...ed by the operation remote controller while the indoor unit power is turned on When the indoor unit outside unit and BS unit installation work is completed confirm that it is safe even with the power...

Page 19: ...3P194121 3M EM07A062C 0909 FS...

Reviews: