5 Preparation
Installer reference guide
8
AZQS100~14 AZQS100~140B7Y1B
Split system air conditioners
4P385529-1B – 2016.10
If the outdoor unit is exposed to direct sea winds, install a
windbreaker.
▪ Height of windbreaker≥1.5×height of outdoor unit
▪ Mind the service space requirements when installing the
windbreaker.
a
b
c
d
c
d
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet
causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
a
b
c
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging:
Model
Cooling
Heating
AZQS
–5~46°C
–15~15.5°C
5.2.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
a
b
c
c
d
a
Snow cover or shed
b
Pedestal (minimum height = 150 mm)
c
Prevailing wind direction
d
Air outlet
5.3
Preparing refrigerant piping
5.3.1
Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
Refrigerant piping material
▪
Piping material:
Phosphoric acid deoxidised seamless copper.
▪
Piping temper grade and thickness:
Outer diameter
(Ø)
Temper grade
Thickness (t)
(a)
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
Annealed (O)
≥0.8 mm
t
Ø
15.9 mm (5/8")
Annealed (O)
≥1.0 mm
19.1 mm (3/4")
Half hard (1/2H)
(a)
Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
▪
Flare connections:
Only use annealed material.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
L1 liquid piping
Ø9.5 mm
L1 gas piping
Ø15.9 mm
Refrigerant piping length and height difference
The piping length and height difference must comply with the
following requirements:
Summary of Contents for AZQS140B8V1B