background image

1 General safety precautions

Installer reference guide

4

AZQS100~14 AZQS100~140B7Y1B

Split system air conditioners

4P385529-1B – 2016.10

1.2.3

Refrigerant

If applicable. See the installation manual or installer reference guide
of your application for more information.

NOTICE

Make  sure  refrigerant  piping  installation  complies  with
applicable  legislation.  In  Europe,  EN378  is  the  applicable
standard.

NOTICE

Make  sure  the  field  piping  and  connections  are  not
subjected to stress.

WARNING

During  tests,  NEVER  pressurize  the  product  with  a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).

WARNING

Take sufficient precautions in case of refrigerant leakage. If
refrigerant  gas  leaks,  ventilate  the  area  immediately.
Possible risks:

▪ Excessive  refrigerant  concentrations  in  a  closed  room

can lead to oxygen deficiency.

▪ Toxic  gas  may  be  produced  if  refrigerant  gas  comes

into contact with fire.

DANGER: RISK OF EXPLOSION

Pump  down  –  Refrigerant  leakage.

  If  you  want  to  pump

down the system, and there is a leakage in the refrigerant
circuit:

▪ Do NOT use the unit's automatic pump down function,

with  which  you  can  collect  all  refrigerant  from  the
system  into  the  outdoor  unit. 

Possible  consequence:

Self-combustion  and  explosion  of  the  compressor
because of air going into the operating compressor.

▪ Use  a  separate  recovery  system  so  that  the  unit's

compressor does NOT have to operate.

WARNING

Always  recover  the  refrigerant.  Do  NOT  release  them
directly  into  the  environment.  Use  a  vacuum  pump  to
evacuate the installation.

NOTICE

After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.

NOTICE

▪ To avoid compressor breakdown, do NOT charge more

than the specified amount of refrigerant.

▪ When  the  refrigerant  system  is  to  be  opened,

refrigerant  must  be  treated  according  to  the  applicable
legislation.

WARNING

Make  sure  there  is  no  oxygen  in  the  system.  Refrigerant
may only be charged after performing the leak test and the
vacuum drying.

▪ In case re-charge is required, refer to the nameplate of the unit. It

states the type of refrigerant and necessary amount.

▪ The unit is factory charged with refrigerant and depending on pipe

sizes  and  pipe  lengths  some  systems  require  additional  charging
of refrigerant.

▪ Only  use  tools  exclusively  for  the  refrigerant  type  used  in  the

system,  this  to  ensure  pressure  resistance  and  prevent  foreign
materials from entering into the system.

▪ Charge the liquid refrigerant as follows:

If

Then

A siphon tube is present

(i.e., the cylinder is marked with
"Liquid filling siphon attached")

Charge with the cylinder upright.

A siphon tube is NOT present

Charge with the cylinder upside
down.

▪ Open refrigerant cylinders slowly.

▪ Charge  the  refrigerant  in  liquid  form.  Adding  it  in  gas  form  may

prevent normal operation.

CAUTION

When  the  refrigerant  charging  procedure  is  done  or  when
pausing,  close  the  valve  of  the  refrigerant  tank
immediately.  If  the  valve  is  not  closed  immediately,
remaining  pressure  might  charge  additional  refrigerant.

Possible consequence: 

Incorrect refrigerant amount.

1.2.4

Brine

If applicable. See the installation manual or installer reference guide
of your application for more information.

WARNING

The selection of the brine MUST be in accordance with the
applicable legislation.

WARNING

Take  sufficient  precautions  in  case  of  brine  leakage.  If
brine  leaks,  ventilate  the  area  immediately  and  contact
your local dealer.

WARNING

The  ambient  temperature  inside  the  unit  can  get  much
higher than that of the room, e.g. 70°C. In case of a brine
leak,  hot  parts  inside  the  unit  can  create  a  hazardous
situation.

WARNING

The  use  and  installation  of  the  application  MUST  comply
with the safety and environmental precautions specified in
the applicable legislation.

1.2.5

Water

If applicable. See the installation manual or installer reference guide
of your application for more information.

NOTICE

Make  sure  water  quality  complies  with  EU  directive
98/83 EC.

Summary of Contents for AZQS140B8V1B

Page 1: ...Installer reference guide Split system air conditioners English Installer reference guide Split system air conditioners AZQS100B8V1B AZQS125B8V1B AZQS140B8V1B AZQS100B7Y1B AZQS125B7Y1B AZQS140B7Y1B...

Page 2: ...e outdoor unit 13 6 4 9 To determine if oil traps are required 14 6 5 Checking the refrigerant piping 14 6 5 1 About checking the refrigerant piping 14 6 5 2 Precautions when checking the refrigerant...

Page 3: ...BURNING Do NOT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you mu...

Page 4: ...n WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the un...

Page 5: ...istant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do not connect wiring of different thicknesses to the po...

Page 6: ...lation What to do and know to install the system Commissioning What to do and know to commission the system after it is installed Hand over to the user What to give and explain to the user Maintenance...

Page 7: ...Also read the following requirements General installation site requirements See the General safety precautions chapter Service space requirements See the Technical data chapter Refrigerant piping req...

Page 8: ...tallation only and for ambient temperatures ranging Model Cooling Heating AZQS 5 46 C 15 15 5 C 5 2 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor...

Page 9: ...nsion cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase adva...

Page 10: ...350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation...

Page 11: ...ng the refrigerant piping to the indoor unit Installing oil traps Insulating the refrigerant piping Keeping in mind the guidelines for Pipe bending Flaring pipe ends Brazing Using the stop valves 6 4...

Page 12: ...ration A Flare tool for R410A clutch type Conventional flare tool Clutch type Ridgid type Wing nut type Imperial type A 0 0 5 mm 1 0 1 5 mm 1 5 2 0 mm 5 Check that the flaring is properly made a b c a...

Page 13: ...m cap is sealed where indicated with the arrow Do NOT damage it After handling the stop valve tighten the stem cap and check for refrigerant leaks Item Tightening torque N m Stem cap liquid side 13 5...

Page 14: ...might cause liquid compression or deterioration of oil return Oil traps in the rising gas piping can prevent this If Then The indoor unit is installed higher than the outdoor unit Install an oil trap...

Page 15: ...old indicates 0 1 MPa 1 bar 2 Leave as is for 4 5 minutes and check the pressure If the pressure Then Does not change There is no moisture in the system This procedure is finished If the pressure Then...

Page 16: ...the service ports indicated on the figures below opened The location is depending on model type Location of service ports AZQS140_V1 a b c AZQS100 125_V1 a b c AZQS140_Y1 a b c AZQS100 125_Y1 a b c a...

Page 17: ...ional refrigerant amount charged d Total refrigerant charge e Greenhouse gas emissions of the total refrigerant charge expressed as tonnes CO2 equivalent f GWP Global warming potential NOTICE In Europ...

Page 18: ...d single core wire b Screw c Flat washer Stranded conductor wire with round crimp style terminal c b b a c a B B a Terminal b Screw c Flat washer Tightening torques Item Tightening torque N m M4 X1M 1...

Page 19: ...are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the e...

Page 20: ...ated this way the compressor will break NOTICE Cooling operation mode Perform the test run in cooling operation mode so that stop valves failing to open can be detected Even if the user interface was...

Page 21: ...wiring and switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA The outdoor and indoor unit are incompatible NOTICE The reversed phase protection detector o...

Page 22: ...her parts according to the applicable legislation INFORMATION For more details see the service manual 11 2 About pump down The unit is equipped with an automatic pump down function with which you can...

Page 23: ...B C D E HB HU HD B 100 A B C 100 100 100 B E 100 1000 500 A B C E 150 150 150 1000 500 D 500 D E 1000 500 500 500 500 B D 100 100 B D E HB HD HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB...

Page 24: ...required to install a roof but seal the gap between the upper and lower units to prevent discharged air from flowing back to the suction side through the bottom of the unit 12 2 Piping diagram Outdoo...

Page 25: ...ion F1U F8U AZQS100_V1 F1U F2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U AZQS125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U AZQS_Y1 F1U F2U Fus...

Page 26: ...company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure a...

Page 27: ......

Page 28: ...4P385529 1B 2016 10 Copyright 2014 Daikin...

Reviews: