![background image](http://html.mh-extra.com/html/daikin/altherma-ehy2komb28aa/altherma-ehy2komb28aa_installers-reference-manual_501275054.webp)
9 Installation
Installer reference guide
54
EJHA EHY32AA
Daikin Altherma Hybrid hydrosplit heat pump
4P531180-1 – 2018.06
Which fixation position to use
a
b
a
In case to fix on the pipe
b
In case to fix on the sleeve
Maximum distance between clamps
Vertical position of pipe
Other position of pipe
2000 mm
1000 mm
▪ Divide the length between the brackets evenly.
▪ Every system MUST contain at least 1 bracket.
▪ Position the first clamp at a maximum of 500 mm from the
gasboiler.
≤1000 mm
≤2000 mm
≤1000 mm
≤250 mm
≤250 mm
≤250 mm
≤250 mm
≥3° (50 mm/m)
≤1000 mm
≤1000 mm
≤500 mm
a
b
A
Second clamp after the second elbow
B
First clamp after the second elbow