9 Installation
Installer reference guide
51
EJHA EHY32AA
Daikin Altherma Hybrid hydrosplit heat pump
4P531180-1 – 2018.06
Number of
units
Concentric
Dual pipe
Gas
exhaust
Air intake
Gas
exhaust
Air intake
3
166
311
166
263
4
176
330
176
279
5
186
349
186
295
6
196
367
196
311
7
206
386
206
326
8
216
404
216
342
9
226
423
226
358
10
236
442
236
374
11
247
463
247
391
12
257
482
257
407
13
267
500
267
423
14
277
519
277
439
15
287
538
287
454
16
297
556
297
470
17
307
575
307
486
18
317
594
317
502
19
328
614
328
519
20
338
633
338
535
Special remark regarding
C
93
:
The minimum inner dimensions of
the chimney have to be 200×200 mm.
9.9.5
Applicable materials
Materials for the installation of the gas exhaust and/or air intake
MUST be bought according to the table below.
D BG BA
HR HU SK
SI
CZ
ES PT PL GR CY IE TR
MT LT
LT LV UK FR
B
Daikin
Daikin
Daikin
Daikin
Daikin
Daikin
(b) (a)
(a)
(a)
(b)
C
C
C
C
93
C
C
C
83
63
53
43
33
13
IT
CH AT
(b)
(a)
Gas exhaust/air intake parts can be bought from the 3
rd
party. All parts purchased from an external supplier MUST
comply with EN14471.
(b)
NOT allowed.
9.9.6
Flue pipe position
See the local and national regulations.
Especially for UK:
Only use flue products approved by the boiler manufacturer, which
can be bought from the supplier of your boiler.
"6.3 Combining units and options" on page 13
P
S
C
B
A
M
R
D
J
Q
G
A
Q
Q
N
P
T2
T2
T2
T1
H
T
I
K
L
F
F
N
E
Terminal position
Minimum
distance (mm)
A
Directly below an open able window or
other opening (e.g. air brick)
300
B
Below gutters, soil pipes or drain pipes
75
C
Below eaves
200
D
Below balconies or car front roofs
E
From vertical drain pipes and soil pipe
150
F
From internal or external corners
300
G
Above ground, roof or balcony level
H
From a surface facing a terminal
600
I
From a terminal discharging towards
another terminal
1200
J
From an opening in a car port (e.g.
door, window) into a dwelling
K
Vertically from a terminal on the same
wall
1500
L
Horizontally from a terminal on the
same wall
300
M
Above an opening, air brick, opening
windows, etc.
N
Horizontally to an opening, air brick,
opening windows, etc.
P
Above roof level (to base terminal)
Q
From an adjacent wall to flue
R
From an adjacent opening window
1000