Refrigerant piping work

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Execute  heat  insulation  work  completely  on  both  sides  of  the  gas
piping and the liquid piping. Otherwise, this can sometimes result in
water leakage.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for the used refrigerant.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

Use copper alloy seamless pipes (ISO 1337).

The outdoor unit is charged with refrigerant.

To  prevent  water  leakage,  execute  heat  insulation  work
completely  on  both  sides  of  the  gas  and  liquid  piping.  When
using a heat pump, the temperature of the gas piping can reach
up  to  approximately  120°C,  use  insulation  which  is  sufficiently
heat resistant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.

Use annealed material only for flare connections.

Refer to 

Table 1

 for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
Table 1 

When connecting the flare nut, coat the flare inner surface with
ether  oil  or  ester  oil  and  initially  tighten  3  or  4  turns  by  hand
before tightening firmly.

If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a fire.

Make sure there is no refrigerant gas leak. A toxic gas may be
released  by  the  refrigerant  gas  leaking  indoor  and  being
exposed to flames from an area heater, cooking stove, etc.

Finally, insulate as shown in the figures below.

Piping insulation procedure

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing  without  carrying  out  nitrogen  replacement  or  releasing
nitrogen  into  the  piping  will  create  large  quantities  of  oxidized
film  on  the  inside  of  the  pipes,  adversely  affecting  valves  and
compressors in the refrigerating system and preventing normal
operation.

When  brazing  while  inserting  nitrogen  into  the  piping,  nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

- Be sure to insulate the duct to prevent condensation 

from forming. (Material: glass wool or polyethylene 
foam, 25 mm thick)

- Use electric insulation between the duct and the wall 

when using metal ducts to pass metal laths of the net or 
fence shape or metal plating into wooden buildings.

- Be sure to explain about the way of maintaining and 

cleaning local procurements (air filter, grille (both air 
outlet and suction grille), etc.) to your customer.

Installation  shall  be  done  by  a  licensed  refrigeration
technician,  the  choice  of  materials  and  installation  shall
comply  with  the  applicable  national  and  international
codes.  In  Europe,  EN378  is  the  applicable  standard  that
shall be used.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe 

gauge

Tightening torque 

(N•m)

Flare dimension 

A (mm)

Flare shape

Ø6.4

15~17

8.7~9.1

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

Ø15.9

63~75

19.3~19.7

1

2

4

3

R0.4~0.8

45

° ±

2

90

°±

2

A

Gas piping

Liquid piping

1

Piping insulation material (field supply)

2

Flare nut connection

3

Insulation for fitting (delivered with the unit)

4

Piping insulation material (main unit)

5

Main unit

6

Clamp (field supply)

7

Medium 1 sealing pad for gas piping (delivered with the unit)
Medium 2 sealing pad for liquid piping (delivered with the unit)

A

Turn seams up

B

Attach to base

C

Tighten the part other than the piping insulation material

D

Wrap over from the base of the unit to the top of the flare nut 
connection

For local insulation, be sure to insulate local piping all
the way into the pipe connections inside the unit.
Exposed  piping  may  cause  condensation  or  may
cause burns when touched.

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

A

B

D

C

7

1

2

3

4

5

6

6

A

B

C

1

2

3

4

5

6

6

D

7

1

2

3

4

5

6

6

4PEN461568-1.book  Page 4  Thursday, October 20, 2016  11:50 AM

Summary of Contents for ADEQ-C

Page 1: ...INSTALLATION MANUAL ADEQ35C2VEB ADEQ50C2VEB ADEQ60C2VEB ADEQ71C2VEB ADEQ100C2VEB ADEQ125C2VEB Split System air conditioners 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 2: ... 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4 4 A A 125 5 4 7 6 3 300 1 2 3 4 5 6a 6b 6c 7a 7b 7c 8 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 3: ...il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information en...

Page 4: ... 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may damage electrical wires and consequently cause fire Sound pressure level is less than 70dB A Accessories Check if the following accessories are inc...

Page 5: ...h relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling before installing the unit Preparations before installation 1 Relation of ceiling opening to unit and suspension bolt position See figure 5 For installation choose one of the possibilities a...

Page 6: ... side flange field supply Connect the flange to the main unit with accessory screws 7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping Air outlet side Connect the duct according to the air inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape or something similar to prevent ai...

Page 7: ...to the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so that it can be felt on the skin Be sure to insulate the duct to prevent conde...

Page 8: ... check drainage in the manner described below Gradually pour approximately 1L of water from the outlet hole into the drain pan to check drainage Check the drainage When electric wiring work is finished Check drainage flow during COOL running explained in Test operation on page 8 When electric wiring work is not finished Remove the switch box cover and connect the single phase power supply and the ...

Page 9: ...e units When none are available follow the instructions below Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the figure Use the specified electric wire Connect the wire securely to the terminal Lock the wire down without applying excessive force to the term...

Page 10: ...he airflow automatic adjustment function Airflow automatic adjustment is the volume of blow off air that has been automatically adjusted to the rated quantity 1 Make sure the test run is done with a dry coil If the coil is not dry run the unit for 2 hours with fan only to dry the coil 2 Check if the power supply wiring to the air conditioning unit is completed along with the duct installation If a...

Page 11: ...eration accordingly to protect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater for 6 hours 4 Set to cooling operation with the remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate nor...

Page 12: ...CN E HA HE HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECTOR FRAMEGROUND S L FLOATSWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOTLAMP LIGHTEMITTINGDIODE S NPL PRESSURESEN...

Page 13: ...4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 14: ...4PEN461568 1 book Page 2 Thursday October 20 2016 11 50 AM ...

Page 15: ...3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 L N 3 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 6 L N L N 1 1 1 1 1 1 L N 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 16 1 4 2 3 5 7 8 11 12 6 9 6 L N 1 2 3 P1 P2 F1 F2 T1 T2 Sec A A 15 14 A A A A 10 13 6 6 9 10 11 12 13 14 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 16: ...4P461568 1 2016 09 Copyright 2016 Daikin 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Reviews: