8

5

When the air conditioning unit has stopped, check on an indoor
unit if the second code No. of mode No. 21 is set to "02".
If the air conditioning unit does not stop operating or the second
code No. is not "02", repeat step 4.
If  the  outdoor  unit  is  not  turned  on,  the  display  on  the  remote
controller  will  show  "

U4

"  or  "

UH

"  (refer  to 

"Test  operation"  on

page 8

).  However,  you  can  continue  setting  this  function

because these messages are only applicable to outdoor units.
After  setting  this  function,  be  sure  to  turn  on  the  outdoor  unit
before performing the test operation on the outdoor unit.
If  any  other  error  display  occurs  on  the  display  of  the  remote
controller, refer to 

"Test operation" on page 8

 and the operation

manual of the outdoor unit. Check the defective point.

Using the remote controller

Check on an indoor unit if the second code of mode No. 21 is set to
"01"  (=  factory  setting).  Change  the  second  code  according  to  the
external  static  pressure  of  the  duct  to  be  connected  as  shown  in
table 2.

Table 2

Setting air filter sign

Remote controllers are equipped with liquid crystal air filter signs
to display the time to clean the air filter.

Change the Second code No. depending on the amount of dirt
or dust in the room. (Second code No. is factory set to "01" for
air filter contamination-light.)

Air filter contamination

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".

Test operation

Refer  to  the  section  of 

"For  the  following  items,  take  special  care

during construction and check after installation is finished" on page 2

.

After finishing the construction of refrigerant piping, drain piping,
and electric wiring, conduct test operation accordingly to protect
the unit.

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify crank case heater for 6 hours.

4

Set  to  cooling  operation  with  the  remote  controller  and  start
operation by pushing ON/OFF button.

5

Press  Inspection/Test  Operation  button  4  times  and  operate  at
Test Operation mode for 3 minutes.

6

Press Inspection/Test Operation button and operate normally.

7

Confirm function of unit according to the operation manual.

If  there  is  no  change  after  airflow  adjustment  in  the
ventilation  paths,  be  sure  to  perform  setting  the
automatic airflow adjustment again.

Contact  your  dealer  if  there  is  no  change  after
performing airflow adjustment in the ventilation paths,
after performing the test operation of the outdoor unit
or when the air conditioning unit is moved to another
location.

If booster fans, an outdoor air processing unit or HRV
via  duct  are  used,  do  not  use  automatic  airflow
adjustment control with a remote controller.

If  the  ventilation  paths  have  been  changed,  perform
the setting of  the airflow  automatic  adjustment  again
as described above from step 3 onwards.

NOTE

The second code No. is set to "01" by default.

Mode 

No.

First 

code No.

Second 

code No.

External static pressure (Pa)

ADEQ

35

50

60

71

100

125

13 (23)

6

01

30

30

30

30

40

50

02

03

30

30

30

30

04

40

40

40

40

40

05

50

50

50

50

50

50

06

60

60

60

60

60

60

07

70

70

70

70

70

70

08

80

80

80

80

80

80

09

90

90

90

90

90

90

10

100

100

100

100

100

100

11

110

110

110

110

110

110

12

120

120

120

120

120

120

13

130

130

130

130

130

130

14

140

140

140

140

140

140

15

150

150

150

150

150

150

Setting

Display interval

Mode No.

First 

code No.

Second 

code No.

Light

±2500 hrs

10 (20)

0

01

Heavy

±1250 hrs

10 (20)

0

02

No display

10 (20)

3

02

NOTE

If the main power supply is turned off during operation,
operation  will  restart  automatically  after  the  power
turns back on again.

4PEN461568-1.book  Page 8  Thursday, October 20, 2016  11:50 AM

Summary of Contents for ADEQ-C

Page 1: ...INSTALLATION MANUAL ADEQ35C2VEB ADEQ50C2VEB ADEQ60C2VEB ADEQ71C2VEB ADEQ100C2VEB ADEQ125C2VEB Split System air conditioners 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 2: ... 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4 4 A A 125 5 4 7 6 3 300 1 2 3 4 5 6a 6b 6c 7a 7b 7c 8 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 3: ...il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information en...

Page 4: ... 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may damage electrical wires and consequently cause fire Sound pressure level is less than 70dB A Accessories Check if the following accessories are inc...

Page 5: ...h relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling before installing the unit Preparations before installation 1 Relation of ceiling opening to unit and suspension bolt position See figure 5 For installation choose one of the possibilities a...

Page 6: ... side flange field supply Connect the flange to the main unit with accessory screws 7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping Air outlet side Connect the duct according to the air inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape or something similar to prevent ai...

Page 7: ...to the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so that it can be felt on the skin Be sure to insulate the duct to prevent conde...

Page 8: ... check drainage in the manner described below Gradually pour approximately 1L of water from the outlet hole into the drain pan to check drainage Check the drainage When electric wiring work is finished Check drainage flow during COOL running explained in Test operation on page 8 When electric wiring work is not finished Remove the switch box cover and connect the single phase power supply and the ...

Page 9: ...e units When none are available follow the instructions below Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the figure Use the specified electric wire Connect the wire securely to the terminal Lock the wire down without applying excessive force to the term...

Page 10: ...he airflow automatic adjustment function Airflow automatic adjustment is the volume of blow off air that has been automatically adjusted to the rated quantity 1 Make sure the test run is done with a dry coil If the coil is not dry run the unit for 2 hours with fan only to dry the coil 2 Check if the power supply wiring to the air conditioning unit is completed along with the duct installation If a...

Page 11: ...eration accordingly to protect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater for 6 hours 4 Set to cooling operation with the remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate nor...

Page 12: ...CN E HA HE HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECTOR FRAMEGROUND S L FLOATSWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOTLAMP LIGHTEMITTINGDIODE S NPL PRESSURESEN...

Page 13: ...4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 14: ...4PEN461568 1 book Page 2 Thursday October 20 2016 11 50 AM ...

Page 15: ...3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 L N 3 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 6 L N L N 1 1 1 1 1 1 L N 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 16 1 4 2 3 5 7 8 11 12 6 9 6 L N 1 2 3 P1 P2 F1 F2 T1 T2 Sec A A 15 14 A A A A 10 13 6 6 9 10 11 12 13 14 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Page 16: ...4P461568 1 2016 09 Copyright 2016 Daikin 4PEN461568 1 book Page 1 Thursday October 20 2016 11 50 AM ...

Reviews: