Code Description
Range
Resolution
Default
S
1607 PARAM . SAVE
0, 1
1
0
Saves all altered parameters to permanent memory .
• Parameters altered through a fieldbus are not automatically saved to permanent memory. To save, you must use this parameter.
• If 1602 PARAMETER LOCK = 2 (NOT SAVED), parameters altered from the control panel are not saved . To save, you must use this parameter .
• If 1602 PARAMETER LOCK = 1 (OPEN), parameters altered from the control panel are stored immediately to permanent memory .
0 = DONE – Value changes automatically when all parameters are saved .
1 = SAVE – Saves altered parameters to permanent memory .
1608 START ENABLE
1
-6…7
1
4
Selects the source of the start enable 1 signal .
Note: Start enable functionality differs from the run enable functionality .
0 = NOT SEL – Allows the drive to start without an external start enable signal .
1 = DI1 – Defines digital input DI1 as the start enable 1 signal.
• This digital input must be activated for start enable 1 signal .
• If the voltage drops and de-activates this digital input, the drive will coast to stop and show alarm
2021 on panel display . The drive will not start until start
enable 1 signal resumes .
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the start enable 1 signal.
• See DI1 above .
7 = COMM – Assigns the fieldbus Command Word as the source for the start enable 1 signal.
• Bit 2 of the Command word 2 (parameter 0302) activates the start disable 1 signal .
• See fieldbus user’s manual for detailed instructions.
(-1) = DI1(INV) – Defines an inverted digital input DI1 as the start enable 1 signal.
(-2)…(-6) = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the start enable 1 signal.
• See DI1(INV) above .
1611 PARAMETER VIEW
1 . . .3
1
2
Selects the parameter view, i .e . which parameters are shown .
Note:
This parameter is visible only when it is activated by the optional FlashDrop device . FlashDrop allows fast customization of the parameter list, e .g .
selected parameters can be hidden . For more information, see MFDT-01 FlashDrop User’s Manual [3AFE68591074 (English)] . FlashDrop parameter values
are activated by setting parameter 9902 to 31 (LOAD FD SET) .
1 = FLASHDROP – FlashDrop parameter list is shown . Does not include short parameter list . Parameters that are hidden by the FlashDrop device are
not visible .
2 = SHORT VIEW – Shows only a subset of all signals and parameters
3 = LONG VIEW – Shows all signals and parameters
a
CTual
s
Ignals
and
p
arameTers
www .DaikinApplied .com 47
OM 1190-1 • MD4 VFD