Miscellaneous Drive Control
NOTE:
The user should change only the parameters for the
functions you wish to control vial fieldbus. All other
parameters should typically remain at factory default .
For simple start/stop and speed reference fieldbus
control, only parameters 1001 and 1103 need to be
changed to comm .
Using the fieldbus for miscellaneous drive control requires:
•
Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 52: Miscellaneous Drive Control Protocol Reference
Drive Parameter
Value
Setting
Protocol Reference
Modbus
1
N2
FLN
BACnet
abb drv
dcu profile
1601
RUN ENABLE
7 (COMM)
Run enable by fieldbus. (Not
recommended1)
40001 bit 3
40031 bit 6
(inverted)
BO4
35
BV12
1604
FAULT RESET SEL
8 (COMM)
Fault reset by fieldbus.
40001 bit 7
40031 bit 4
BO6
94
BV14
1606
LOCAL LOCK
8 (COMM)
Source for local lock selection is
the fieldbus.
Does not apply
40031 bit 14
1607
PARAM SAVE
1 (SAVE)
Saves altered parameters to
memory (then value returns to 0) .
41607
40032 bit 2
BO18
N/A
1
1608
START ENABLE 1
7 (COMM)
Source for start enable 1 is the
fieldbus Command word. (Not
recommended)
1
Does not apply .
40032 bit 2
BV20
1609
START ENABLE 2
7 (COMM)
Source for start enable 2 is the
fieldbus Command word. (Not
recommended)
1
40032 bit 3
BV21
2013
MIN TORQUE SEL
7 (COMM)
Source for minimum torque
selection is the fieldbus.
40031 bit 15
2014
MAX TORQUE SEL
7 (COMM)
Source for maximum torque
selection is the fieldbus.
2201
ACC/DEC 1/2 SEL
7 (COMM)
Source for ramp pair selection is
the fieldbus.
40031 bit 10
•
1
Daikin recommends hard wiring run permissive and safeties .