Code Description
Range
Resolution
Default
S
1104 REF1 MIN
0 .0 . . .500 .0
Hz
0 . . .30000
rpm
0 .1 Hz
1 rpm
0 .0 Hz
0 rpm
Sets the minimum for external reference 1 .
• The minimum analog input signal (as a percent of the full signal in volts or amps) corresponds to REF1 MIN in Hz/rpm .
• Parameter 1301 MINIMUM AI1 or 1304 MINIMUM AI2 sets the minimum analog input signal .
• These parameters (reference and analog min . and max . settings) provide scale and offset adjustment for the reference .
1105 REF1 MAX
0 .0 . . .500 .0
Hz
0 . . .30000
rpm
0 .1 Hz
1 rpm
60 .0 Hz
(US)
1800 rpm
(US)
Sets the maximum for external reference 1 .
• The maximum analog input signal (as a percent of full the signal in volts or amps) corresponds to REF1 MAX in Hz/rpm .
• Parameter 1302 MAXIMUM AI1 or 1305 MAXIMUM AI2 sets the maximum analog input signal .
1106 REF2 SELECT
0 . . .19
1
2
Selects the signal source for external reference REF2 .
0…17 – Same as for parameter 1103 REF1 SELECT .
19 = PID1OUT – The reference is taken from the PID1 output . See Groups 40 and 41 .