Group 11: Reference Select
This group defines:
• How the drive selects between command sources .
• Characteristics and sources for REF1 and REF2 .
Table 27: Group 11: Reference Select
Code Description
Range
Resolution
Default
S
1101 KEYPAD REF SEL
1,2
1
1
Selects the reference controlled in local control mode .
1 = REF1 (Hz/rpm) – Reference type depends on parameter 9904 MOTOR CTRL MODE .
• Speed reference (rpm) if 9904 = 1 (VECTOR: SPEED) .
• Frequency reference (Hz) if 9904 = 3 (SCALAR; FREQ) .
2 = REF2 (%)
1102 EXT1/EXT2 SEL
- 6 . . .12
1
0
Defines the source for selecting between the two external control locations EXT1 or EXT2. Thus, defines the source for Start/Stop/Direction commands and
reference signals .
0 = EXT1 – Selects external control location 1 (EXT1) .
• See parameter 1001 EXT1 COMMANDS for EXT1’s Start/Stop/Dir definitions.
• See parameter 1103 REF1 SELECT for EXT1’s reference definitions.
1 = DI1 – Assigns control to EXT1 or EXT2 based on the state of DI1
(DI1 activated = EXT2; DI1 de-activated = EXT1) .
2…6 = DI2…DI6 – Assigns control to EXT1 or EXT2 based on the state of the selected digital input . See DI1 above .
7 = EXT2 – Selects external control location 2 (EXT2) .
• See parameter 1002 EXT2 COMMANDS for EXT2’s Start/Stop/Dir definitions.
• See parameter 1106 REF2 SELECT for EXT2’s reference definitions.
8 = COMM – Assigns control of the drive via external control location EXT1 or EXT2 based on the fieldbus control word.
• Bit 5 of the Command Word 1 (parameter 0301) defines the active external control location (EXT1 or EXT2).
• See Fieldbus user’s manual for detailed instructions .
9 = TIMER 1 – Assigns control to EXT1 or EXT2 based on the state of the Timer
(Timer activated = EXT2; Timer de-activated = EXT1) . See Group 36, Timer Functions .
10…12 = TIMER 2… 4 – Assigns control to EXT1 or EXT2 based on the state of the Timer . See Timer 1 above .
-1 = DI1(INV) – Assigns control to EXT1 or EXT2 based on the state of DI1
(DI1 activated = EXT1; DI1 de-activated = EXT2) .
-2…-6 = DI2(INV)…DI6(INV) – Assigns control to EXT1 or EXT2 based on the state of the selected digital input . See DI1(INV) above .
a
CTual
s
Ignals
and
p
arameTers
www .DaikinApplied .com 39
OM 1190-1 • MD4 VFD
Summary of Contents for ACS320