Code
Description (continuation of Table 49)
EFB Protocol Reference
Modbus
N2
FLN
BACnet
5310 EFB PAR10
.
Not used for Comm
setup
Sets them response turnaround time in milliseconds . When this protocol is
selected, the default value is:
3 msec .
0 msec .
5 msec .
5311
EFB PAR11
Not used for Comm setup .
This parameter, together with
parameter 5317, EFB PAR 17,
sets BACnet Device Object
Instance IDs:
• For the range 1 to 65,535:
This parameter sets the ID
directly (5317 must be 0) . For
example, the following values
set the ID to 49134: 5311 =
49134 and 5317 = 0 .
• For IDs > 65,335: The ID
equals 5311’s value plus
10,000 times 5317’s value .
For example, the following
values set the ID to 71234:
5311 = 1234 and 5317 = 7 .
5312 EFB PAR12
Not used for Comm setup .
This parameter sets the BACnet
Device Object Max Info Frames
Property .
5313 EFB PAR13
Not used for Comm setup .
This parameter sets the BACnet
Device Object Max Master
Property .
5314 EFB PAR14
Not used for Comm setup .
5315 EFB PAR15
Not used for Comm setup .
5316 EFB PAR 16
Not used for Comm setup .
This parameter indicates the
count of MS/TP tokens passed
to this drive .
5317 EFB PAR17
This parameter works with
parameter 5311 to set BACnet
Device Object Instance IDs .
See parameter 5311 .
NOTE:
After any changes to the communication settings, protocol must be reactivated by either cycling the drive power, or by
clearing and then restoring the station Id (5302) or use Reinitialize Device Service .
OM 1190-1 • MD4 VFD 74 www .DaikinApplied .com
f
Ieldbus
C
onTrols