Group 16: System Controls
This group defines a variety of system level locks, resets and enables.
Table 31: Group 16: System Controls
Code Description
Range
Resolution
Default
S
1601 RUN ENABLE
-6…7
1
0
Selects the source of the run enable signal .
0 = NOT SEL – Allows the drive to start without an external run enable signal .
1 = DI1 – Defines digital input DI1 as the run enable signal.
• This digital input must be activated for run enable .
• If the voltage drops and de-activates this digital input, the drive will coast to stop and not start until the run enable signal resumes .
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the run enable signal.
• See DI1 above .
7 = COMM – Assigns the fieldbus Command Word as the source for the run enable signal.
• Bit 6 of the Command Word 1 (parameter 0301) activates the run disable signal .
• See fieldbus user’s manual for detailed instructions.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the run enable signal.
• This digital input must be de-activated for run enable .
• If this digital input activates, the drive will coast to stop and not start until the run enable signal resumes .
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the run enable signal.
• See DI1(INV) above .
1602 PARAMETER LOCK
0…2
1
1
Determines if the control panel can change parameter values .
• This lock does not limit parameter changes made by macros .
• This lock does not limit parameter changes written by fieldbus inputs.
• This parameter value can be changed only if the correct pass code is entered . See parameter 1603, PASS CODE .
0 = LOCKED – You cannot use the control panel to change parameter values .
• The lock can be opened by entering the valid pass code to parameter 1603 .
1 = OPEN – You can use the control panel to change parameter values .
2 = NOT SAVED – You can use the control panel to change parameter values, but they are not stored in permanent memory .
• Set parameter 1607 PARAM SAVE to 1 (SAVE) to store changed parameter values to memory .
1603 PASS CODE
0…65535
1
0
Entering the correct pass code allows you to change the parameter lock .
• See parameter 1602 above .
• The code 358 allows you to change the value of the parameter 1602 once .
• This entry reverts back to 0 automatically .
1604 FAULT RESET SEL
-6…8
1
0
Selects the source for the fault reset signal . The signal resets the drive after a fault trip if the cause of the fault no longer exists .
0 = KEYPAD – Defines the control panel as the only fault reset source.
• Fault reset is always possible with control panel .
1 = DI1 – Defines digital input DI1 as a fault reset source.
• Activating the digital input resets the drive .
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as a fault reset source.
• See DI1 above .
7 = START/STOP – Defines the Stop command as a fault reset source.
• Do not use this option when fielbus communication provides the start, stop and direction commands.
8 = COMM – Defines the fieldbus as a fault reset source.
• The Command Word is supplied through fieldbus communication.
• The bit 4 of the Command Word 1 (parameter 0301) resets the drive .
-1 = DI1(INV) – Defines an inverted digital input DI1 as a fault reset source.
• De-activating the digital input resets the drive .
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as a fault reset source.
• See DI1(INV) above .
OM 1190-1 • MD4 VFD 46 www .DaikinApplied .com