5 Piping installation

Installation manual

9

4MWXM-A9
R32 Split series
3P600450-7T – 2022.09

5.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

≥13 mm

12.7 mm (1/2")

14~16 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

Use  separate  thermal  insulation  pipes  for  the  gas  and  liquid
refrigerant piping.

5.1.3

Refrigerant piping length and height
difference

The shorter the refrigerant piping, the better the performance of the
system.

The  piping  length  and  height  differences  must  comply  with  the
following requirements.

Shortest allowable length per room is 3 m.

Refrigerant piping length to each
indoor unit

Refrigerant piping total
length

≤25 m

≤50 m

Height difference
outdoor-indoor

Height difference
indoor-indoor

Outdoor unit installed
higher than indoor
unit

≤15 m

≤7.5 m

Outdoor unit installed
lower than at least 1
indoor unit

≤7.5 m

≤15 m

5.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

CAUTION

▪ No  brazing  or  welding  on  site  for  units  with  R32

refrigerant charge during shipment.

▪ During installation of the refrigeration system, joining of

parts with at least one part charged shall be performed
taking  into  account  the  following  requirements:  inside
occupied  spaces  non-permanent  joints  are  NOT
allowed  for  R32  refrigerant  except  for  site  made  joints
directly connecting the indoor unit to piping. Site made
joints directly connecting piping to indoor units shall be
of non-permanent type.

CAUTION

Do  NOT  connect  the  embedded  branch  piping  and  the
outdoor  unit  when  only  carrying  out  piping  work  without
connecting  the  indoor  unit  in  order  to  add  another  indoor
unit later.

5.2.1

Connections between outdoor and indoor
unit using reducers

Total indoor air conditioning units capacity class that can be
connected to this outdoor unit

≤9.0 kW

Port

Dimensions

Class

Reducer

A

Liquid Ø6.4 mm

Gas Ø9.5 mm

15, 20, 25, 35, (42)

(a)

B+C

Liquid Ø6.4 mm

Gas Ø12.7 mm

15, 20, 25, 35, (42)

(a)

1+2
(accessory)

42, 50, 60

71

(b)

ASYCPIR

To tank Liquid Ø6.4 mm

Gas Ø9.5 mm

90, 120

(a)

Only in case of connection with FTXM42R.

(b)

Only for connection with FBA71A9. Use option ASYCPIR for
liquid (Ø9.5 mm→Ø6.4 mm) and gas (Ø15.9 mm→Ø12.7 mm)
piping.

1

2

Ø12.7 mm → Ø9.5 mm

Connection examples:

▪ Connecting  a  Ø9.5  mm  inter  unit  pipe  to  a  Ø12.7  mm  gas  pipe

connection port on the outdoor unit

Ø9.5 mm

Ø12.7 mm

a

b

c

a

Reducer 1

b

Reducer 2

c

Flare nut (on the outdoor unit)

Coat the threaded connection port of the outdoor unit where the flare
nut comes in with refrigeration oil.

Flare nut for (mm)

Tightening torque (N•m)

Ø6.4

15~17

Ø9.5

33~39

Ø12.7

50~60

NOTICE

Use  an  appropriate  wrench  to  avoid  damaging  the
connection  thread  by  overtightening  the  flare  nut.  Be
careful NOT to overtighten the nut, or the smaller pipe may
be damaged (about 2/3-1× the normal torque).

5.2.2

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

Summary of Contents for 4MWXM52A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 4MWXM52A2V1B9...

Page 2: ...a f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt...

Page 3: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 4: ...Commissioning 15 11 1 Checklist before commissioning 15 11 2 Checklist during commissioning 15 11 3 Trial operation and testing 15 11 3 1 About wiring error check 15 11 3 2 To perform a test run 16 1...

Page 5: ...he refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause abno...

Page 6: ...n devices of the unit Do NOT touch live parts for 10 minutes after the power supply is turned off because of high voltage risk Please note that some sections of the electric component box are hot Make...

Page 7: ...ambient temperatures within the following ranges unless otherwise specified in the operation manual of the connected indoor unit DX operation range Cooling mode Heating mode 10 46 C DB 15 24 C DB DHW...

Page 8: ...ring refrigerant piping 5 1 1 Refrigerant piping requirements CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly conne...

Page 9: ...ed taking into account the following requirements inside occupied spaces non permanent joints are NOT allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to pip...

Page 10: ...est solution to all connections 3 Discharge all nitrogen gas 5 3 2 To perform vacuum drying DANGER RISK OF EXPLOSION Do NOT open the stop valves before the vacuum drying is finished NOTICE Connect the...

Page 11: ...vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before charging refrigerant make sure the refrigerant piping is connected a...

Page 12: ...ctor d MR30_A MR30_B suspend lead wire connectors e S40 thermal overload relay lead wire and high pressure switch connector f Multimeter DC voltage range g S90 S92 S93 thermistor lead wire connector h...

Page 13: ...ox cover before turning ON the power supply 1 Insulate and fix the refrigerant piping and cables as follows g b a f e c d a Gas pipe b Gas pipe insulation c Interconnection cable d Field wiring if app...

Page 14: ...iority in the following cases Operation mode priority If the priority room function is set on an indoor unit all other indoor units enter the standby mode Priority during high power operation If the i...

Page 15: ...nsate water might drip The indoor unit receives the signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection...

Page 16: ...unit for about 20 minutes The difference should be more than 8 C cooling or 20 C heating 3 First check operation of each unit individually then check simultaneous operation of all indoor units Check b...

Page 17: ...ssor motor M F Fan motor M P Drain pump motor Symbol Meaning M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Print...

Page 18: ...ler v Room A B C and Domestic hot water tank W c Heat exchanger thermistor m Discharge pipe thermistor w Field piping liquid d Refnet header n Compressor x Field piping gas e Fan motor o Accumulator y...

Page 19: ......

Page 20: ...3P600450 7T 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: