10 Configuration

Installation manual

14

4MWXM-A9

R32 Split series

3P600450-7T – 2022.09

10.1

About standby electricity saving
function

INFORMATION

This  function  is  available  only  for  the  indoor  units  listed
below.

The standby electricity saving function:

▪ turns OFF the power supply to the outdoor unit and,

▪ turns ON the standby electricity saving mode on the indoor unit.

The standby electricity saving function works with following units:

FTXM, FTXJ, FVXM, FTXA, CTXA, CTXM, CVXM, EKHWET

If  another  indoor  unit  is  used,  the  connector  for  standby  electric
saving MUST be plugged in.

The  standby  electricity  saving  function  is  turned  OFF  before
shipping.

10.1.1

To turn ON standby electricity saving
function

Prerequisite: 

The main power supply MUST be turned OFF.

1

Remove the service cover.

2

Disconnect the selective standby electricity saving connector.

3

Turn ON the main power supply.

10.2

About priority room function

INFORMATION

▪ The priority room function requires initial settings to be

made  during  the  installation  of  the  unit.  Ask  the
customer  in  which  rooms  he  plans  to  use  this  function
and make the necessary settings during installation.

▪ The  priority  room  setting  is  only  applicable  for  an  air

conditioner indoor unit and only one room can be set.

The  indoor  unit  for  which  the  priority  room  setting  is  applied  takes
priority in the following cases:

Operation mode priority:

 If the priority room function is set on an

indoor unit, all other indoor units enter the standby mode.

Priority during high-power operation:

 If the indoor unit on which

the priority room function is set operates at high power, the other
indoor units will run with reduced capabilities.

Quiet  operation  priority:

  If  the  indoor  unit  on  which  the  priority

room  function  is  set  to  quiet  operation,  the  outdoor  unit  will  also
run quietly.

Ask  the  customer  in  which  rooms  he  plans  to  use  this  function  and
make  the  necessary  settings  during  installation.  Setting  it  in  the
guest rooms is convenient.

10.2.1

To set the priority room function

1

Remove the switch cover on the service PCB.

2

Set  the  switch  (SW4)  for  the  indoor  unit  for  which  you  want  to
activate the priority room function to ON.

E

D

C

B

A

E

D

C

B

A

A

1

2
3
4
5

SW4

OFF

ON

2

1

3

Reset the power.

10.3

About night quiet mode

The  night  quiet  mode  function  makes  the  outdoor  unit  run  more
quietly at nighttime. This will reduce the cooling capacity of the unit.
Explain  Night  quiet  mode  to  the  customer  and  confirm  if  customer
wants to use this mode.

10.3.1

To turn ON the night quiet mode

1

Remove the switch cover on the service PCB.

1

2

1

A

1

2
3
4
5

SW6

2

OFF

ON

2
1

2

Set the night quiet mode switch (SW6-1) to ON.

10.4

About heat mode lock

Heat mode lock limits the unit to heat operation.

10.4.1

To turn ON heat mode lock

1

Remove the switch cover on the service PCB.

2

Set the heat mode lock switch (SW5-1) to ON.

Summary of Contents for 4MWXM52A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 4MWXM52A2V1B9...

Page 2: ...a f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt...

Page 3: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 4: ...Commissioning 15 11 1 Checklist before commissioning 15 11 2 Checklist during commissioning 15 11 3 Trial operation and testing 15 11 3 1 About wiring error check 15 11 3 2 To perform a test run 16 1...

Page 5: ...he refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause abno...

Page 6: ...n devices of the unit Do NOT touch live parts for 10 minutes after the power supply is turned off because of high voltage risk Please note that some sections of the electric component box are hot Make...

Page 7: ...ambient temperatures within the following ranges unless otherwise specified in the operation manual of the connected indoor unit DX operation range Cooling mode Heating mode 10 46 C DB 15 24 C DB DHW...

Page 8: ...ring refrigerant piping 5 1 1 Refrigerant piping requirements CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly conne...

Page 9: ...ed taking into account the following requirements inside occupied spaces non permanent joints are NOT allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to pip...

Page 10: ...est solution to all connections 3 Discharge all nitrogen gas 5 3 2 To perform vacuum drying DANGER RISK OF EXPLOSION Do NOT open the stop valves before the vacuum drying is finished NOTICE Connect the...

Page 11: ...vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before charging refrigerant make sure the refrigerant piping is connected a...

Page 12: ...ctor d MR30_A MR30_B suspend lead wire connectors e S40 thermal overload relay lead wire and high pressure switch connector f Multimeter DC voltage range g S90 S92 S93 thermistor lead wire connector h...

Page 13: ...ox cover before turning ON the power supply 1 Insulate and fix the refrigerant piping and cables as follows g b a f e c d a Gas pipe b Gas pipe insulation c Interconnection cable d Field wiring if app...

Page 14: ...iority in the following cases Operation mode priority If the priority room function is set on an indoor unit all other indoor units enter the standby mode Priority during high power operation If the i...

Page 15: ...nsate water might drip The indoor unit receives the signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection...

Page 16: ...unit for about 20 minutes The difference should be more than 8 C cooling or 20 C heating 3 First check operation of each unit individually then check simultaneous operation of all indoor units Check b...

Page 17: ...ssor motor M F Fan motor M P Drain pump motor Symbol Meaning M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Print...

Page 18: ...ler v Room A B C and Domestic hot water tank W c Heat exchanger thermistor m Discharge pipe thermistor w Field piping liquid d Refnet header n Compressor x Field piping gas e Fan motor o Accumulator y...

Page 19: ......

Page 20: ...3P600450 7T 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: