7 Electrical installation

Installation manual

12

4MWXM-A9

R32 Split series

3P600450-7T – 2022.09

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

MR30_A

S80

S70

D

C-

FU2

AL1

DP2

DP1

AL2

S60

S

S50

MR30_B

S20

S21

S22

S23

S93

S92

S90

W

V

U

S40

AC

DC

DC

c

e

d

f

b

a

l

k

j

i

g

h

DC(-)

FU2

a

AL1, AL2, DP1, DP2: solenoid valve lead wire connectors

b

S: terminal strip lead wire connector

c

S20~S22 (room A, B, C) + S23 (TO TANK): electronic
expansion valve coil lead wire connector,

d

MR30_A, MR30_B - suspend lead wire connectors

e

S40: thermal overload relay lead wire and high pressure
switch connector

f

Multimeter (DC voltage range)

g

S90, S92, S93: thermistor lead wire connector

h

S50: suspend lead wire connector

i

S60: pressure sensor connector

j

S70: fan motor lead wire connector

k

S80: 4-way valve lead wire connector

l

W, V, U: Compressor lead wire connector

7.1

Specifications of standard wiring
components

NOTICE

We recommend using solid (single-core) wires. If stranded
wires are used, twist the conductor to consolidate the end
or  twist  the  conductor  to  consolidate  the  end  in
combination with the usage of a round crimp-style terminal
on  the  end  of  the  conductor.  Details  are  described  in
"Guidelines  when  connecting  the  electrical  wiring"  in  the
installer reference guide.

Component

Power supply
cable

Voltage

220~240 V

Current

16.3 A

Phase

1~

Frequency

50 Hz

Wire size

MUST comply with national

wiring regulation

3-core cable

Wire size based on the

current, but not less than

2.5 mm

2

Interconnection
cable
(indoor↔outdoor)

Voltage

220~240 V

Wire size

Only use harmonised wire

providing double insulation

and suitable for applicable

voltage

4-core cable

Minimum 1.5 mm

2

Recomended circuit breaker

20 A

Earth leakage circuit breaker /
residual current circuit breaker

MUST comply with national

wiring regulation

Electrical  equipment  must  comply  with  EN/IEC  61000-3-12,  the
European/International  Technical  Standard  setting  the  limits  for
harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.

7.2

To connect the electrical wiring to
the outdoor unit

1

Remove the switch box cover (1 screw).

1

2

2

Connect the wires between the indoor and outdoor units so that
the  terminal  numbers  match.  Make  sure  to  match  the  symbols
for piping and wiring.

3

Make sure to connect correct wiring to correct room.

Summary of Contents for 4MWXM52A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 4MWXM52A2V1B9...

Page 2: ...a f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt...

Page 3: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 4: ...Commissioning 15 11 1 Checklist before commissioning 15 11 2 Checklist during commissioning 15 11 3 Trial operation and testing 15 11 3 1 About wiring error check 15 11 3 2 To perform a test run 16 1...

Page 5: ...he refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause abno...

Page 6: ...n devices of the unit Do NOT touch live parts for 10 minutes after the power supply is turned off because of high voltage risk Please note that some sections of the electric component box are hot Make...

Page 7: ...ambient temperatures within the following ranges unless otherwise specified in the operation manual of the connected indoor unit DX operation range Cooling mode Heating mode 10 46 C DB 15 24 C DB DHW...

Page 8: ...ring refrigerant piping 5 1 1 Refrigerant piping requirements CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly conne...

Page 9: ...ed taking into account the following requirements inside occupied spaces non permanent joints are NOT allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to pip...

Page 10: ...est solution to all connections 3 Discharge all nitrogen gas 5 3 2 To perform vacuum drying DANGER RISK OF EXPLOSION Do NOT open the stop valves before the vacuum drying is finished NOTICE Connect the...

Page 11: ...vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before charging refrigerant make sure the refrigerant piping is connected a...

Page 12: ...ctor d MR30_A MR30_B suspend lead wire connectors e S40 thermal overload relay lead wire and high pressure switch connector f Multimeter DC voltage range g S90 S92 S93 thermistor lead wire connector h...

Page 13: ...ox cover before turning ON the power supply 1 Insulate and fix the refrigerant piping and cables as follows g b a f e c d a Gas pipe b Gas pipe insulation c Interconnection cable d Field wiring if app...

Page 14: ...iority in the following cases Operation mode priority If the priority room function is set on an indoor unit all other indoor units enter the standby mode Priority during high power operation If the i...

Page 15: ...nsate water might drip The indoor unit receives the signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection...

Page 16: ...unit for about 20 minutes The difference should be more than 8 C cooling or 20 C heating 3 First check operation of each unit individually then check simultaneous operation of all indoor units Check b...

Page 17: ...ssor motor M F Fan motor M P Drain pump motor Symbol Meaning M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Print...

Page 18: ...ler v Room A B C and Domestic hot water tank W c Heat exchanger thermistor m Discharge pipe thermistor w Field piping liquid d Refnet header n Compressor x Field piping gas e Fan motor o Accumulator y...

Page 19: ......

Page 20: ...3P600450 7T 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: