background image

Table of contents

Installation manual

4

4MWXM-A9

R32 Split series

3P600450-7T – 2022.09

Table of contents

1 About the documentation

4

1.1

About this document..................................................................

4

2 Specific installer safety instructions

5

3 About the box

6

3.1

Outdoor unit...............................................................................

6

3.1.1

To remove the accessories from the outdoor unit.......

6

4 Unit installation

6

4.1

Preparing the installation site ....................................................

7

4.1.1

Installation site requirements of the outdoor unit ........

7

4.1.2

Additional installation site requirements of the
outdoor unit in cold climates .......................................

7

4.2

Mounting the outdoor unit..........................................................

7

4.2.1

To provide the installation structure ............................

7

4.2.2

To install the outdoor unit............................................

8

4.2.3

To provide drainage ....................................................

8

5 Piping installation

8

5.1

Preparing refrigerant piping .......................................................

8

5.1.1

Refrigerant piping requirements..................................

8

5.1.2

Refrigerant piping insulation .......................................

9

5.1.3

Refrigerant piping length and height difference ..........

9

5.2

Connecting the refrigerant piping ..............................................

9

5.2.1

Connections between outdoor and indoor unit using
reducers ......................................................................

9

5.2.2

To connect the refrigerant piping to the outdoor unit ..

9

5.3

Checking the refrigerant piping .................................................

10

5.3.1

To check for leaks....................................................... 10

5.3.2

To perform vacuum drying .......................................... 10

6 Charging refrigerant

10

6.1

About the refrigerant..................................................................

10

6.2

To determine the additional refrigerant amount ........................

11

6.3

To determine the complete recharge amount ...........................

11

6.4

To charge additional refrigerant ................................................

11

6.5

To fix the fluorinated greenhouse gases label...........................

11

6.6

To check for refrigerant leaks after charging.............................

11

7 Electrical installation

11

7.1

Specifications of standard wiring components ..........................

12

7.2

To connect the electrical wiring to the outdoor unit ...................

12

8 Finishing the outdoor unit installation

13

8.1

To finish the outdoor unit installation.........................................

13

9 Maintenance and service

13

10 Configuration

13

10.1

About standby electricity saving function ..................................

14

10.1.1

To turn ON standby electricity saving function............ 14

10.2

About priority room function ......................................................

14

10.2.1

To set the priority room function ................................. 14

10.3

About night quiet mode .............................................................

14

10.3.1

To turn ON the night quiet mode................................. 14

10.4

About heat mode lock................................................................

14

10.4.1

To turn ON heat mode lock......................................... 14

11 Commissioning

15

11.1

Checklist before commissioning ................................................

15

11.2

Checklist during commissioning ................................................

15

11.3

Trial operation and testing.........................................................

15

11.3.1

About wiring error check ............................................. 15

11.3.2

To perform a test run .................................................. 16

11.4

Starting up the outdoor unit .......................................................

16

12 Disposal

16

13 Technical data

16

13.1

Wiring diagram ........................................................................... 16

13.1.1

Unified wiring diagram legend...................................... 16

13.2

Piping diagram: Outdoor unit...................................................... 17

1

About the documentation

1.1

About this document

WARNING

Make  sure  installation,  servicing,  maintenance,  repair  and
applied  materials  follow  the  instructions  from  Daikin
(including  all  documents  listed  in  “Documentation  set”)
and, in addition, comply with applicable legislation and are
performed  by  qualified  persons  only.  In  Europe  and  areas
where  IEC  standards  apply,  EN/IEC  60335-2-40  is  the
applicable standard.

Target audience

Authorised installers

INFORMATION

This appliance is intended to be used by expert or trained
users  in  shops,  in  light  industry,  and  on  farms,  or  for
commercial and household use by lay persons.

INFORMATION

This  document  only  describes  installation  instructions
specific  to  the  outdoor  unit.  For  installation  of  the  indoor
unit  (mounting  the  indoor  unit,  connecting  the  refrigerant
piping to the indoor unit, connecting the electrical wiring to
the indoor unit …), see the installation manual of the indoor
unit.

Documentation set

This  document  is  part  of  a  documentation  set.  The  complete  set
consists of:

General safety precautions:

▪ Safety instructions that you MUST read before installing

▪ Format: Paper (in the box of the outdoor unit)

Outdoor unit installation manual:

▪ Installation instructions

▪ Format: Paper (in the box of the outdoor unit)

Installer reference guide:

▪ Preparation of the installation, reference data, …

▪ Format:  Digital  files  on 

https://www.daikin.eu

.  Use  the  search

function   to find your model.

Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.

Scan the QR code below to find the full documentation set and more
information about your product on Daikin website.

The original documentation is written in English. All other languages
are translations.

Technical engineering data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

Summary of Contents for 4MWXM52A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 4MWXM52A2V1B9...

Page 2: ...a f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt...

Page 3: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 4: ...Commissioning 15 11 1 Checklist before commissioning 15 11 2 Checklist during commissioning 15 11 3 Trial operation and testing 15 11 3 1 About wiring error check 15 11 3 2 To perform a test run 16 1...

Page 5: ...he refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause abno...

Page 6: ...n devices of the unit Do NOT touch live parts for 10 minutes after the power supply is turned off because of high voltage risk Please note that some sections of the electric component box are hot Make...

Page 7: ...ambient temperatures within the following ranges unless otherwise specified in the operation manual of the connected indoor unit DX operation range Cooling mode Heating mode 10 46 C DB 15 24 C DB DHW...

Page 8: ...ring refrigerant piping 5 1 1 Refrigerant piping requirements CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly conne...

Page 9: ...ed taking into account the following requirements inside occupied spaces non permanent joints are NOT allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to pip...

Page 10: ...est solution to all connections 3 Discharge all nitrogen gas 5 3 2 To perform vacuum drying DANGER RISK OF EXPLOSION Do NOT open the stop valves before the vacuum drying is finished NOTICE Connect the...

Page 11: ...vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before charging refrigerant make sure the refrigerant piping is connected a...

Page 12: ...ctor d MR30_A MR30_B suspend lead wire connectors e S40 thermal overload relay lead wire and high pressure switch connector f Multimeter DC voltage range g S90 S92 S93 thermistor lead wire connector h...

Page 13: ...ox cover before turning ON the power supply 1 Insulate and fix the refrigerant piping and cables as follows g b a f e c d a Gas pipe b Gas pipe insulation c Interconnection cable d Field wiring if app...

Page 14: ...iority in the following cases Operation mode priority If the priority room function is set on an indoor unit all other indoor units enter the standby mode Priority during high power operation If the i...

Page 15: ...nsate water might drip The indoor unit receives the signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection...

Page 16: ...unit for about 20 minutes The difference should be more than 8 C cooling or 20 C heating 3 First check operation of each unit individually then check simultaneous operation of all indoor units Check b...

Page 17: ...ssor motor M F Fan motor M P Drain pump motor Symbol Meaning M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Print...

Page 18: ...ler v Room A B C and Domestic hot water tank W c Heat exchanger thermistor m Discharge pipe thermistor w Field piping liquid d Refnet header n Compressor x Field piping gas e Fan motor o Accumulator y...

Page 19: ......

Page 20: ...3P600450 7T 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: