SQLC-220-086
3
① Voltage, current input (2/2)
№
Setting item
Default settings
110V input
220V input
5
Instantaneous
measurement detection
Voltage upper limit value
OFF
Voltage lower limit value
OFF
6 Backlight
Action
AUTO
Brightness
3(Middle)
7 Measurement range
Voltage range
6600V
220V
Current range
100.0A
Current display peculiar sensitivity
100.0A
Active power polarity
One side swing
Active power range
1200kW
40.0kW
Reactive power range
600kvar
20.00kvar
Power factor range
LEAD 0.500 to 1.000 to LAG 0.500
Frequency range
45.0 to 65.0Hz
8
Analog output
(
1
)
Output factor 1
A(V)
Output factor 2
V(UV)
Output factor 3
W
Output factor 4
cosφ
Output peculiar sensitivity
Current
100.0%
Active power
100.0%
Reactive power
50.0%
Low input cut
OFF
9
Pulse output
(
1
)
Output 1
Factor
Wh
Pulse unit
10kWh/p
0.1kWh/p
Output 2
Factor
Wh
Pulse unit
10kWh/p
0.1kWh/p
10
External operation
input (
1
)
Input 1 function
Alarm reset
Input 2 function
Max./Min. reset
11
Measurement display
ON/OFF
Voltage
ON
Current
ON
Active power
ON
Reactive power
ON
Power factor
ON
Frequency
ON
Watt-hour of receiving
ON
Watt-hour of transmission
ON
var-hour of receiving
ON
var-hour of transmission
ON
Harmonic current
ON
Harmonic voltage
ON
12 Input circuit
Phase line change
3φ3W (Fixed)
Input voltage
110V
220V
13 Measurement
Dead band
0.0%
Tidal current measurement
General measurement
14 Analog output specification (
1
)(
2
)
1 to 5V
15
Analog output
adjustment
(
1
)
Output 1
Bias adjustment
0.0%
Span adjustment
100.0%
Output 2
Bias adjustment
0.0%
Span adjustment
100.0%
Output 3
Bias adjustment
0.0%
Span adjustment
100.0%
Output 4
Bias adjustment
0.0%
Span adjustment
100.0%
Note(
1
) The setting item is not displayed in case there is no corresponding option.
The external operation input constitutes default value with an alarm output option.
If there is no alarm output option, the function is as follows.
Input 1 function:Max. / Min. reset, Input 2 function:Measurement factor change.
Note(
2
) Setting items are not displayed except for analog output DC0 to 5V or DC1 to 5V.
And analog output insulation product does not display a setting item.