SQLC-220-086
32
(4) Setting of reactive power measurement range.
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Setting of
measurement range of
reactive power.
(216)
Press SET and RESET/SHIFT together for longer than 3 seconds
(211)
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
(212) (213) (214)
Press RESET/SHIFT
Press RESET/SHIFT
Select a measuring range by + and -
(215) (216)
Press SET
Selected measuring range is entered
Press DISPLAY
Returns to
display mode.
47 to
51
(5) Setting of Wh (varh) output pulse unit.
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Set the pulse unit
of pulse output 1
(Po1).
(242P)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press MODE
(211) (221A)
Press MODE
Press RESET/SHIFT
Select a output pulse unit by + and -
(241A) (242P)
Press SET
Selected output pulse unit is entered
Press DISPLAY
Returns to
display mode.
54
Set the pulse unit
of pulse output 2
(Po2).
(244P)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press MODE
(211) (221A)
Press MODE
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
(241A) (242P) (243P) (244P)
Select a output pulse unit by + and -
Press SET
Selected output pulse unit is entered
Press DISPLAY
Returns to display mode.
54
(6) Setting of power factor and frequency measurement range
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Set the measurement
range of power
factor.
(217)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press RESET/SHIFT
(211) (212)
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
(213) (214) (215) (216)
Press RESET/SHIFT
Select a measuring range by + and -
Press SET
(217)
Selected measuring range is entered
Press DISPLAY
Returns to display mode.
47 to
51
Set the measurement
range of frequency.
(218)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press RESET/SHIFT
(211) (212)
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
(213) (214) (215) (216)
Press RESET/SHIFT
Press RESET/SHIFT
Select a measuring range by + and -
(217) (218)
Press SET
Selected measuring range is entered
Press DISPLAY
Returns to
display mode.
47 to
51
(7) Setting of current display intrinsic sensitivity.
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Set the display
sensitivity (% of
a display to an
input) of current.
(213)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press RESET/SHIFT
(211) (212)
Press RESET/SHIFT
Select a display sensitivity by + and -
Press SET
(213)
Selected display sensitivity is entered
Press DISPLAY
Returns to display mode.
47 to
51