CDC 200/350

CDC-PC xxxx-T01

* TMS line must 
  be disconnected!

CDC-PC xxxx-T01

*

*

Tandem Safety Function

For the operation of 2-3 drives on separate vents the 
tandem safety function (TMS) may not be used! For 
this  the  TMS  line  (yellow)  of  the  connection  cable 
CDC-PC xxxx of the drives is disconnected, so that 
the remaining drive(s) are still opened in case of fire 
in the event of a failure, under voltage or overload 
cut-out.

Whenever two drives are operated on a single sash, 
the  tandem  safety  function  can  be  used.  This 
function  connects  the  cut-offs  of  the  two  drives  in 
such a way that if one drive is cut off due to overload, 
the other drive will also be cut off.

In this case active jamming protection may not 
activated!

Type 

 

CDC 200/350 

 

CDC 200/350 -SBD

Rated voltage 

 

24 VDC, ±15%, 0,6 A 

24 VDC, ±15%, 0,5 A

Chain type 

 

Standard chain   

Side bow chain

Nominal pressure   

200 N + ca. 20% cut-off reserve 

150 N + ca. 20% cut-off reserve

   

 

(temporary) 

 

(temporary)

Nominal tractive force 

150 N safety cut-off force

Nominal locking force 

approx. 1500 N 

Runtime-OPEN 

 

approx. 6,7 mm/s 

Runtime-CLOSED   

approx. 5 mm/s

Service life 

 

>20.000 double strokes

Housing   

 

Aluminium pressure die casting

Protective system   

IP 50

Temp.range 

 

-5 ... +75°C

Fire stability 

 

30 min / 300°C

Emission sound pressure level  LpA ≤ 70 dB(A)
Connection 

 

2,5 m silicone cable

Additional functions 

Closing edge protection = deactivated

   

 

Locking relief = activated (retraction lift max. 0.2 mm) 

Technical data

99.823.30 2.4/03/16

7/16

English

CDC 200/350

Mot. b 

(BN)

 Mot. a 

(WH)

Pin Assignment

YE (TMS)

BN (Mot. b)
WH (Mot. a)

OG (n.c.)

Standard

YE (TMS)

GY (-SGI)
GN (+SGI)
BN (Mot. b)
WH (Mot. a)
PK (n.c.)

OG (n.c.)

YE (TMS)

GY (BRV)

BN (Mot. b)
WH (Mot. a)
PK (n.c.)

OG (n.c.)

GN (n.c.)

GN (n.c.)

Option -SGI

Option -BRV

(WH)  white
(BN)  brown
(OG)  orange
(YE)  yellow
(GN)  green
(PK)  pink
(GY)  grey

Minimum sash height/ -width

The details apply to a 

non-rotational installation of the drive!

Standard chain:

Minimum size (mm) = Stroke (mm) x 3.9

Side bow chain -SBD:

Stroke 

 

Minimum size (x)

150 mm  =  300 mm 
280 mm  =  450 mm
350 mm  =  550 mm 

x

x

Electrical devices, accessories, batteries and packa-
ging  should  be  sorted  for  environmental-friendly 
recycling.  Do  not  dispose  electrical  devices  and 
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for 
waste  electrical  and  electronic  equipment  and  its 
implementation into national right, electrcal devices 
that are no longer usable must be collected separa-
tely  and  disposed  of  in  an  environmentally  correct 
manner.

Disposal

Declaration of Conformity

We  declare  under  our  sole  responsibility  that  the 
product  described  under  “Technical  Data”  is  in 
conformity with the following directives:

2014/30/EU, 2014/35/EU

Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek

Dirk Dingfelder 

Maik Schmees

Member of the Board 

Authorized signatory, Technical Director

24.02.2016

Observe maximum pressure load of the chain!
Maximum pressure load of chain is not automatically 
identical with maximum pressure force of the drive!

Pressure load diagram

Pressure load (N)

-SBD / -SBU

Standard

100

200

300

400

500

600

50

100

150

200

250

250

80

Stroke (mm)

Summary of Contents for CDC 200

Page 1: ...ixation Rogamos que pidan los juegos de fijación por separado de Originalbetriebsanleitung Seite 2 Anschluss Seite 14 Abmessungen Seite 16 en Original instructions Page 5 Connection Page 14 Dimensions Page 16 fr Notice originale Page 8 Connexion Page 14 Dimensions Page 16 es Manual original Página 11 Conexión Página 14 Dimensión Página 16 CDC PC xxxx T01 ...

Page 2: ...o RWAgemäß DIN EN 12101 2 sowie für täglichen Lüftungsbetrieb Nur für die Innenmontage geeignet Kettentypen Vor der Montage desAntriebes ist die Montageanleitung des Konsolensatzes zu beachten Die darin enthaltenen Montagehinweise sind unbedingt einzuhalten Achtung bei SBD SBU Ketten SBD Standardkette SBU Seitenbogenkette Seitenbogenkette Wartung und Reinigung Wartungs undReinigungsarbeitennurinsp...

Page 3: ...03 16 CDC 200 350 3 16 Deutsch Konformitätserklärung Wir erklären in alleiniger Verantwortung dass das unter Technische Daten beschriebene Produkt mit den folgenden Richtlinien übereinstimmt 2014 30 EU 2014 35 EU Technische Unterlagen bei D H MechatronicAG D 22949Ammersbek Dirk Dingfelder Maik Schmees Vorstand Prokurist Technischer Leiter 24 02 2016 Elektrogeräte Zubehör Batterien und Verpackungen...

Page 4: ...trieben an separaten Flügeln darf die Tandem Sicherheits Funktion TMS nicht genutzt werden Hierbei wird die TMS Leitung gelb des Verbindungskabel CDC PC xxxx der Antriebe getrennt so dass bei Ausfall Unterspannung oder Überlastabschaltung eines Antriebes der die andere n Antrieb e im Brandfall trotzdem geöffnet werden Bei Betrieb von 2 Antrieben an einem Flügel kann die Tandem Sicherheits Funktion...

Page 5: ...f rain Use unmodified original D H parts only Observe enclosed red safety note Safety notes SBD Standard chain SBU Side bow chain Side bow chain Chain type The mounting instructions for the bracket set must be observed before mounting Always observe and comply with the information in the mounting instructions Attention with side bow chains SBD and SBU Maintenance and cleaning Maintenance work is o...

Page 6: ...ize x 150 mm 300 mm 280 mm 450 mm 350 mm 550 mm x x Electrical devices accessories batteries and packa ging should be sorted for environmental friendly recycling Do not dispose electrical devices and batteriesinto householdwaste Only for EC countries According the European Guideline 2012 19 EU for waste electrical and electronic equipment and its implementation into national right electrcal device...

Page 7: ...ver two drives are operated on a single sash the tandem safety function can be used This function connects the cut offs of the two drives in such a way that if one drive is cut off due to overload the other drive will also be cut off In this case active jamming protection may not activated 99 823 30 2 4 03 16 7 16 English CDC 200 350 Mot b BN Mot a WH PinAssignment YE TMS BN Mot b WH Mot a OG n c ...

Page 8: ... pièces d origine D H non modifiées Respecter les indications figurant sur la notice de sécurité rouge ci jointe Consignes de sécurité 99 823 30 2 4 03 16 Type de chaîne Avant le montage de la motorisation veuillez consulter la notice de montage du kit de console Les instructions de montage qu elle contient sont à respecter absolument Attention lorsqu il s agit de chaînes SBD SBU Chaîne standard C...

Page 9: ...re chacun une voie de recyclage appropriée Ne jetez pas votre appareilélectroportatifaveclesorduresménagères Seulementpourlespaysdel UnionEuropéenne Conformément à la directive européenne 2012 19 EU relative aux déchets d équipements électriques et électroniques et sa réalisation dans les lois nationales les outils électroportatifs dont on ne peut plus se servir doivent être séparés et suivre une ...

Page 10: ...onnement de 2 à 3 moteurs sur des battants séparés Il est alors requis de sectionner la ligne de la TMS jaune du câble de raccordement CDC PC xxxx des moteurs de manière à ce que l ouverture des battants demeure possible lors d une panne d une sous tension ou d une coupure de surcharge d un moteur via le ou les autres moteurs en cas d incendie Dans le cas d un fonctionnement avec 2 moteurs sur un ...

Page 11: ... deberán utilizarse sensores de lluvia Emplear únicamente piezas originales D H no modificadas Respetar las indicaciones de la hoja de serguridad adjunta Notas de seguridad 99 823 30 2 4 03 16 Tipo de cadena Antes de montar el accionamiento lea las instrucciones de montaje de la consola Las instrucciones de montaje allí descritas son de obligado cumplimiento Atención En las cadenas SBD SBU Cadena ...

Page 12: ... de la cadena La carga de compresión máxima de la cadena no se corresponde automáticamente con la fuerza de compresión máxima del accionamiento Diagramadecargadecompresión Altura latitud mínima de la hoja Las indicaciones son válidas para el montaje no giratorio del accionamiento Cadena estándar Mínimo x mm Carrera mm x 3 9 Cadenas de flexión lateral Carrera Mínimo x 150 mm 300 mm 280 mm 450 mm 35...

Page 13: ...iduales no debe utilizarse la función de seguridad tándem TMS En este caso se desconectará el cable TMS amarillo del cable de conexión CDC PC xxxx de los accionamientos de forma que en caso de avería subvoltaje o una desconexión por sobrecarga de un accionamiento el o los otros accionamientos se abran en caso de incendio Al actuar dos accionamientos en una hoja se puede utilizar la función de segu...

Page 14: ...rs par ouvrant Cable conforme a la tabla de cableado D H Véanse instrucciones de uso de la central Atención se necesitan 2 motores por cada batiente Mot b BN Mot a WH Anschluss von 2Antrieben sternförmig Connection of 2 drives star shaped Raccordement de 2 moteurs en étoile Conexión de 2 accionamientos en estrella 99 823 30 2 4 03 16 CDC 200 350 14 16 DE EN FR ES TMS YE Mot b BN Mot a WH BK BK OG ...

Page 15: ...ot a Mot b MOT 2 3 1 Gruppe Group Groupe Grupo CDC 200 350 15 16 DE EN FR ES 99 823 30 2 4 03 16 WH weiss white blanc blanco BN braun brown brun marrón OG orange orange orange naranja YE gelb yellow jaune amarillo GN grün green vert verde PK rosa pink rose rosa GY grau grey gris gris TMS gegen Kurzschluss sichern Protect TMS wire against short circuit TMS Protéger contre les courts circuits TMS Pr...

Page 16: ...mersbek 49 239 Tel 40 605 65 49 Fax 40 605 65 254 E Mail info dh partner com www dh partner com 2012 D H Mechatronic AG Ammersbek Technische Änderungen vorbehalten Rights to technical modifications reserved Sous réserve de modifications techniques Derecho reservado a modificaciones técnicas 100 Recyclingpapier Recycled paper Papier recyclé Papel reciclado ...

Reviews: