TECHNICAL SPECIFICATIONS
Models
OLS6000ERT6UA
OLS10000ERT6UA
Capacity (VA)
6000
10000
Capacity (Watts)
5400
9000
Form Factor
Rackmount/ Tower
Input
Phase
Single
Voltage Range
110~276Vac (Depends on load level)
Frequency Range
50/60±10%Hz
Rated Current
36A
55A
Power Factor
≥
0.99 @ full load
Battery
Rated Voltage
192Vdc
Rated Current
31A
51A
Output
Voltage*
208/220/230/240Vac
Frequency
Synchronized 50/60×(1±10%)Hz @Line mode
50/60×(1±0.1%)Hz @Battery mode
Wave Form
Sine
Load Type
PF 0.5~1, lagging
THDV
≤
2% @ full linear load ;
≤
5% @ full nonlinear load
Protection
Overload Protection**
Line Mode:
105~125% Warning, transfer to bypass after 1m
125~135% Warning, transfer to bypass after 30s
135~150% Warning, transfer to bypass after 1s
>150% Transfer to bypass immediately
Battery Mode:
105~125% Warning, transfer to bypass after 1m
125~135% Warning, transfer to bypass after 30s
>135% Transfer to bypass immediately
Operating Environment
Temperature
0
℃
~40
℃
Humidity
20-90% (non-condensing)
Altitude***
<1000m
Physical Size
Dimensions W×H×D (mm)
438 x 261 x 680
Net Weight (kg)
59.4
70
*The load capacity would be derated to 90% automatically when the output voltage is adjusted to 208Vac.
**The overload capacity would be derated automatically in Line mode while the circumstance temperature
is higher than 35 degree.
***The load capacity should be derated 1% every 100m heightened on the basis of 1000m.