OPERATION
PARALLEL FUNCTION
Brief Introduction
1.
N represents the minimum UPS number that the total load needs, X represents
the redundant UPS number, i.e. the fault UPS number that the system can handle
simultaneously. When the X is larger, the reliability of the power system is higher.
2. Up to 4 UPS can be connected in parallel to achieve output power sharing and power
redundancy.
How To Install A New Parallel UPS System
1.
Before installing a new parallel UPS system, user need to prepare input and output wires,
input and output breaker, main maintenance bypass switch.
2. Remove the cover plate of the parallel port on the UPS, connect each UPS one by one
with the parallel cable, and re-screw the parallel port cover which is supplied in the
accessories.
3. Please follow the
POWER WIRES INSTALLATION
on page 14 strictly to perform the
wiring of each UPS.
4. Connect the output wires of each UPS to an output breaker panel.
5. Connect each output breaker to a main output breaker and then to the loads.
6.
CAUTION: Each UPS needs an independent battery pack.
7. Please refer to the below wiring diagram.