14
ELECTRICAL INSTALLATION
(2) No matter the Power module is connected to the mains power or not, the output of the
Power module may be electrically live. The parts inside the unit may still have hazardous
voltage after turning off the Power module. To make the Power module without output,
turn off the Power module, and cut off the mains power supply, wait the Power module
shut down completely, finally remove the battery connection.
(3) Open the terminal block cover located on the rear panel of Power module, please refer to
the appearance diagram.
(4) For XRT6-6000(L), it is recommended to select the UL1015 10AWG/6mm² or other
insulated wire which complies with AWG Standard for the Power module input and output
wirings.
(5) For XRT6-10000(L), it is recommended to select the UL1015 8AWG/10mm² or other
insulated wire which complies with AWG Standard for the Power module input and output
wirings.
(6) Ensure the capacity of mains power supply. Do not use the wall receptacle as the input
power source for the Power module, as its rated current is less than the Power module’s
maximum input current. Otherwise the receptacle may be burned and destroyed.
(7) The protective earth ground wire should be installed first according to the following
diagram. It is better to use green wire or green wire with yellow ribbon wire.
(8) Connect other input and output wires to the corresponding input and output terminals
according to the following diagram.
(9) It is requested to use the accessorial terminal splices which can be compacted on the
wires tightly, to ensure the connection between the wires and the terminal block is reliable.
Input and output terminal block wiring diagram
Parallel Mode Output L
Parallel Mode Output N
Single Mode Output L
Single Mode Output N
Battery -
Input L
Input N
Input Ground
B
pL
pN
sL
sN
OUTPUT~
BATTERY
INPUT~
N
L