23
OPERATION
SETTING Menu
1.
Select “Setting” and press “ENTER” button.
2. Press “UP” and “DOWN” buttons to scroll through the “Setting” menu shown in the table
below.
3. Press “ENTER” button to enter the setting page.
4. Press “UP” and “DOWN” buttons to scroll through the setting value.
5. Press “ENTER” button to confirm the selected setting value and return to the previous
page.
6. Press “ESC” button to return to the sub-menu.
*Password is AAAA when Enabled.
SETTING ITEMS
AVAILABLE SETTINGS
DEFAULT
SETTING
User password*
[Enabled] [Disabled]
Disabled
Audio alarm
[Enabled] [Disabled]
Enabled
Site wiring fault alarm
[Enabled] [Disabled]
Enabled
Ambient temperature warning
[Enabled] [Disabled]
Enabled
DC start
[Enabled] [Disabled]
Enabled
Auto Restart
[Enabled] [Disabled]
Enabled
Automatic overload restart
[Enabled] [Disabled]
Enabled
Auto Bypass
[Enabled] [Disabled]
Disabled
Short circuit clearance
[Enabled] [Disabled]
Disabled
Power strategy
[Normal] [ECO] [CVCF]
Normal
Rated output voltage
[208V] [220V] [230V] [240V]
230V
Output frequency
[50Hz] [60Hz]
50Hz
Bypass voltage low range
[10%] [15%] [20%]
15%
Bypass voltage high range
[10%] [15%]
10%
Bypass frequency range
[1%] [2%] [3%] [4%] [5%] [6%] [7%] [8%]
[9%] [10%]
10%
ECO voltage range
[10%] [15%]
10%
ECO frequency range
[1%] [2%] [3%] [4%] [5%] [6%] [7%] [8%]
[9%] [10%]
5%
Automatic battery tests period
[0 day] ~ [45days]
7days
Set running time
Day:hour:minute:second
0000:00:00:00~9999:23:59:59
Running
time
Ext. Bat Type
[Standard] [Customized]
Standard
Ext. Bat Pack
[1 Pack] ~ [15 Packs]
0 Pack
Restore default setting
[Yes] [NO]