13
ELECTRICAL INSTALLATION
POWER WIRES INSTALLATION
• The system must be installed and wired only by qualified electricians in accordance with
applicable safety regulations.
• For safety, please cut off the mains power switch before installation.
• When installing the electrical wiring, please note the nominal amperage of your incoming
feeder.
• The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
• Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of
space on each side.
• Condensation to water drops may occur if the UPS is unpacked in a very low temperature
environment. In this case, it is necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of electric shock.
(1) It is suggested to install an external isolating device against current backfeed between
mains input and Power module. After the device is installed, it must add a warning label with
the following wording or the equivalent on the external AC contactor:
RISK OF VOLTAGE
BACKFEED
. Isolate the Power module before operating on this circuit, then check for
hazardous voltage between all terminals.
MODEL
XRT6-6000(L)
XRT6-10000(L)
Protective earth conductor
Minimum cross section
6mm²
10mm²
Input L, N, G
Minimum conductor cross section
(UL1015 10AWG)
(UL1015 8AWG)
Input breaker
6mm²
(UL1015 10AWG)
10mm²
(UL1015 8AWG)
Output L,N,
Minimum conductor cross section
40A/250Vac
63A/250Vac
Torque for fixing above terminals
6mm²
(UL1015 10AWG)
10mm²
(UL1015 8AWG)
Typical external isolating device installation
L
Input Main
Breaker
AC Contactor
Coil Remotes Switch
UPS
Main
Input
N