Part No. 4801-5307 Rev 2-15
Evolution 3000 and 3001
38 of 70
** Cool Evaporative Properties **
These stages typically operate
Evaporative Cooling Systems. The
following are additional properties:
(1)Only Operate During Tunnel Vent = No
(2)Time Override:
Allow to Operate Always
Time falls between 12:00p - 5:00p
(3)Humidity Override:
Allow to Operate Always
Humidity < 75%
(4)Growout Day Override:
Allow to Operate Always
Growout Day > 14
(5)Outside Temperature Override
Allow to Operate Always
Outside Temperature > 10.2°
** Natural Ventilation Properties **
The Natural Ventilation Stages typically
operate sidewalls. The following are some
additional properties:
(1)Time Override:
Allow to Operate Always
Time falls between 5:00p - 5:00a
(2)Growout Day Override:
Allow to Operate Only While
Growout Day > 7
(3)Outside Temperature Override
Allow to Operate Always
Outside Temperature > 10.2°
7.10.6
Cool Evaporative Properties
Cool Evaporative Properties allow for setting several override functions. Take note when setting the
properties. All options must be true before the stage is allowed to operate.
For example if all options are set to Only While, then all options will have to be true or in the range before
the stage is allowed to operate.
(1) Only Operate During Tunnel
Vent
–Setting this to “Yes”
will only allow the
evaporative cooling stages to
operate during tunnel.
Otherwise on “No” will
allow the stages to operate
while not in tunnel. For
example on misting Hogs
during natural ventilation.
(2) Time Override –
When set to
Only While, the Time
Override will allow the
stages to operate only while
the time is between the times
you set. Otherwise when set
to Always, the time will not
affect the stages.
(3) Humidity Override -
Run while humidity is less than XX%. When set to Only While, the Humidity
Override will allow the stages to operate only while the humidity is less than the humidity you set.
Otherwise when set to Always, the humidity will not affect the stages.
(4) Growout Day Override -
When set to Only While, the Growout Day Override will allow the stages to
operate only while the growout day is greater than the day you set. Otherwise when set to Always,
the day of growout will not affect the stages.
(5) Outside Temperature Override -
When set to Only While, the Outside Temperature Override will
allow the stages to operate only while the outside temperature is greater than the target plus or
minus the desired setting. Otherwise when set to Always, the outside temperature will not affect
the stages.
7.10.7
Natural Ventilation Properties
(1) Time Override
- When set to Only
While, the Time Override will
allow the Natural Curtain
Stages to open while the time
is between the times you set.
Otherwise when set to Always,
the time will not affect the
Natural Curtain Stages.
(2) Growout Day Override
- When set
to Only While, the Growout
Day Override will allow the
Natural Curtain stages to
operate only while the growout
day is greater than the day you
set.
Otherwise when set to Always, the day of growout will not affect the stages.
(3) Outside Temperature Override
- When set to Only While, the Outside Temperature Override will
allow the stages to open only while the outside temperature is greater than the target plus or minus
the desired setting. Otherwise when set to Always, the outside temperature will not affect the
stages.