WARNING
It is important to respect the clearances above and below the enclosure to allow
airflow to the heatsink
Cable Connectors
NOTE:
Nylon cable glands are permitted for cable or wire fastening.
WARNING
Use watertight compression cable glands rated IP54 for each cable used.
WARNING
Use silicone to seal the cable gland rated IP54 if more than one cable is use in the
same cable gland.
WARNING
The warranty is void if the product enclosures are not sealed correctly and the
installation does not respect the manufacturer recommendations.
WARNING
Ensure all cables enter through the bottom of the plastic enclosure. Do not make
holes on the top or on the sides of the enclosures. Be careful not to damage the
electronic cards located inside the enclosure when drilling at the bottom of the
enclosure.
NOTICE
The use of flexible tube with water and dust tight connectors at both ends is
acceptable.
Cable Support
Support the cables with clips or cable trays whenever possible to avoid damage at the connection points.
Cable Routing
NOTICE
Never run low voltage (24V and less) wires like communication wires, inputs or
sensors wires in the same conduit or underground trench as a High Voltage (Power)
wire.
When low voltage cables run parallel to high voltage cables (120/230/380 VAC or 24 VDC), place them at
a distance of at least 460 mm (18 inches) from each other to avoid electromagnetic interference. This
also applies to high and low voltage cables running through an underground trench.
If low voltage cables cross high voltage cables, ensure they cross at an angle of 90° to minimize electro-
magnetic interference.
18
891–00516
EDGE Wiring Diagram
Summary of Contents for EDGE 074-11793
Page 4: ...NOTES 4 891 00516 EDGE Wiring Diagram...
Page 16: ...Chapter 1 Introduction 16 891 00516 EDGE Wiring Diagram...
Page 22: ...NOTES 22 891 00516 EDGE Wiring Diagram...
Page 25: ...NOTES 891 00516 EDGE Wiring Diagram 25...
Page 37: ...NOTES 891 00516 EDGE Wiring Diagram 37...
Page 45: ...Chapter 2 Wiring Diagrams Figure 2 25 Inlet Wiring 891 00516 EDGE Wiring Diagram 45...
Page 46: ...Chapter 2 Wiring Diagrams Figure 2 26 Inlet Failsafe Wiring 46 891 00516 EDGE Wiring Diagram...
Page 72: ...NOTES 72 891 00516 EDGE Wiring Diagram...
Page 76: ...NOTES 76 891 00516 EDGE Wiring Diagram...
Page 79: ...C Extending a cable Best practice using a junction box 891 00516 EDGE Wiring Diagram 79...
Page 80: ...Appendix C Extending a cable Using of heat shrink tubing 80 891 00516 EDGE Wiring Diagram...