Guidelines on the Ideal Location for Installation
Consider the environment, mounting recommendations, and clearance space to choose the ideal location
for your system.
Operating Environment
• To avoid exposing the system to harmful gases or excessive humidity, install the system and the
Expansion Boxes in a corridor or an area dedicated to electronic controllers.
• The ideal ambient temperature is between 20 °C and 25 °C (68 °F - 77 °F). The temperature should
not go lower than 0 °C (32 °F) and should not exceed 40 °C (104 °F).
• Ensure there is sufficient ventilation around the unit.
• Install the Expansion Boxes far from sources of vibrations and where they are not likely to get
bumped.
• Install the EDGE 4IN-2V-8DO in a cabinet
• The EDGE 4IN-2V-8DO temperature must be lower than 70°C (158°F) in the cabinet
IMPORTANT:
If you are not planning on installing the system immediately, store the units in a cool dry
place.
Requirements for the Mounting Structure
Fix the enclosures into the supporting structure behind a drywall. If this is not possible, consider the addi-
tion of a wood frame on which the enclosure could be screwed.
Clearance Around the System Modules
The following minimum clearances must be respected around the EDGE enclosures.
891–00516
EDGE Wiring Diagram
15
Summary of Contents for EDGE 074-11793
Page 4: ...NOTES 4 891 00516 EDGE Wiring Diagram...
Page 16: ...Chapter 1 Introduction 16 891 00516 EDGE Wiring Diagram...
Page 22: ...NOTES 22 891 00516 EDGE Wiring Diagram...
Page 25: ...NOTES 891 00516 EDGE Wiring Diagram 25...
Page 37: ...NOTES 891 00516 EDGE Wiring Diagram 37...
Page 45: ...Chapter 2 Wiring Diagrams Figure 2 25 Inlet Wiring 891 00516 EDGE Wiring Diagram 45...
Page 46: ...Chapter 2 Wiring Diagrams Figure 2 26 Inlet Failsafe Wiring 46 891 00516 EDGE Wiring Diagram...
Page 72: ...NOTES 72 891 00516 EDGE Wiring Diagram...
Page 76: ...NOTES 76 891 00516 EDGE Wiring Diagram...
Page 79: ...C Extending a cable Best practice using a junction box 891 00516 EDGE Wiring Diagram 79...
Page 80: ...Appendix C Extending a cable Using of heat shrink tubing 80 891 00516 EDGE Wiring Diagram...