NOTICE
The recommended installation wire gauge is 16 AWG (diameter of 1.29mm or
cross sectional area of 1.30mm
2
) for the power supply wires at a length of 300
meters (1000 feet). The recommended installation wire gauge is 18 AWG
(diameter of 1.02mm or cross sectional area of 0.82mm
2
) for the communication
wires at a length of 1200 meters (4000 feet). The cable must be twisted pair and shielded.
WARNING
Installation must only be performed by qualified service personnel.
NOTICE
For the small terminal blocks used for inputs and low voltage outputs, use a
tightening torque from 0.5N*m (4.43lbf*in) to 0.6 N*m (5.2lbf*in) to fasten a wire.
The communication network must be installed in a daisy chain topology. The order of the wires is
very important. At both ends of network, the End-of-Line must be activated. If the wiring can’t be
done in a single chain, you might need to deactivate the end-of-line (EOL) resistor to improve com-
munication. AP/Cumberland does not warranty the proper operation if the topology network is not
daisy chain.
60
891–00516
EDGE Wiring Diagram
Summary of Contents for EDGE 074-11793
Page 4: ...NOTES 4 891 00516 EDGE Wiring Diagram...
Page 16: ...Chapter 1 Introduction 16 891 00516 EDGE Wiring Diagram...
Page 22: ...NOTES 22 891 00516 EDGE Wiring Diagram...
Page 25: ...NOTES 891 00516 EDGE Wiring Diagram 25...
Page 37: ...NOTES 891 00516 EDGE Wiring Diagram 37...
Page 45: ...Chapter 2 Wiring Diagrams Figure 2 25 Inlet Wiring 891 00516 EDGE Wiring Diagram 45...
Page 46: ...Chapter 2 Wiring Diagrams Figure 2 26 Inlet Failsafe Wiring 46 891 00516 EDGE Wiring Diagram...
Page 72: ...NOTES 72 891 00516 EDGE Wiring Diagram...
Page 76: ...NOTES 76 891 00516 EDGE Wiring Diagram...
Page 79: ...C Extending a cable Best practice using a junction box 891 00516 EDGE Wiring Diagram 79...
Page 80: ...Appendix C Extending a cable Using of heat shrink tubing 80 891 00516 EDGE Wiring Diagram...