Direction menu
In this menu, has to set if the pump has to dose above the setpoint or below this value. For instance to reduce pH value, dosing
an acid chemical, the direction arrow has to point down. In this way the pump will be active, dosing, when the pH value is higher
than the setpoint previously set.
To select the direction of the arrow, use the + and -
buttons. Pressing OK the direction will be
memorized.
Manual or Proportional mode
After selected direction of the dosing, the pump will show ON-OFF or PROP. flashing. With + or - buttons it's possible to shift
among them.
ON-OFF - When the pump has to dose it will run at flow rate selected by the user in Flow rate setting, and it stops at the
Setpoint;
PROP. - In this mode the pump will dose proportionally to the setpoint value. The pump starts dosing over setpoint (determined
by hysteresis), increasing its speed up to the MAX FREQUENCY ADJUSTMENT use will set after pressing OK from this menu.
Use + and - to select the operative mode
Press OK to confirm the selection. Following will be
described these two modes:
Frequency adjustment
If the user has select Manual mode (ON-OFF), after pressing OK button, the pump will pass in Frequency adjustment menu.
User has to set the flow rate of the pump, from 0 to 100% of maximum frequency.
Use + e - buttons to select the desired flow rate
percentage. Pressing OK the pump will save data
and go out from Setpoint mode. It will be enough to
press ESC button to go in metering mode.
Summary of Contents for BOMBAPRO PH-RX
Page 2: ......
Page 7: ...Limpieza y mantenimiento del electrodo 30 DIBUJOS 117 Bomba 117 Cuerpo bomba 118 ESPAÑOL 7 ...
Page 32: ......
Page 35: ...DISEGNI 117 Pompa 117 Corpo Pompa 118 ITALIANO 35 ...
Page 60: ......
Page 63: ...DRAWINGS 117 Pump 117 Pump head 118 ENGLISH 63 ...
Page 88: ......
Page 91: ...DESSINS 117 Pompe 117 Corps de pompe 118 FRANÇAIS 91 ...
Page 116: ......
Page 119: ......
Page 120: ...CDMU 00203ML1A 03 2016 ...