8. ELECTRICAL EQUIPMENT LMO14.113 (380IC 17/19)
8.1.1 Component list
A1 Oil burner control
T1 Ignition transformer
E1 Preheater
Y1 Solenoid valve
M1 Burner motor
X1 Plug-in contact, burner
R1 Photocell QRB
X2 Plug-in contact, boiler
U2 UV-Detector QRC
Preheater wiring colours:
A Blue
B Brown
C Black
The installation must be connected to the mains and fused according to
local regulations.
8.1.2 Function LMO14.113
1a.
Operations switch ON, thermostat ON
The burner motor starts, ignition sparks initiated and pre-ventilation
continues until the set pre-ventilation period is over and the
solenoid valve (2) opens.
1b.
Operations switch ON, thermostat ON
The preheater is energized and the pre-heating period begins.
This continues until the operating temperature is reached and the
preheater thermostat closes. The burner motor starts, ignition
sparks initiated and pre-ventilation continues until the set pre-
ventilation period is over and the solenoid valve (2) opens.
2.
Solenoid valve opens
The oil mist is formed and ignited. The photocell indicates fl ame.
The ignition spark ceases 15 sec. after fl ame indication.
3.
a
b
Safety period runs out
If the fl ame is not present before the end of this period, the
oil burner
control blocks further operation.
If the fl ame for any reason disappears after this time period, the
burner will make a new start attempt.
4-5 During operation
If burner operations are interrupted via the main switch or
thermostat, a new start will be initiated when conditions accord-
ing to point 1 are fulfi lled.
Oil burner control blocks
Red light on the oil burner control illuminates. The burner is re-
started by pressing the reset button.
8.1.3 Technical data
LMO14.113
Pre-ignition period:
15 s
Pre-ventilation period:
16 s
Post-ignition period:
10 s
Safety period:
< 10 s
Re-connection after release:
< 1 s
Reaction time fl ame extinction:
< 1 s
Ambient temperature:
–5 - +60°C
Min. current with fl ame:
45 µA
Max current when dark, start:
5,5 µA
Ingress Protection:
IP 40
Photocell current checks
Photocell current is measured with a direct current ammeter
(mulitimeter μA) connected in series with the photocell.
Summary of Contents for CTC 380 IC
Page 2: ......
Page 3: ...CTC 380 IC Models 17 19 24 29 162 105 11 1 2013 05 21...
Page 4: ......
Page 6: ...CTC 380 IC 6...
Page 45: ...CTC 380 IC 45...
Page 46: ......
Page 67: ...21 Boiler 8 ELECTRICAL EQUIPMENT 380IC 17 19 8 1 Wiring diagram LMO14 113...
Page 73: ......
Page 74: ......
Page 75: ......