HV Breakout Module – Appendix
Installation Manual
39
Version 01.20 // 2021
Cable
cross section Cable
Ring terminals
PG gland
35 mm²
Coroplast
FHLR2GCB2G 35 mm²
ART1520523
Ring Terminal Set 35 mm²
HV BM 1.2
ART1520201
PG cable gland set
11/20 HV BM
50 mm²
Coroplast
FHLR2GCB2G 50 mm²
ART1520524
Ring Terminal Set 50 mm²
HV BM 1.2
ART1520201
PG cable gland set
11/20 HV BM
70 mm²
Coroplast
FHLR2GCB2G 70 mm²
ART1520545
Ring Terminal Set 70 mm²
HV BM 1.2
ART1520201
PG cable gland set
11/20 HV BM
95 mm²
Coroplast
FHLR2GCB2G 95 mm²
ART1520526
Ring Terminal Set 95 mm²
HV BM 1.2
ART1520200
PG cable gland set
15/25 HV BM
Tab. 7-1: Components for single-wire HV power cables
Fig. 7-4: Step 1: Removing the outer sheath
"
Remove the outer sheath to the required length.
16
Make sure that the
shielding mesh lying underneath will not be damaged.
Fig. 7-5: Step 2: Removing the protective foil.
"
Remove the protective foil from the shielding mesh.
Fig. 7-6: Step 3: Applying a mark on the shielding
"
Mark a 20 mm wide segment on the shielding mesh.
"
Remove the remaining shielding mesh.
Fig. 7-7: Step 4: Marking the inner sheath
"
Apply a mark on the inner sheath with a distance of 3 mm to the end of the
shielding mesh.
16 Stripping length of the outer sheath depending on the cable cross section: 35 mm²: 65 mm, 50 mm²: 62 mm,
70 mm²: 55 mm, 95 mm²: 55 mm