CS THERMOS Arianna 10 Instructions Manual Download Page 45

45

code 6118250   iss. 10-2018

10.3  Cleaning the combustion chamber 

Cleaning by turbulators must be performed at least once a week, as described below:

- Raise or remove any covers.

- Raise and lower the turbulators repeatedly so that the dirt falls to the bottom of the stove using the special tool to 

be hooked to the handle (Arianna - Cortina - Sirmione models). For the Garda model, move the 2 side decorations.

- Remove the ash tray.

- Clean the bottom using an ash vacuum cleaner.

When cleaning is completed, refit all the previously removed components correctly.

Before starting work on the burner, disconnect the stove from the mains and turn the circuit 
breaker on the main panel to OFF.

Arianna 10/12

Cortina 9/10

Sirmione 9/10/12

Garda 9

Summary of Contents for Arianna 10

Page 1: ...Air heaters Instructions for models Arianna Cortina Garda Sirmione...

Page 2: ...is managed by an electronic board that keeps the burner always clean obtaining great efficiency and reliability of use The modulating operation varies according to the set ambient temperature and ther...

Page 3: ...5 Setting up the stove 28 8 6 Connecting the flue through the stove rear outlet 29 8 7 Connecting the flue on the side of the stove 29 8 8 Combustion air inlet 31 8 9 Minimum distance to position the...

Page 4: ...eleasing the Manufacturer from any liability Extraordinary maintenance must be carried out only by qualified personnel authorized by the Dealer or Manufacturer This pictogram refers to a situation of...

Page 5: ...e parts making up the equipment have not been damaged If this is the case inform the installer and or our customer service Do not leave any flammable containers or substances next to the stove comply...

Page 6: ...ught conditions unsuitable to the flue excessive fuel humidity or high ash residue in the combustion chamber can cause IGNITION FAILURES THAT MUST NOT BE CONSIDERED A FAULT IN THE PRODUCT In case of f...

Page 7: ...Draught conditions unsuitable to the flue excessive fuel humidity or high ash residue in the combustion chamber can cause ignition failures that must not be considered a fault in the product The compa...

Page 8: ...8 code 6118250 iss 10 2018 2 STOVE MODELS DEALT WITH IN THIS MANUAL Arianna 10 12 Cortina 9 10 Sirmione 9 10 12 Garda 9...

Page 9: ...If no anomaly is found the product can be installed Handle the equipment following the Manufacturer s instructions shown on the packaging and in this manual Use personal protection equipment all the t...

Page 10: ...ifting equipment must be kept free from people when the loads are lifted Shifting must always be vertical Use steel hooks chains or cables in perfect condition of a suitable material and capacity and...

Page 11: ...entral position to keep the centre of gravity of the load balanced Move the equipment carefully avoiding sudden movements If the transport is done with a forklift truck ensure this is strong enough to...

Page 12: ...chnical data label 4 Top discharge arrangement 5 Burner 6 Ash drawer 7 Explosion relief 8 Hearth door 9 Glass cleaning air adjuster 5 1 Arianna Cortina Garda Sirmione stoves 1 2 3 4 5 6 7 9 8 1 2 3 4...

Page 13: ...tat 11 Electrical outlet 12 Boiler thermostat 13 Flue gas discharge 14 Duct arrangement 10 13 14 13 12 11 12 11 13 13 10 10 11 13 14 13 12 10 13 13 12 11 10 13 14 13 12 11 12 11 13 13 10 Arianna 10 12...

Page 14: ...35 215 135 255 455 4 3 1 2 130 250 180 235 450 210 1210 560 590 4 4 1 3 2 4 4 1 3 235 590 480 185 285 355 500 560 195 305 234 336 1080 4 4 1 3 Arianna 10 12 Cortina 9 Cortina 10 12 Garda 9 1 2 3 4 Flu...

Page 15: ...6118250 iss 10 2018 550 470 1090 230 185 295 335 4 4 1 3 1210 180 235 450 210 130 250 550 560 4 4 1 2 3 Sirmione 9 Sirmione 10 12 1 2 3 4 Flue gas discharge Duct arrangement External air intake Hot ai...

Page 16: ...model The container is always in the top part of the appliance and is protected by a lid To load lift the lid and let the pellets slide into the container Find below an example with a stove model the...

Page 17: ...I RACCOMANDATI LEGGERE LE ISTRUZIONI D USO NUMERO DI SERIE EN 14785 2006 FREQUENZA NOMINALE TENSIONE NOMINALE POTENZA ELETTRICA NOMINALE CO AL 13 DI O2 NOMINALE CO AL 13 DI O2 RIDOTTA PPBT al 13 O2 Th...

Page 18: ...l h 30 max 30 max 30 max 16 max Pellet container capacity Kg 20 20 20 13 Heatable volume m3 120 420 max 120 350 max 120 350 max 80 240 max Smoke outlet diameter mm 80 80 80 80 Smoke temperature C 210...

Page 19: ...0 80 80 210 max 210 max 210 max 210 max V230 50Hz V230 50Hz V230 50Hz V230 50Hz 3 3 3 3 80 90 90 80 620 max 620 max 620 max 620 max see relative chapter see relative chapter see relative chapter see r...

Page 20: ...ameter of 4mm To get a correct mixture weigh each fuel with a set of scales having a 100g precision factor and mix them together in a container outside and not inside the stove container since it is n...

Page 21: ...e outlet tube must exceed 80 mm in diameter minimum dimensions have been complied with In case of installation near flammable or combustible walls keep a safety distance of at least 30cm on both sides...

Page 22: ...er or the environmental conditions are adverse The section of flue that gets out of the roof or remains in contact with the outside must be covered in flat tiles or anyway be very well isolated Any bu...

Page 23: ...SECTIONS They must be as vertical as possible with a constant section and a smooth internal surface to prevent the accumulation of head losses that would affect the draft required to discharge the smo...

Page 24: ...Inside the building simple wall tubes can be used but have the flue sections passing through the roof space or unheated areas well insulated Flue in uninsulated pre existing masonry in order to preve...

Page 25: ...tural draught For this reason we recommend you contact a specialized engineer to build the flue The costs for any modification in programming carried out by the service centres due to the incorrect in...

Page 26: ...with the legal regulations in force grounding is compulsory by law at no point should the supply cable reach an overtemperature of 50 C in comparison with the ambient temperature If direct connection...

Page 27: ...what you have received all deliveries are accompanied by transport documents containing the list and description of the items delivered Check all the components are present and undamaged contact the...

Page 28: ...ay attention not to damage its external parts Please pay attention to the distances mentioned above In positioning the stove make sure there are no objects underneath it that might affect its correct...

Page 29: ...the stove The stove can be connected to the previously installed flue by rotating the fume motor towards the side of the stove as shown in the following images A T can be connected directly to which a...

Page 30: ...pipe 5 and then mount the supplied pipe passage bracket 6 Reposition the stove back The figure on the side shows the sides with the pieces to be cut for the tube The side has to be taken apart the par...

Page 31: ...and install a grille at the start of the air intake on the outside to prevent foreign bodies from entering and affecting the correct operation of the unit The assembly is shown with one model of stove...

Page 32: ...hing it to the anchor holes 5 and fasten it with the screws Make the electrical connection on the motherboard 6 and activate the channelling function via the software menu Close the sides 7 8 and the...

Page 33: ...33 code 6118250 iss 10 2018 CROG MISC CIRC AMB 6 9 7 8...

Page 34: ...CONNECTION OF THE ROOM THERMOSTAT AND DUCTING THERMOSTAT OPTIONS It is possible to connect a room thermostat option that detects the temperature in the area where it is installed and that enables and...

Page 35: ...ed to be with a clean contact to avoid damaging the electronic board FUME FAN ENCODER HEATING FAN 1 FUME MOTOR CRUCIBLE AUGER MOTOR MIX AUGER MOTOR HEATING FAN 2 FUME Stove SAFETY THERMOSTAT PELLET LO...

Page 36: ...s reached the stove is kept ON at minimum power modulating mode YES The flashing LED shows that when the set temperature is reached the stove switches OFF modulating mode NO When OFF the LED shows tha...

Page 37: ...leted and all the above has been checked the system can be started for the first time Only a CSTHERMOS authorized engineer can do this also informing the customer on the operations to carry out to mak...

Page 38: ...to use for the stove operation is selected see relative chapter It is important to make sure that the same type of fuel has been added into the container Ventilation menu during operation this setting...

Page 39: ...o confirm SET to confirm To program another switch on period repeat the same operations setting the second timer PR02 SET to set the starting time modify the time SET to set the switching off time mod...

Page 40: ...fter flame ignition with fuel intermediate loading ON Burner normal operation phase with power variation from 1 to 6 Switching off Timed switching off phase associated to fuel interruption with crucib...

Page 41: ...uthorized engineer 31 room sensor Temperature probe interrupted or not connected call for an authorized engineer 40 auger sensor Fuel auger safety thermostat triggered clean the stove interior reset t...

Page 42: ...for use stated on the product label To clean the decorative stone parts use suitable dedicated detergents following the instructions for use on the prod uct label Always finish by drying it perfectly...

Page 43: ...ve the more obstinate residue Do not use aggressive or corrosive detergents i e hydrochloric muriatic sulphuric acid water jets Before starting work on the burner disconnect the stove from the mains a...

Page 44: ...drawer Once cleaning is complete the burner lid can be refitted and closed carrying out the same operations in reverse order After every cleaning check the wear of the hearth door seal Check every ti...

Page 45: ...stove using the special tool to be hooked to the handle Arianna Cortina Sirmione models For the Garda model move the 2 side decorations Remove the ash tray Clean the bottom using an ash vacuum cleane...

Page 46: ...use a fire To open and empty the ash collection drawer follow the procedure below The pictures are based on one stove model but the procedure is the same for the other models too 1 5 6 4 2 3 7 The ash...

Page 47: ...stion air inlet on the back of the stove at least once a month Remove any dirt as required Maintenance company CS THERMOS annual cleaning Check all mechanical elements are working correctly Check and...

Page 48: ...ether with urban waste but must be delivered to the appropriate collection centres or to the dealers that offer this service Disposing of the equipment separately allows avoiding possible negative con...

Page 49: ...49 code 6118250 iss 10 2018 12 NOTES...

Page 50: ...50 code 6118250 iss 10 2018...

Page 51: ...differences between this manual and the product you have received we apologize in advance for any inconvenience The total or partial reproduction of this manual without the Manufacturer s consent is...

Page 52: ...RL Societ Uninominale Via Padania 35 Z I 31020 San Vendemiano Treviso Italy TV Companies Register Tax code VAT No 03892500269 Fully paid up share capital 100 000 00 Tel 39 0438 62717 Fax 39 0438 45379...

Reviews: